INSTALLATION

CLEARANCES AND HEIGHT REQUIREMENTS

INSTALLATION

The FP90 may be placed on or near construction materials. The combustion air kit, fire stop spacer and roof fl ashings (not chase fl ashings) may be placed directly on or against normal construction materials. The chimney requires a minimum 2" (51mm) clearance. A combustible mantle (to a depth of 10", 254mm) may be installed no closer than 18" (457mm) above the warm air vent or 55-1/2" (1410mm) from bottom of unit.

The chimney must be enclosed when installed in or passing through a living area where combustible material or people may come in contact with it. This is important to prevent possible personal injury or fi re hazard.

For any further information, please call your dealer. Special restrictions apply to the front and facing of the fi replace and nearby walls.

WARNING: If insulation is used, do not place the unit against it. Insulation or vapor barriers, if used, must be secured to assure insulation and vapor barriers remain in place and do not affect the required air spaces.

No Combustibles on Face of Unit.

Combustibles May Not Extend to Unit Face.

Do not notch wallboard around standoffs.

WARNING: Do not pack or fill required air spaces with insulation or other material. No material of any kind is allowed in these areas.

NOTES:

1)Do not insulate the chase cavity with blown or fi ll type insulation materials.

2)Local codes may not require fi restopping at the ceiling level for outside chase installations; however, it is recommended for safety and the reduction of heat loss.

3)We recommend that you insulate at least the fi rst fl oor of the chase to prevent heat loss.

4)Some local codes require 1 hour fire rating on one or all sides of fire chases. Check with your local authorities.

Max. 10" (254mm)

Depth of Mantel

center line

18" (457mm)

 

 

55-1/2" (1410mm) from bottom of unit

20" (508mm)

18" (457mm)

40" (1016mm)

Clearances to Combustibles

8

FPI FP90 Wood Fireplace

Image 8
Contents FP90 Wood Fireplace Regency Fireplace Product Table of Contents Safety Label Safety Label for FP90Installation Product DetailsPlease Retain this Manual for Future Reference Dimensions and Specifications Clearances and Height Requirements Installation of Nailing Strips Fireplace Enclosure FramingFraming Details Hearth ExtensionInstallation Components Before YOU StartChimney System Considerations Chase EnclosureInstallation Measurements / Framing Details On EAssembly Steps Installing STAND-OFFSInstalling the Chimney System SET the Regency FP90 Into PositionOffset Chimney Installation Special NotesInstalling Outside AIR KIT Elevation FT # of Elbows Above SEA LevelWiring the FP90 Installing Blower SystemsGravity AIR Feed KIT Option Internal Blower with Thermo-DiscCompleting The Facing Non-self Supporting, Thin Veneer Facades InstallationFinishing Regency FP90 Masonry Retainer Kit Option Finishing Details Completing The MantleGlass Secondary AIR Tube Installation Masonry Liner BricksAsh Drawer Kit Installation Safety PrecautionsASH Drawer KIT OptionFAN Installation DiagramMasonry Cover Plate Installation Installation Finishing Trim KIT Installation 60W xAREAStandoff Fireplace Screen Installation Installing the Handles on the ScreenRegency Louver Installation Installing the Top Louver Installing the Bottom LouverExcalibur Faceplate Installation Installing the Facing GuideExcalibur Accent KIT Installation Heatwave KIT not EPA Approved GeneralListings and Code Approvals InformationInstallation Minimum Framing ClearancesR90 / EX90 Models All ModelsOperation MaintenanceWiring Diagram Safety Guidelines Operating InstructionsOperating Instructions First FireMaintenance Plated Finishes Glass CleaningGlass Removal Replacement Door GasketParts List Parts LIST- Firebox & BodyParts LIST- BAFFLES, DOOR, Options FPI FP90 Wood Fireplace Warranty Warranty LifetimeInstaller Please complete the following information