Lochinvar 400 - 801 service manual Flame Sequence, Auto Reset, High Limit, Fan Low, Fan Speed Low

Page 39

Service Manual

3Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flame

 

 

 

 

 

 

 

 

 

 

 

Sequence

 

• Check supply voltage for proper polarity.

 

 

 

 

(will require a manual

 

 

 

 

 

 

• Check external wiring for voltage feedback.

 

 

reset once the condition

 

 

 

The flame detector circuit is seeing a flame

• Check the flame rod and make sure it is clean.

 

 

has been corrected.

signal while no flame is present.

 

 

Press the RESET button

• Check the internal wiring for bad connections.

 

 

on the SMART

 

 

 

 

• Replace main control board.

 

 

 

 

 

 

SYSTEM display to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight

XL

Installation

and

Operation

Manual

 

 

for the proper piping methods for the Knight XL boiler.

 

 

• Check 120 vac to boiler pump motor on a call for

 

 

heat. If voltage is not present, check wiring back to

 

 

the main control board.

 

 

 

 

 

 

 

 

 

• Replace the main control board if necessary.

 

 

Auto Reset

The outlet water temperature has exceeded

• If 120 vac is present on a call for heat and the boiler

the setting of the automatic reset high limit.

pump is not operating, replace the pump.

 

 

 

 

High Limit

 

 

 

 

 

 

 

 

 

 

 

• If the system pump is a variable speed pump, ensure

 

 

 

 

that the system flow is not less than the boiler flow.

 

 

• If operating on something other than an outlet sensor,

 

 

check temperature setting of the main control board.

 

 

• If the optional manual reset high limit has tripped,

 

 

check setting of the device.

 

 

 

 

 

 

 

 

 

• Check resistance of water sensors and compare to

 

 

Table 3-2A on page 35 of this manual. Replace

 

 

sensor if necessary.

 

 

 

 

 

 

 

 

 

• Replace high limit.

 

 

 

 

 

 

 

 

 

 

 

The actual fan RPM is 30% lower than what

• Vent/air intake lengths exceed the maximum allowed

 

is being called for.

lengths. Refer to Section 3 - General Venting of the

Fan Low

 

Knight XL Installation and Operation Manual for

 

proper lengths.

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

 

 

 

Fan Speed Low

 

• Check

for

obstruction or

blockage

in

the

vent/air

 

intake pipes or at terminations.

 

 

 

 

 

 

(will require a manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset once the condition

 

• Check

the wiring connections at

the

fan

and at the

has been corrected.

 

 

main control board.

 

 

 

 

 

 

 

Press the RESET button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the SMART

 

• Replace the fan.

 

 

 

 

 

 

 

SYSTEM display to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset.)

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blown fuse.

• Replace fuse F2 on the control board, see page 33

 

of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 39
Contents Models 400 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessDisplay panel parameter access General Parameter tableSettings Reset Notification Software Version Temperature units C / FViewable and changeable control parameters Date and TimeTemperature Settings Data LoggingFunctions DHW Settings Outdoor Reset Anti-Cycling BMS Thermostat Input Active / Inactive SH Ramp DelayControl modes Controlling SensorMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Wire Color R/BK and Y Wire Color G and YDHW Pump NoisyNo Pump Boiler Pump System PumpFlow Switch/LWCOFlame Fail Ign Anti-cyclingFan Low Auto ResetFlame Sequence High LimitFan Speed High GV/RelayFail Fan HighHigh Flue Temp HighDelta T High Outlet TempService Blk Rem Ctrl FltParameters Progr Write EEProm Watch Dog ErrorNo Error Stored Low 24 vacGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionGas valve adjustment procedure ModelModels 601 Page