2Maintenance

Maintenance and annual startup

Table 2-1Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

General:

Address reported problems

Inspect interior; clean and vacuum if necessary;

Clean condensate trap and fill with fresh water

•Check for leaks (water, gas, flue, condensate)

Verify flue and air lines in good condition and sealed tight

UP

•Check

system water pressure/system

 

START-

piping/expansion tank

 

• Check control settings

 

• Check ignition and flame sense

 

ANNUAL

electrodes (sand off any deposits; clean

and reposition)

 

 

 

 

 

 

• Check wiring and connections

 

 

• Perform start-up

checkout

and

 

performance verification per Section 10

 

in the Knight XL Installation and

 

Operation Manual.

 

 

 

• Flame inspection (stable, uniform)

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

• Clean

the heat

exchanger

if flue

 

temperature is more than 54°F (30°C)

 

above return water temperature.

 

If combustion or performance indicate need:

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Owner maintenance

(see the Knight XL User’s Information Manual for

instructions)

 

• Check boiler area

Daily

• Check pressure/temperature

 

gauge

 

 

 

• Check vent piping

 

• Check air piping

Monthly

• Check air and vent termination

 

 

screens

 

• Check relief valve

 

• Check condensate drain system

 

• Check air vents

 

 

Periodically

•Test low water cutoff (if used)

 

 

• Reset button (low water cutoff)

 

 

Every

• Check boiler piping (gas and

water) for leaks

6 months

 

 

• Operate relief valve

 

 

End

•Shut boiler down (unless boiler

of season

used for domestic hot water)

 

months

 

 

 

28

Image 28
Contents Models 400 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler What is in this manual? ServiceMaintenance TroubleshootingService Near boiler pipingKnight XL display Navigation DialControl inputs LOW Voltage Connection BoardSmart Control Module Control outputsAccess modes General OperationHow the boiler operates How the control module operatesOperation Display From previous page Sequence of Operation Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Parameter table GeneralSettings Reset Notification Temperature units C / F Viewable and changeable control parametersDate and Time Software VersionData Logging Temperature SettingsFunctions DHW Settings Outdoor Reset Anti-Cycling SH Ramp Delay Control modesControlling Sensor BMS Thermostat Input Active / InactiveCascade Offset Minimum On/Off TimeCirculation pumps Service Notification Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check boiler relief valveCheck ignition ground wiring Check all boiler wiringCheck control settings Inspect ignition and flame sense electrodesCheck flame signal Cleaning boiler heat exchangerReview with owner Model Kit Part Component Number DescriptionTroubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No BurnerOperation Unit Does NotChecking temperature sensors Temperature ResistanceWire Color R/BK and Y Wire Color G and Y Resistance TemperatureNoisy No PumpBoiler Pump System Pump DHW PumpSwitch/LWCO FlowAnti-cycling Flame Fail IgnAuto Reset Flame SequenceHigh Limit Fan LowGV/Relay FailFan High Fan Speed HighFlue Temp High Delta T HighOutlet Temp HighRem Ctrl Flt Service BlkParameters Progr Watch Dog Error No Error StoredLow 24 vac Write EEPromCombustion Analysis Procedure Gas Valve AdjustmentOr Obstruction Gas Supply PressureModel Gas valve adjustment procedureModels 601 Page