Outdoor Air Shutdown Differential (SH1 - SH3)

The outdoor air shutdown differential parameter is the number of degrees below parameters F5, F10 and F15 the outdoor air temperature must go before the boiler will respond to a SH demand. These parameters can be changed by the installer by accessing parameters F6, F11 and F16. The temperature range of this parameter is 0°F (0°C) to 90°F (50°C). The default value is 10°F (6°C).

Shift Reset Curve (SH1 - SH3)

There is a shift reset curve for each outdoor reset. The shift reset curve parameter shifts the actual set point above the calculated set point the number of degrees in this parameter. These parameters can be changed by the installer by accessing parameter F7, F12 and F17. The temperature range of this parameter is -17°F (-27°C) to 18°F (-8°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).

Boost Temperature

If a SH demand lasts longer than the programmed time delay setting (F19) and there have been no DHW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or the maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing parameter F18. The temperature range of this parameter is 0°F (0°C) to 25°F (-4°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).

Boost Time

The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature set point will be increased. This parameter can be changed by the installer by accessing parameter F19. The time range for this parameter is 0 minute to 50 minutes. The default value is 0 minutes.

G: Anti-Cycling

Anti-Cycling Time

Once a SH demand has been satisfied, a set amount of time must elapse before the control will respond to a new SH demand. The control will block the new heat demand and anti-cycling will be shown in the display until the time has elapsed or the water temperature drops below parameter G2. This parameter can be changed by the installer by accessing parameter G1. The time range for this parameter is 0 minutes to 10 minutes. The default value is 1 minute.

Anti-Cycling Override Differential

The control will bypass the anti-cycling time if the water temperature drops too quickly. The control will use the water temperature the boiler was at when it shut off as the starting point. If the temperature drops below the temperature parameter the control will abort anti-cycling and allow the boiler to fire. This parameter can be changed by the installer by accessing parameter G2. The temperature range of this parameter is 0°F (0°C) to 54°F (30°C). The default value is 10°F (6°C).

Ramp Delay (Enable / Disable)

This parameter allows the installer to enable or disable the SH ramp delay by accessing parameter G4.

23

Image 23 Contents
Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessDisplay panel parameter access General Parameter tableSettings Reset Notification Software Version Temperature units C / F Viewable and changeable control parameters Date and TimeFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling BMS Thermostat Input Active / Inactive SH Ramp DelayControl modes Controlling SensorMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Wire Color R/BK and Y Wire Color G and YDHW Pump NoisyNo Pump Boiler Pump System PumpFlow Switch/LWCOFlame Fail Ign Anti-cyclingFan Low Auto ResetFlame Sequence High LimitFan Speed High GV/RelayFail Fan HighHigh Flue Temp HighDelta T High Outlet TempParameters Progr Service BlkRem Ctrl Flt Write EEProm Watch Dog ErrorNo Error Stored Low 24 vacGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModels 601 Gas valve adjustment procedureModel Page