F: Outdoor Reset
The option of controlling up to three (3) different outdoor resets for low outdoor temperatures is available.
Low Outdoor Temperature
When the outdoor air temperature drops below this point, the water temperature will be at parameters F3, F8 and F13 (FIG.
parameter is | |
value is 25°F |
High Outdoor Temperature
When the outdoor air temperature rises to or above this point, the water temperature will be at parameters F4, F9 and F14 (FIG.
Service Manual
SH1 - SH3 Set Point at Low Outdoor Temperature
When the outdoor air temperature drops below this point, the water temperature will be at this setting (FIG.
SH1 - SH3 Set Point at High Outdoor Temperature
When the outdoor air temperature rises to or above this point, the water temperature will be at this setting (FIG.
Outdoor Air Shutdown (SH1 - SH3)
When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). These parameters can be changed by the installer by accessing parameters F5, F10 and F15. The temperature range of this parameter is 32°F (0°C) to 104°F (40°C). The default value is 70°F (21°C).
Figure 1-1 Outdoor Air Reset Curve