INSTALLATION
|
|
|
|
|
|
|
| TABLE 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| Required Firestop, Radiation Shield, Or Attic Insulation Shield |
|
|
|
| ||||||||
|
| Model |
|
|
| 1st Floor |
|
|
| 2nd Floor into Attic |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CF Sentinal |
|
|
| Intermediate Joist Shield |
|
|
| Attic Insulation Shield |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Super Pro 2100+ |
|
|
| Attic Insulation Shield |
|
|
| Attic Insulation Shield |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Super Vent 2100+ |
|
|
| Attic Insulation Shield |
|
|
| Attic Insulation Shield |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Security S2100+ |
|
| Radiation Shield Fire Stop |
| Insulation Radiation Shield Attic Radiation Shield |
| ||||||||
| Oliver Macleod Project HT6000+ |
| Radiation Shield Fire Stop |
| Insulated Attic Radiation Shield |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Simpson DuraPlus HTC |
| Fire Stop Radiation Shield |
|
|
| Attic Insulation Shield |
|
| |||||||
|
| ICC Excel 2100 |
|
|
| Radiation Shield |
| Radiation Shield with Storm Collar |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TABLE 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Minimum Recommended Flue Height In Feet |
|
|
|
|
| |||||
|
|
|
| (Measured from the top of the solid fuel appliance) |
|
|
|
| ||||||||
| ELEVATION (FT) |
|
|
|
|
|
| # OF ELBOWS |
|
|
|
|
| |||
| ABOVE SEA LEVEL |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 0 |
|
| 2 x 15o | 4 x 15o |
| 2 x 30o |
| 4 x 30o | 2 x 45o |
| 4 x 45o |
| ||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 0ft - 1000ft |
| 12.00ft |
| 13.00ft | 14.00ft |
| 15.0ft |
| 18.00ft | 16.00ft |
| 20.0ft |
| ||
| (0m - 305m) |
| (3.66m) |
| (3.96m) | (4.27m) |
| (4.57m) |
| (5.49m) | (4.88m) |
| (6.10m) |
| ||
| 1000ft - 2000ft |
| 12.48ft |
| 13.52ft | 14.56ft |
| 15.6ft |
| 18.72ft | 16.64ft |
| 20.0ft |
| ||
| (305m | - 610m) |
| (3.80m) |
| (4.12m) | (4.44m) |
| (4.75m) |
| (5.71m) | (5.07m) |
| (6.10m) |
| |
| 2000ft | - 3000ft |
| 12.96ft |
| 14.04ft | 15.12ft |
| 16.2ft |
| 19.44ft | 17.28ft |
| 21.6ft |
| |
| (610m | - 914m) |
| (3.95m) |
| (4.28m) | (4.61m) |
| (4.94m) |
| (5.93m) | (5.27m) |
| (6.58m) |
| |
| 3000ft | - 4000ft |
| 13.44ft |
| 14.56ft | 15.68ft |
| 16.8ft |
| 20.16ft | 17.92ft |
| 22.4ft |
| |
| (914m - 1219m) |
| (4.10m) |
| (4.44m) | (4.78m) |
| (5.12m) |
| (6.14m) | (5.46m) |
| (6.83m) |
| ||
| 4000ft - 5000ft |
| 13.92ft |
| 15.08ft | 16.24ft |
| 17.4ft |
| 20.88ft | 18.56ft |
| 23.2ft |
| ||
| (1219m | - 1524m) |
| (4.24m) |
| (4.60m) | (4.95m) |
| (5.30m) |
| (6.36m) | (5.66m) |
| (7.07m) |
| |
| 5000ft | - 6000ft |
| 14.40ft |
| 15.60ft | 16.80ft |
| 18.0ft |
| 21.60ft | 19.20ft |
| 24.0ft |
| |
| (1524m | - 1829m) |
| (4.39m) |
| (4.75m) | (5.12m) |
| (5.49m) |
| (6.58m) | (5.85m) |
| (7.32m) |
| |
| 6000ft | - 7000ft |
| 14.88ft |
| 16.12ft | 17.36ft |
| 18.6ft |
| 22.32ft | 19.84ft |
| 24.8ft |
| |
| (1829m | - 2134m) |
| (4.54m) |
| (4.91m) | (5.29m) |
| (5.67m) |
| (6.80m) | (6.05m) |
| (7.56m) |
| |
| 7000ft | - 8000ft |
| 15.36ft |
| 16.64ft | 17.92ft |
| 19.2ft |
| 23.04ft | 20.48ft |
| 25.6ft |
| |
| (2134m | - 2438m) |
| (4.68m) |
| (5.07m) | (5.46m) |
| (5.85m) |
| (7.02m) | (6.24m) |
| (7.80m) |
| |
| 8000ft | - 9000ft |
| 15.84ft |
| 17.16ft | 18.48ft |
| 19.8ft |
| 23.76ft | 21.12ft |
| 26.4ft |
| |
| (2438m | - 2743m) |
| (4.83m) |
| (5.23m) | (5.63m) |
| (6.04m) |
| (7.24m) | (6.44m) |
| (8.05m) |
| |
| 9000ft - 10000ft |
| 16.32ft |
| 17.68ft | 19.04ft |
| 20.4ft |
| 24.48ft | 21.76ft |
| 27.2ft |
| ||
| (2743m | - 3048m) |
| (4.97m) |
| (5.39m) | (5.80m) |
| (6.22m) |
| (7.46m) | (6.63m) |
| (8.29m) |
|
INSTALLATION
INSTALLING THE
OUTSIDE AIR KIT
Combustion air is fed to the fi rebox through a connection on the rear lower left side of the unit. A free fl owing supply of air must be available to this opening at all times. Combustion air may be taken from inside the building if the local building code allows, but performance may suffer. Also, it must go through the 6" (152mm) duct to the connection on the left hand side.
Air drawn from the interior of the building will affect the performance of gas or oil furnaces, and exhaust fans and fan driven appliances. This may cause a negative pressure in the house allowing smoke to back into the home.
The preferred source of combustion air is from outside the building. If possible, install the kit on the wind loading side of the building not the leeward or (negative pressure) side.
Note: Do not obtain combustion air from attic, garage or other enclosed space.
1)Put the supplied insulated air duct to a nearby exterior wall. Maximum length of duct is 20ft (6.1m). Duct length should be kept to a minimum and as straight as possible. Note: 4 ft. only is supplied with unit. Termination should be in an area with good air fl ow.
2)Ensure that your air source is not close to automobile exhaust, gas meters or other vents.
3)Cut a 7" (178mm) hole through the wall and mount the outside air kit.
4)Attach the two ends of the duct (making sure not to damage the insulating cover) after installing the fl ange on the fi replace side. Duct must be secured by screws or
clamp.SideConnection
Exterior
Wall
Outside
Metal
InsulatedMetal
Vent
6” Duct
Outside Air Inlet must be 6 ft. (152mm) below
the chimney termination point
FPI FP90 Wood Fireplace | 15 |