Mitsubishi G-50A, MN Converter manual Connecting information Trouble, Operation Monitor Trouble

Page 66

A[**]appears in the unit address button for

Interference caused an non-existing unit

Wait a moment and then click on the

a unit that does not exist.

to appear.

address button for the same unit again.

 

 

The[**] display will disappear.

 

 

 

A[??]appears in the address button.

There is a unit that is not compatible with

Refer to the explanation on terminology in

 

the maintenance tools.

help.

 

 

If there is no explanation, the unit is not a

 

 

compatible type.

 

 

 

Address searching takes 3 minutes or

The port required for communication is

In this case, the communication

more per set. (G-50 connection)

being protected by the Firewall checking

transmitted from G-50 may not partially be

 

function of Windows or anti-virus

received. Please remove the check mark

 

software.

on the Firewall function of the necessary

 

 

port. (For detail, please refer to Page 57.)

 

 

(If the version of G-50 is more than 2.50,

 

 

only [IC] can be searched, even if it uses

 

 

FIREWALL. However, [OC] reference

 

 

cannot be performed. Moreover, since

 

 

other functions cannot operate normally,

 

 

please be sure to remove a check.)

 

When a maintenance tool is not ended

In this case, please perform "Stop mail

 

normally, G-50 will be in a data resending

communication" of 3.4 (2), and start a

 

state, and LAN communication will

maintenance tool again after waiting

 

increase.

about 15 minutes.

 

The version of G-50 is old.

A recommendation version is 2.50 or

 

 

more.

 

 

 

Connecting information Trouble

Trouble

Cause

Repair

 

 

Cannot switch to connection information

A unit other than an outdoor unit (OC) has

Refer to 3.6.1

screen.

been selected.

 

The connection data display does not

An operating SC other than remote

Click on remote control.

appear when the operating system SC is

control has been clicked.

Monitoring of connection data cannot be

clicked.

 

done from operating SC other than

 

 

remote control.

 

 

 

Operation Monitor Trouble

Trouble

Cause

Repair

 

 

 

The monitor display screen on the

Because of the increased re-transmission

Please take a countermeasure against

operation monitor has red characters.

process work due to abundant

the communication noise source in this

 

communication noise, data may not be

case.

 

monitored fully within the rated cycle.

 

All of the characters on the monitor

There is no answer from the unit.(Cannot

Error with unit.

display for some units are red.

communicate with the unit.)

Refer to the service handbook for that

 

 

unit.

The message of ” G50 can't Connect to

The dial-up router is not connected. Or

By referring to Instruction Manual of

SMTP Server !

connected but incorrectly.

Dial-up router, connect or set correctly.

or G-50 Date Setting is wrong !!

The default gateway of G-50A is not set.

Set correctly by using the G-50A initial

Continue ?” is displayed at remote

monitor setting.

 

setting tool. (Refer to Instruction Manual

 

 

of G-50A initial setting tool.)

 

The incorrect display of the receiver

Set the correct mailing address.

 

address is pointed out by SMTP.

 

 

The Monitor Finish Date is older than the

Set the monitor finish date correctly.

 

current date/time of G-50A.

(However when connecting to G-50A in a

 

 

region with a time differential, set it by

 

 

considering the time in that place.)

A message of " Monitor data size is very

The memory capacity to store data is

Move to Offline Screen, and delete

65

Image 66
Contents Mitsubishi Operating ManualIntroduction of Maintenance Tools ForewordOn-Line Monitorvia MN converter Case for remote connection Dialup connection mode On-Line Monitorvia G-50Remote access method Wide area access modeImage of the Operation monitor mail communication mode Off-Line MonitorRequired Operating Environment Hardware RequirementsRequired Materials Setting up the database InstallationSetting Up the Maintenance Tools New setup MinutesSetting up the Maintenance Tools Uninstalling the Maintenance Tool Running Maintenance Tool UpgradeEnding the Maintenance Tool Upgrade the DatabaseUninstalling the Maintenance Tools RE Change of computer name on PCWide area access mode Starting the Maintenance ToolNormal mode Starting and Ending the ApplicationCase for remote connection Page Click on Line will be disconnected Starting the On-Line MonitorG-50 connection Case for local connectionCase for remote connection Dialup Next Remote Monitor screen is displayedCase for remote connection E-mail Address book Using the Wide area access mode Starting the Off-Line MonitorOnline Connection Creating the Area name folderCreating the Customer name folder Setting the Air conditioning system name Setting screen of air conditioning systemAbove Setting of Com port Other settingMail setting of maintenance tool PC Offline AnalyzeEnding the Off-Line Monitor Open the Main ScreenOpen the Off-line Analyze Screen Terms for Each Section Design of ScreenOperating Method On-Line Monitor Operating Method On-Line Monitor Screen TransferAddress Search Method Selection Function ChartAddress Search Method Automatic SearchAutomatic Searching Manual SearchingSearching Screen will appear Refer to 3.6 Connecting Information 3.6.2 2 Menu Bar Main ScreenScreen Transfer Operation Connecting InformationFunction Selection Operations Items Performed Here4Momentarily, the Connecting Information Screen Screen Functions and OperationClick on Term and Explanation of Terminology Screen appear Operation Monitor Message Monitoring! Please wait for a moment. will appearMomentarily, the Operation Status Monitor Screen will appear Screen Functions and Operations 1Operation ButtonsAbout LM Adapter Introduction to the screen Tens digit Trend graph Ending the graph Screen function and operationMalfunction Log Message Monitoring. Please wait for a moment. will appearMessage Close the malfunction log display? will be displayed Optional Setting Self-Diagnosis MonitoringCommand Screen and return to the Optional Setting Screen Sending CommandMonitoring of Pre-error Data Refer to 3.6 Connecting Information 3.6.2 2Menu BarDate / Time Setting Main ScreenOperation Control Screen Functions and Operation Indoor unit, Lossnay unitScreen Functions and OperationBC Controller Free contact of indoor unit Starting of this functionMonitoring of contact status Operation of output contact Termination of this functionOff-Line Monitor Screen Transfer Monitoring of Pre-error DataOff-Line Monitor Operating Method Title ScreenSystem Information Monitor Function common for each screen Filing operationOff-Line Analyzing Operation Status Monitor ScreenMonitor Screen. Refer to c Graph Trend Graph ScreenPage Mail Server Setting Check mailSystem Information Monitoring of Pre-error Data 4.5.1 Off-Line Analyzing Export Function common for each screen Filing operationDelete Data ImportText Convert Monitor Data information convertRight-clicking menu Offline Analyze on Wide area access mode System Information Data Pre-error DataFile Names Operating Status Monitor DataHow to change setting of Firewall How to Change Setting of Firewall for Windows XPE-Mail mode and MN converter connection, it is not related II In the case of G-50 Network Remote Connection Dialup Case of Windows XP Service Pack Page Page Trouble with Main Screen Troubleshooting?Trouble When Installing or Starting Trouble Cause RepairConnecting information Trouble Operation Monitor TroubleOperation Monitor Mail Communication Mode Trouble Malfunction Log TroubleSpecific troubles induced by E-mail connection mode Free contact of indoor unit TroubleOff-Line Monitor Trouble1 Off-Line Monitor Trouble2