Service Manual
3Troubleshooting (continued)
Table
FAULT | DESCRIPTION |
| CORRECTIVE ACTION |
| ||||
|
|
| ||||||
|
| • Inspect the heat exchanger. Reference page 32 of | ||||||
|
| this manual for the procedure on how to clean the flue | ||||||
|
| side of the heat exchanger. |
|
|
| |||
|
| • Inspect the flue sensor and associated wiring. | ||||||
|
| Measure the resistance of the flue sensor and | ||||||
Flue Temp High | The stack temperature has exceeded the set | compare to Table | ||||||
parameters for the boiler. | Replace the sensor if necessary. |
|
| |||||
|
| • Verify that the vent/air intake pipes are properly | ||||||
|
| installed and that there are no obstructions. |
| |||||
|
| • Replace the main control board. |
|
| ||||
|
|
| ||||||
|
| • Verify that the system is full of water and that all air | ||||||
|
| has been properly purged from the system. |
| |||||
|
| • Verify that the boiler is piped properly into the heating | ||||||
|
| system. Refer to Section 6 - Hydronic Piping of the | ||||||
|
| Knight | XL | Installation | and | Operation | Manual | |
|
| for the proper piping methods for the Knight XL boiler. | ||||||
|
| • Check for 120 vac to the boiler pump motor on a call | ||||||
Delta T High | The temperature rise across the heat | for heat. If voltage is not present, check the wiring | ||||||
back to the main control board. Replace the main | ||||||||
| exchanger has exceeded the set parameters | |||||||
| control board if necessary. |
|
|
| ||||
| for the boiler. |
|
|
| ||||
|
|
|
|
|
|
| ||
|
| • If 120 vac is present on a call for heat and the boiler | ||||||
|
| pump is not operating, replace the pump. |
| |||||
|
| • Verify that the boiler pump is set to the proper speed | ||||||
|
| or that the pump is the proper size. Reference | ||||||
|
| Section | 6 | - Hydronic | Piping of the | Knight | ||
|
| XL Installation and Operation Manual for boiler | ||||||
|
| pump specifications. |
|
|
| |||
|
|
| ||||||
|
| • Verify that the system is full of water and that all air | ||||||
|
| has been properly purged from the system. |
| |||||
|
| • Verify that the boiler is piped properly into the heating | ||||||
|
| system. Refer to Section 6 - Hydronic Piping of the | ||||||
Outlet Temp |
| Knight | XL | Installation | and | Operation | Manual | |
| for the proper piping methods for the Knight XL boiler. | |||||||
High | Outlet water temperature has exceeded the |
|
|
|
|
|
| |
| maximum outlet water temperature. | • Check for 120 vac to the boiler pump motor on a call | ||||||
|
| for heat. If voltage is not present, check wiring back | ||||||
|
| to the main control board. Replace the main control | ||||||
|
| board if necessary. |
|
|
| |||
|
| • If 120 vac is present on a call for heat and the boiler | ||||||
|
| pump is not operating, replace the pump. |
| |||||
|
|
|
|
|
|
|
|