Table Cadra Nova with interior MV150
Determine according to the table 4 the right total horizontal- and vertical length.
When meeting an X, and when the values are outside the table, the combination is not allowed. Normally the 30 mm flue restrictor is preinstalled.
UK/IRL
3.2 Flue requirements (continuing)
3.2.1 Terminal position
Verify if the required terminal position meets the local installation regulations regarding disturbance, good functioning and ventilation.
Effective height
Horizontal extension
| 0 | 1 | 2 | 3 | 4 | 5 | 6 |
0 | X | X | X | X | X | X | X |
0,5 | X | 0 | X | X | X | X | X |
1 | X | 30 | 0 | 0 | 0 | 0 | X |
2 | 40 | 30 | 0 | 0 | 0 | 0 | 0 |
3 | 40 | 40 | 30 | 0 | 0 | 0 | 0 |
4 | 50 | 40 | 40 | 30 | 0 | 0 | 0 |
5 | 50 | 50 | 40 | 40 | 30 | 30 | 0 |
6 | 50 | 50 | 50 | 40 | 40 | 30 | 0 |
7 | 60 | 50 | 50 | 40 | 40 | 40 | X |
8 | 60 | 60 | 50 | 50 | 50 | X | X |
9 | 60 | 60 | 60 | 50 | X | X | X |
10 | 65 | 60 | 60 | X | X | X | X |
11 | 65 | 65 | X | X | X | X | X |
12 | 65 | X | X | X | X | X | X |
Xcombination not allowed
0remove flue restrictor
Number is size in mm of the flue restrictor
table 4
interior Cadra Nova
(Also see: safety requirements).
Note:
The terminal must be located so that the outlet is not obstructed. If the flue terminal is located within 2 meters of a footway, path or where people could come into contact with it then a suitable terminal guard must be fitted.
Terminals located close to shared walkways, footpaths etc. could be subject to legal constraints and this should be pointed out to the customer before installation. If in any doubt about flue location advice should be sought from local building control, or if appliance- related, from the manufacturer including wherever possible a dimensioned sketch.
Misty with roundscreen
Determine according to the table 5 the right total horizontal- and vertical length.
When meeting an X, and when the values are outside the table, the combination is not allowed. Normally the 30 mm flue restrictor is preinstalled.
Horizontal extension
|
| 0 | 1 | 2 | 3 | 4 | 5 | 6 |
|
| |
| 0 | X | X | X | X | X | X | X |
|
| |
| 0,5 | X | 0 | X | X | X | X | X | X | combination | |
| 1 | X | 30 | 0 | 0 | 0 | X | X | |||
|
| not allowed | |||||||||
| 1,5 | 40 | 30 | 0 | 0 | 0 | 0 | 0 |
| ||
| 0 | remove flue restrictor | |||||||||
height | 2 | 40 | 30 | 0 | 0 | 0 | 0 | 0 | |||
|
| ||||||||||
3 | 40 | 40 | 30 | 0 | 0 | 0 | 0 |
| Number is size in mm | ||
|
| ||||||||||
| 4 | 50 | 40 | 40 | 30 | 0 | 0 | 0 |
| ||
Effective |
| of the flue restrictor | |||||||||
7 | 60 | 50 | 50 | 40 | 40 | 40 | X |
| |||
|
| ||||||||||
| 5 | 50 | 50 | 40 | 40 | 30 | 30 | 0 |
|
| |
| 6 | 50 | 50 | 50 | 40 | 40 | 30 | 0 |
|
| |
| 8 | 60 | 60 | 50 | 50 | 50 | X | X |
|
| |
| 9 | 60 | 60 | 60 | 50 | X | X | X |
|
| |
| 10 | 65 | 60 | 60 | X | X | X | X | table 5 | ||
| 11 | 65 | 65 | X | X | X | X | X | |||
| 12 | 65 | X | X | X | X | X | X | interior Roundscreen |
Avoid locating the terminal in close proximity to plastic materials such as gutters or other combustibles. If this is unavoidable then a suitable deflector should be made.
Some important requirements for a good functioning are:
The
0.5 meters off:
-Corners of the building.
-Below eaves.
-Balcony's etc. unless the duct is dragged to the front side of the overhanging part.
The roof mounted terminal has to be at a distance of at least 0.5 meters of the sides of the roof, excluded the ridge.