North Star 864 HH Massachusetts Requirements, Requirements for the Commonwealth of Massachusetts

Page 8

8

Installation (for qualified installers only)

Massachusetts Requirements

N O T E: The following requirements reference various Massachusetts and national codes not contained in this document.

Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8)feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

--Detailed instructions for the installation of the venting system design or the venting system components; and

--A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

--The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

--The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See “Gas Line Requirements” on page17 for additional Massachusetts requirements.

Travis Industries

4070201

100-01182_002

Image 8
Contents 864 HH Fireplace Overview Listing DetailsTable of Contents Safety Precautions Safety WarningsSafety Precautions Dimensions Installation OptionsHeating Specifications Installation Overview Recommended Installation ProcedurePacking List Additional Items RequiredMassachusetts Requirements Requirements for the Commonwealth of MassachusettsTop Vent or Rear Vent Configuration Converting Fireplace to Top Vent ConfigurationConverting the Fireplace to Top Vent Do not Over Tighten ScrewsRaised Fireplaces Fireplace Placement RequirementsClearances Minimum Framing Dimensions Rear Vent Configuration Minimum 49 Fireplace Enclosure HeightMinimum Framing Dimensions Top Vent Configuration Nailing Brackets Corner Installations Rear Vent Configuration Corner Installations Top Vent Configuration Gas Line Requirements FuelGas Line Connection Gas Inlet PressureGas Line Location Left Side Gas Inlet preferredElectrical Connection required Wall Switch Installation Wall Switch or Thermostat InstallationWiring Diagram Millivolt System Altitude Considerations Vent RequirementsVent Clearances Vent Installation Approved VentRestrictor Position Approved Vent ConfigurationsExhaust Restrictor Adjustment Intake Restrictor Adjustment Diffuser Plate Adjustment Diffuser Side ViewExhaust Restrictor Removal 0feet 5feet 22 max Feet 10feet 15feet Rear Vent Configuration with Vertical Termination Top Vent Configuration with Horizontal Termination Feet 21 max 5feet 10feet 15feetTop Vent Configuration with Vertical Termination May use 8 or 6-5/8 Diameter vent see page for DetailsTermination Requirements Hearth Requirements Floor Mounted FireplacesDrywall Installation Facing RequirementsOptional Faceplates Sizing Chart Facing OverviewFront View Raised Fireplace with no Hearth Front View Thick Facing with Fireplace Xtrordinair FPX Arched Faces Thick Facing Installation Side Floor-Mounted Fireplace with HearthMantel Requirements Side View Installation Example Build-In with Horizontal Termination Horizontal Termination Section FirestopPilot Flame Inspection Steps for Finalizing the InstallationStarting the Pilot Flame Finalizing the Installation for qualified installers only Air Shutter AdjustmentGlass Frame Removal and Installation Based upon the face being used, eitherFinalizing the Installation for qualified installers only Fireback and Grate Installation Right Log Installation Log Set InstallationRear Log Installation Left Log Installation Right Twig Installation Verify Rear LOG PositionEmber Installation Center Twig InstallationFront Twigs Installation LP Conversion Instructions Follow the directions below to replace the orifices Slotted Screwdriver Or T-20 Torx Grill Installation Upper Grill InstallationOption # 2 Remote Thermostat Remote Control Receiver Installation 2 OptionsOption # 1 Remote Thermostat Special Instructions for 864 HH Extra Room Power Heat Duct skuNew Wire Hook-Up Installation Overview Length =Duct Installation Instructions LengthFloor Mounting Attach the grill and wall adapter, if necessary Wiring Diagram -864TRV Operating Instructions OFFAccent Light Installation sku Optional Equipment for qualified installers only Optional Wall-Mounted Rheostat Accent Light OperationOptional Equipment for qualified installers only 68Index Index