3.1 Builders opening and surround (continuing)
If the builders' opening is constructed out of
-Ventilate the space above the appliance (min. 1000 mm2 ).
-Always fit the DC convection set.
-The plaster of the outside has to be resistant to a high temperature. Use therefore the plaster materials especially made for this, to prevent discoloring (min. 100 °C temperature resistant).
| Builders opening (mm) | Feeling | Silence | Whisper | Spectra | Cadra | Misty |
|
|
|
|
| Nova | Nova |
|
A | Opening width* | 960 | 960 | 780 | 780 | 680 | 710 |
B | Opening height* | 649 | 649 | 705 | 698 | 798 | 890 |
C | Opening depth* | 385 | 385 | 430 | 430 | 430 | 370 |
| Shelf dimensions |
|
|
|
|
|
|
| (combustible) |
|
|
|
|
|
|
D | Min. height shelf from |
|
|
|
|
|
|
| top frame | 350 | 350 | 350 | 350 | 350 | 350 |
E | Depth shelf max. | 150 | 150 | 150 | 150 | 150 | 150 |
| Dimensions (mm) |
|
|
|
|
|
|
F | Box width | 880 | 880 | 750 | 750 | 650 | 698 |
G | Box depth | 366 | 366 | 397 | 375 | 375 | 338 |
H | Box height | 636 | 636 | 714 | 715 | 815 | 879 |
I | Frame width | 1064 | 1064 | 815 | 794 | 694 | 740 |
J | Frame height | 678 | 678 | 720 | 703 | 803 | 905 |
K | Frame thickness | 47 | 20 | 16 | 30 | 30 | 144 |
L | Position flue |
|
|
|
|
|
|
| (behind frame) | 255 | 255 | 257 | 235 | 235 | 196 |
M | Position flue (from the |
|
|
|
|
|
|
| back side box) | 111 | 111 | 140 | 140 | 140 | 142 |
|
|
|
|
|
|
|
|
*the points A until C applies a tolerance from: |
|
– 0 mm and + 5 mm. | table 1 |
|
If the appliance is to be fitted against a wall with combustible cladding, the cladding must be removed from the area covered by the surround.
The minimum height from the top surface of the fire to the underside of any shelf made from wood or other combustible materials is as follows:
-For a shelf up to 150 mm deep – Minimum height = 350 mm (fig. 1).
-If the shelf depth is greater than 150 mm add 50 mm to the upper- clearance height for every 25 mm increase in shelf depth.
-Side clearance = Minimum distance from the side of the fire frame to combustible material = 150 mm.