To calculate the thickness required for an alternate ma- terial to result in a K value of 0.84, first determine the alternate material’s K factor. This information should be available from your local building supply yard. Then, calculate the following formula:
(K factor |
|
|
|
| ||
of alternate |
| (Thickness of |
| (Required thickness | ||
material) |
|
| ||||
X | Wonderboard | = | ||||
|
| of alternate material) | ||||
(K factor of |
| required) |
| |||
|
|
| ||||
Wonderboard) |
|
|
|
|
Let’s use brick as an example, since it is a commonly used hearth material. Its K factor is 5.0.
(5.0) | X (7/16” [11 mm]) = 2.6” (65 mm) |
(0.84) |
That is, when using brick for the hearth extension, the brick must be a minimum of 2.6” (65 mm) thick.
Once you know the K factor of a given material, you can use this same formula to calculate its required thickness for approved hearth protection.
Flush with the Floor or Laid Over It?
Generally, it is easier to lay floor protectors over the fin- ished floor in existing homes. In new construction, flush installations are a popular alternative.
When placed over a finished floor, the floor protector extends completely under the ventilated plinth. (Fig.
32)The cabinet is elevated by an amount equal to the thickness of the floor protector so that the plinth and cabinet are at the same level. This is necessary for a proper fit between the WinterWarm front and the plinth. If you raise the cabinet more than 1” (25 mm), a corre- sponding increase in the height of the framed chase is required to retain adequate clearance.
When the floor protector is installed flush, the Winter- Warm cabinet rests on plywood shimming that brings it level with the finished floor. (Fig. 33)
Whichever method you choose, the floor protector must satisfy the requirements outlined above, and the 3” x 38” (76 x 965 mm) sheet metal spark protector strip (included) must be laid under the junction of the cabinet and the ventilated plinth.
WinterWarm Fireplace Insert or System
Ventilated | ||
Protector | ||
Plinth | ||
24ga. Galva- | ||
Spark | ||
nized Sheet | ||
Protector | ||
Metal | ||
Strip | ||
| ||
| Cabinet | |
Finished | Base | |
Floor |
| |
| ||
Plywood Shim | FP1109 |
Fig. 32 The components of a raised hearth. The floor protec- tor is placed over the finished floor and extends completely under the ventilated plinth.
Inlaid Floor | Ventilated | |
Protector | ||
Plinth | ||
| ||
24ga. Galva- |
| |
nized Sheet | Spark | |
Metal | Protector | |
| Strip | |
Finished | Cabinet | |
Floor | ||
| Base | |
FP1110 | ||
Plywood Shim |
Fig. 33 The components of a flush hearth. The floor protector is inlaid flush with the finished floor.
Important Reminders:
1.INSTALL ONLY AS ILLUSTRATED.
2.Elevating the cabinet requires a corresponding in- crease in the height of the chase to retain adequate clearances. Refer to the chase specifications on Page 20 and
3.The air inlet through the ventilated plinth must not be blocked.
4.A 3” x 38” (76 mm x 965 mm) strip of sheet metal (included in your Fireplace System) must be placed as a spark protector
2000941 | 25 |