Lochinvar 400 - 801 service manual Outdoor Reset

Page 22

1Service

F: Outdoor Reset

The option of controlling up to three (3) different outdoor resets for low outdoor temperatures is available.

Low Outdoor Temperature

When the outdoor air temperature drops below this point, the water temperature will be at parameters F3, F8 and F13 (FIG. 1-1). However, if the user set point is set lower, the water temperature will be limited by the user set point instead. This parameter can be changed by the installer by accessing parameter F1. The temperature range of this

parameter is

-40°F (-40°C) to 104°F (40°C). The default

value is 25°F

(-4°C).

High Outdoor Temperature

When the outdoor air temperature rises to or above this point, the water temperature will be at parameters F4, F9 and F14 (FIG. 1-1). This parameter can be changed by the installer by accessing parameter F2. The temperature range of this parameter is -40°F (-40°C) to 104°F (40°C). The default value is 70°F (21°C).

Service Manual

SH1 - SH3 Set Point at Low Outdoor Temperature

When the outdoor air temperature drops below this point, the water temperature will be at this setting (FIG. 1-1). However, if the user set point is set lower, the water temperature will be limited by the user set point instead. These parameters can be changed by the installer by accessing parameters F3, F8 and F13. The temperature range of this parameter is -40°F (-40°C) to 104°F (40°C). The default value is 25°C (-4°C).

SH1 - SH3 Set Point at High Outdoor Temperature

When the outdoor air temperature rises to or above this point, the water temperature will be at this setting (FIG. 1-1). These parameters can be changed by the installer by accessing F4, F9 and F14. The temperature range of this parameter is -40°F (- 40°C) to 104°F (40°C). The default value is 70°F (21°C).

Outdoor Air Shutdown (SH1 - SH3)

When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). These parameters can be changed by the installer by accessing parameters F5, F10 and F15. The temperature range of this parameter is 32°F (0°C) to 104°F (40°C). The default value is 70°F (21°C).

Figure 1-1Outdoor Air Reset Curve

22

Image 22
Contents Models 400 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler Maintenance What is in this manual?Service TroubleshootingService Near boiler pipingKnight XL display Navigation DialControl inputs LOW Voltage Connection BoardSmart Control Module Control outputsHow the boiler operates Access modesGeneral Operation How the control module operatesOperation Display From previous page Sequence of Operation Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Parameter table GeneralSettings Reset Notification Date and Time Temperature units C / FViewable and changeable control parameters Software VersionData Logging Temperature SettingsFunctions DHW Settings Outdoor Reset Anti-Cycling Controlling Sensor SH Ramp DelayControl modes BMS Thermostat Input Active / InactiveCascade Offset Minimum On/Off TimeCirculation pumps Service Notification Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check expansion tank Flue vent system and air pipingCheck water system Check boiler relief valveCheck control settings Check ignition ground wiringCheck all boiler wiring Inspect ignition and flame sense electrodesReview with owner Check flame signalCleaning boiler heat exchanger Model Kit Part Component Number DescriptionCheck control module fuses TroubleshootingBefore troubleshooting Check the followingOperation No DisplayNo Burner Unit Does NotWire Color R/BK and Y Wire Color G and Y Checking temperature sensorsTemperature Resistance Resistance TemperatureBoiler Pump System Pump NoisyNo Pump DHW PumpSwitch/LWCO FlowAnti-cycling Flame Fail IgnHigh Limit Auto ResetFlame Sequence Fan LowFan High GV/RelayFail Fan Speed HighOutlet Temp Flue Temp HighDelta T High HighRem Ctrl Flt Service BlkParameters Progr Low 24 vac Watch Dog ErrorNo Error Stored Write EEPromOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureModel Gas valve adjustment procedureModels 601 Page