Regency FP90 installation manual Fireplace Enclosure Framing, Installation of Nailing Strips

Page 9

INSTALLATION

INSTALLATION OF NAILING STRIPS

1)Assemble 3 Nailing Strip Spacer Plates to the left and the right Nailing Strips as shown below.

Left Nailing Strip

Nailing

Spacer

Right Nailing

Strip

x 12

2)Mount Nailing Strips left, right and top to the positions indicated below.

FIREPLACE

ENCLOSURE FRAMING

As per the diagram, the framing of the main enclosure should not infringe on the area above the fi replace to the ceiling level. The rear and side walls as well as the face above the fi replace must not extend into the area above the unit. The only structure allowed above the unit is on the stand-offs at the front of the unit supporting the header.

The enclosure walls can be framed using any suitable material (2x4 - 2x6 studs, plywood, gyproc, etc.), Normally, framing will be set back to allow Non-Combustible Material to be flush with the front of the fireplace.

There is framing only on the front of the unit. When framing in the header (directly above the fi replace) DO NOT bring any combustible material lower than the top of the stand-offs. Framing header may be positioned on end directly on top of the front fi replace stand-offs. Be sure to seal the space between the fi replace and the enclosure above and on either side of the unit with Wonderboard, Durock or other similar non-combustible sheeting to prevent hot air from entering the enclosure.

C A U T I O N : O N LY N O N - C O M B U S T I B L E M AT E R I A L LIKE EXPANDED METAL OR CONCRETE BOARDS SUCH AS WONDERBOARD AND DUROCK, ETC. MAY BE USED IN THE SPACE BETWEEN THE UNIT AND THE FRAMING IN FRONT OF THE UNIT ONLY.

INSTALLATION

Right Nailing Strip

Top Nailing

Strip

44"

50-3/4"

(1289mm)

Note: If the fireplace is being cantilevered through an outside wall, the entire enclosure (floor, wall and false

(1118mm)

Framing Specifi cations

Left

Nailing

Strip

934 " [248mm]

x 9

ceiling) up to the first ceiling level must be completely insulated and vapor sealed and sheathed, to avoid transfer of cold air through the fireplace when not in use.

3141 " [795mm]

8121 " [2072mm]

5758 " [1465mm]

NOTE:

Nailing Strips are adjustable to allow for correct offset from the front of the fireplace for your current application.

There are two adjustments to allow for maximum offset (1" , 25mm recessed from front of fireplace or1.25",32mm extendingpastfrontoffireplace). The Nailing Strip Spacers can be adjusted by loosening the two screws securing them to the Nailing Strips. The Nailing Strips can also be moved forward and back by adjusting the screws that mount them to the fi replace.

1153

" [2930mm]

8

 

60 " [1524mm] CHASE

1334 " [348mm]

1334 " [348mm]

44 " [1118mm]

1458 " [370mm]

28 " [710mm]

18 " [457mm]

Building Structures Cannot Encroach on Chase

FPI FP90 Wood Fireplace

9

Image 9
Contents FP90 Wood Fireplace Regency Fireplace Product Table of Contents Safety Label for FP90 Safety LabelProduct Details InstallationPlease Retain this Manual for Future Reference Dimensions and Specifications Clearances and Height Requirements Fireplace Enclosure Framing Installation of Nailing StripsHearth Extension Framing DetailsBefore YOU Start Installation ComponentsChimney System Considerations Chase EnclosureOn E Installation Measurements / Framing DetailsInstalling STAND-OFFS Assembly StepsInstalling the Chimney System SET the Regency FP90 Into PositionSpecial Notes Offset Chimney InstallationElevation FT # of Elbows Above SEA Level Installing Outside AIR KITInstalling Blower Systems Wiring the FP90Gravity AIR Feed KIT Option Internal Blower with Thermo-DiscNon-self Supporting, Thin Veneer Facades Installation Finishing Regency FP90Completing The Facing Masonry Retainer Kit Option Completing The Mantle Finishing DetailsMasonry Liner Bricks Glass Secondary AIR Tube InstallationSafety Precautions Ash Drawer Kit InstallationASH Drawer KIT OptionDiagram FAN InstallationMasonry Cover Plate Installation Installation 60W xAREA Finishing Trim KIT InstallationStandoff Installing the Handles on the Screen Fireplace Screen InstallationInstalling the Top Louver Installing the Bottom Louver Regency Louver InstallationInstalling the Facing Guide Excalibur Faceplate InstallationExcalibur Accent KIT Installation General Heatwave KIT not EPA ApprovedListings and Code Approvals InformationMinimum Framing Clearances InstallationR90 / EX90 Models All ModelsMaintenance Wiring DiagramOperation Operating Instructions Safety GuidelinesOperating Instructions First FirePlated Finishes Glass Cleaning MaintenanceGlass Removal Replacement Door GasketParts LIST- Firebox & Body Parts ListParts LIST- BAFFLES, DOOR, Options FPI FP90 Wood Fireplace Warranty Lifetime WarrantyInstaller Please complete the following information