Lochinvar 400 - 801 service manual Flue Temp High, Delta T High, Outlet Temp

Page 41

Service Manual

3Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

 

• Inspect the heat exchanger. Reference page 32 of

 

 

this manual for the procedure on how to clean the flue

 

 

side of the heat exchanger.

 

 

 

 

 

• Inspect the flue sensor and associated wiring.

 

 

Measure the resistance of the flue sensor and

Flue Temp High

The stack temperature has exceeded the set

compare to Table 3-2D on page 35 of this manual.

parameters for the boiler.

Replace the sensor if necessary.

 

 

 

 

• Verify that the vent/air intake pipes are properly

 

 

installed and that there are no obstructions.

 

 

 

• Replace the main control board.

 

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight

XL

Installation

and

Operation

Manual

 

 

for the proper piping methods for the Knight XL boiler.

 

 

• Check for 120 vac to the boiler pump motor on a call

Delta T High

The temperature rise across the heat

for heat. If voltage is not present, check the wiring

back to the main control board. Replace the main

 

exchanger has exceeded the set parameters

 

control board if necessary.

 

 

 

 

for the boiler.

 

 

 

 

 

 

 

 

 

 

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

 

• Verify that the boiler pump is set to the proper speed

 

 

or that the pump is the proper size. Reference

 

 

Section

6

- Hydronic

Piping of the

Knight

 

 

XL Installation and Operation Manual for boiler

 

 

pump specifications.

 

 

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

Outlet Temp

 

Knight

XL

Installation

and

Operation

Manual

 

for the proper piping methods for the Knight XL boiler.

High

Outlet water temperature has exceeded the

 

 

 

 

 

 

 

maximum outlet water temperature.

• Check for 120 vac to the boiler pump motor on a call

 

 

for heat. If voltage is not present, check wiring back

 

 

to the main control board. Replace the main control

 

 

board if necessary.

 

 

 

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

 

 

 

 

 

 

 

41

Image 41
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Service What is in this manual?Maintenance TroubleshootingNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleGeneral Operation Access modesHow the boiler operates How the control module operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessDisplay panel parameter access General Parameter tableSettings Reset Notification Viewable and changeable control parameters Temperature units C / FDate and Time Software VersionFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling Control modes SH Ramp DelayControlling Sensor BMS Thermostat Input Active / InactiveMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check boiler relief valveCheck all boiler wiring Check ignition ground wiringCheck control settings Inspect ignition and flame sense electrodesCleaning boiler heat exchanger Check flame signalReview with owner Model Kit Part Component Number DescriptionBefore troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does NotTemperature Resistance Checking temperature sensorsWire Color R/BK and Y Wire Color G and Y Resistance TemperatureNo Pump NoisyBoiler Pump System Pump DHW PumpFlow Switch/LWCOFlame Fail Ign Anti-cyclingFlame Sequence Auto ResetHigh Limit Fan LowFail GV/RelayFan High Fan Speed HighDelta T High Flue Temp HighOutlet Temp HighParameters Progr Service BlkRem Ctrl Flt No Error Stored Watch Dog ErrorLow 24 vac Write EEPromGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply PressureModels 601 Gas valve adjustment procedureModel Page