Service Manual

1Service (continued)

Viewable and changeable control parameters

CAUTION

Before changing parameters, note the

settings so that the unit can be returned to

 

its original operating parameters.

A: General

Date and Time

The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than four (4) hours. To set the clock, parameter A1 must be accessed.

NOTICE

The internal clock does not adjust for

Daylight Savings Time and therefore,

 

 

will require a manual adjustment.

Software Version

The software version allows the user to view the software version in use by the control. This software controls the operation of the boiler. When a new software version becomes available, the existing control can be replaced with a new control to update the software.

Software version is read only.

Temperature units (°C / °F)

The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter A3. The default is °F.

Space Heating (SH) and Domestic Hot Water (DHW) Night Setback Offset

The unit’s internal clock can be set up to run at a lower set point temperature during unoccupied times. Both the space heating and DHW can be programmed for night setback. When in night setback, the control reduces the set point by a fixed amount. For space heating, it subtracts the space heating night setback offset from each of the SH user set points (parameters B1, B6, and B9), or the calculated outdoor reset set point (if lower). For DHW, it subtracts the DHW night setback offset from the tank set point (parameter E2).

NOTE: The DHW night setback will not work without a tank sensor installed.

The installer may adjust the space heating night setback offset by accessing A4 and the DHW night setback offset by accessing parameter A7. The minimum setting is 0°F (0°C) and the maximum setting is 90°F (50°C).

Space Heating (SH) and Domestic Hot Water (DHW) Night Setback On Times

This is the time in which the SH Night Setback Offset becomes active. There are 7 start times and 7 stop times each for the space heating and DHW night setback features. Both may be set to any time within a 7-day week. These settings are referred to as triggers. Multiple start or stop triggers may be set within a single day, if desired. When a start trigger and a stop trigger are set to the same time, the stop trigger has priority. The installer may adjust the space heating night setback start triggers by accessing parameter A5. The DHW start triggers in parameter A8. This screen shows the start trigger number, the day of the week, and the time of day.

NOTICE

Please note that the brackets ([]) denote

screen status.

 

 

1.When the screen is first accessed, start trigger number 1 is shown. If a different trigger number is desired, the installer can rotate the NAVIGATION dial until the desired trigger number is displayed. Once the desired trigger number is selected, the installer can press the SCROLL knob and the day of the week will start to flash.

2.The installer can adjust the day of the week to the one he wishes to set. Once the day is set, the installer can press the NAVIGATION dial and the hour will begin to flash.

3.After setting the hour, the installer can press the SCROLL knob and the minutes will flash. Once all settings have been made, the installer can press the RIGHT SELECT [SAVE] key. The installer can now select a different trigger and adjust the settings for that trigger.

4.Once all adjustments are made, the installer can press the RIGHT SELECT [SAVE] key to save all of the new settings and return to the A menu, or press the LEFT SELECT [EXIT] key to return to the A menu without saving the changes.

Space Heating (SH) and Domestic Hot Water (DHW)

Night Setback Off Times

The corresponding space heating night setback stop triggers are set by accessing parameter A6. The stop triggers for the DHW night setback feature can be adjusted by accessing parameter A9. The adjustment procedure for these parameters is identical to the space heating start triggers described above.

19

Image 19 Contents
Models 400 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessDisplay panel parameter access General Parameter tableSettings Reset Notification Software Version Temperature units C / FViewable and changeable control parameters Date and TimeData Logging Temperature SettingsFunctions DHW Settings Outdoor Reset Anti-Cycling BMS Thermostat Input Active / Inactive SH Ramp DelayControl modes Controlling SensorMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Wire Color R/BK and Y Wire Color G and YDHW Pump NoisyNo Pump Boiler Pump System PumpFlow Switch/LWCOFlame Fail Ign Anti-cyclingFan Low Auto ResetFlame Sequence High LimitFan Speed High GV/RelayFail Fan HighHigh Flue Temp HighDelta T High Outlet TempRem Ctrl Flt Service BlkParameters Progr Write EEProm Watch Dog ErrorNo Error Stored Low 24 vacGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModel Gas valve adjustment procedureModels 601 Page