INSTALLATION

Diagram 3

Note: A noncombustible mantel may be installed at a lower height if the framing is made of metal studs covered with a noncombustible board.

VENTING

THE APPLIANCE MUST NOT BE

CONNECTED TO A

CHIMNEY FLUE SERVING A

SEPARATE SOLID FUEL

BURNING APPLIANCE.

This appliance is designed to be attached to two 3" (76mm) co-linear aluminium fl ex running the full length of the chimney. The fl ue length must be a minimum length of 8 ' (2.44m) and a maximum of 35' (10.7m). See chart below for minimum distances from roof. Periodically check that the vent is unrestricted.

Masonry chimneys may take various contours which the fl exible liner will accommodate. However, keep the flexible liner as straight as possible, avoid unnecessary bending.

TheAir Intake pipe must be attached to the inlet air collar of the termination cap.

Part #

Description

948-305

3" Flex - 35 ft.

946-529

Co-linear DV Vertical

 

Termination Cap

The Air Intake pipe must be attached to the inlet air collar of the termination cap.

FLUE LINER

INSTALLATION

1)Cut the fl ex liner as required.

2)Mark the end of one liner to indicate Inlet.

3)Connect the other end of the above liner to the inlet side of the termination adaptor, seal connection with high temperature silicone. Secure with gear clamp.

4)Connect the 2nd liner to the exhaust side of the adaptor, seal connection with high temperature silicone. Secure with gear clamp.

GAS CONNECTION

GAS CONNECTION WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

1)If the appliance is to be installed into an existing chimney system, thoroughly clean the masonry or factory built fi replace.

2)Theapplianceisprovidedwithanopeningon thelefthandsideofthecontrolcompartment. A3/8" NPT gas supply pipe must be brought near this inlet hole.

3)Locate the center point where the vent will pass through the chimney above the appliance. Move the appliance into the exact location where it is to be installed. Ensure that the Insert is level.

Alternate Approved Caps

980

Vertical Termination Cap

991

High Wind Cap

923GK

3" Co-linear Adaptor with fl ashing

In areas of consistently high winds, we recommend using the Simpson Dura-Vent System (923GK adapter and 991 high-wind cap).

5)Install fl ashing.

6)Insert both liners into chimney, passing through the damper opening.

7)Install termination cap.

8)Connect the marked end of the liner to the inlet collar of the vent connector plate marked with an "I", seal connection with high temperature silicone. Secure with gear clamp.

8

U32-4 FPI Direct Vent Gas Insert

Image 8
Contents U32 Gas Insert FPI GAS Insert To the NEW OwnerTable of Contents Safety Label Requirements MA Code CO DetectorInstallation Installation Checklist Minimum Fireplace DimensionsManufactured Mobile Home Additional Requirements Materials RequiredGAS Connection Flue Liner InstallationVenting GAS Pipe Pressure Testing GAS Insert Aeration SystemOptional Brick Panel Natural Gas PropaneLOG SET Installation Gas log kit contains the followingRegency Faceplate Trim Installation Rear burnerOptional Double Screen Doors Standard Flush DoorOptional Flush Trim Flush LouversBAY Louvers Optional BAY DoorOptional BAY Trim Removing Bay DoorConversion KIT #514-969 from NG to LP For P36D-1 / P36-4 OnlyInstallation of the DC Sparker Ground Wire from Kit Full Screen Doors Hinge Hampton Cast Faceplate Installation Ensure that Top and sides are AlignedHampton Cast Grill Installation U31 onlyKensington Front Installation Left SideKensington Panel Door Installation Glass Door Sub-Frame HookOptional Remote Control Thermostat Wire TableKensington Optional Wall ThermostatWiring Diagrams Electrical Grounding InstructionsFor Propane Units and Units Equipped with DC Spark Boxes Operating Instructions Maintenance Instructions Copy of Lighting Instruction PlateMaintenance FAN Maintenance Bay Glass RemovalValve Replacement Entrire assembly outInstall a new gasket and reinstall the valve assembly Shut off the gas supplyParts List Main AssemblyBurner Assembly & LOG SET Bay Door Flush Door402-918 Complete Faceplate Set Faceplate Assembly400-917 Hampton Cast Faceplate Assembly 187 189 188 194 203 201 207 195 205U32-4 FPI Direct Vent Gas Insert U32-4 FPI Direct Vent Gas Insert U32-4 FPI Direct Vent Gas Insert Warranty Warranty Limited LifetimeInstaller Please complete the following information