INSTALLATION
THE KENSINGTON®
3-panel Door
Installation
1)Install the
Glass Door
Hook
OPTIONAL WALL
THERMOSTAT
A wall thermostat may be installed if desired, follow the wiring diagram below. FPI offers an optional programmable thermostat but any
Thermostat Wire Table
Recommended Maximum Lead Length
Thermostat
Wire Size | Max. Length | |
|
|
|
14 GA. | 50 | Ft. |
16 GA. | 32 | Ft. |
18 GA. | 20 | Ft. |
20 GA. | 12 | Ft. |
22 GA. | 9 | Ft. |
CAUTION
Do not connect the millivolt wall
thermostat wires to the 120V wires.
FINAL CHECK
Before leaving this unit with the customer, the installer must ensure that the appliance is fi ring correctly. This includes:
1)Clocking the appliance to ensure the correct fi ring rate (rate noted on label) at 15 minutes.
2)Ifrequired,adjustingtheprimaryairtoensure that the fl ame does not carbon. First allow the unit to burn for 15 min. to stabilize.
3)Check for proper draft.
CAUTION
Any alteration to the product that causes sooting or carboning that results in damage to the exterior facia is not the responsibility of the manufacturer.
2)Mount the
OPTIONAL REMOTE
CONTROL
Use the FPI Remote Control Kit approved for this unit. Use of other systems may void your warranty.
The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.
1)Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fi replace to that location. Use Thermostat Wire Table.
2)Connectthewiresasperthewiringdiagrams below.
CAUTION
Do not connect the millivolt
remote control wires for
to the 120V wires.
3)Install 3AAAalkaline batteries in transmitter and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation.
23 |