Lochinvar 400 - 801 service manual Temperature Settings, Data Logging, Functions

Page 20

1Service

Display Timeout

This is the time in which the display remains illuminated. The range is 10 seconds to 10 minutes. The default is 3 minutes.

B: Temperature Settings

Space Heating (SH1, SH2, SH3) Set Point

CAUTION

Mixing valves are required for the

 

protection of any low temperature loops.

 

There are three (3) individual user set points for better zone control. These are listed as SH1 Set Point through SH3 Set Point. If multiple set points are calling for heat the highest set point has priority. The range is 32°F (0°C) to 190°F (88°C). The default is 125°F (52°C).

Space Heating (SH) Minimum Set Point

The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation. The user or installer will not be able to program the control with a lower SH set point. This parameter can only be changed by the installer by accessing parameter B2. The temperature range of this parameter is 32°F (0°C) to 190°F (88°C). The default value is 70°F (21°C).

Space Heating (SH) Maximum Set Point

The SH maximum set point sets the maximum water temperature set point that can be used for space heating. The user or installer will not be able to program the control with a higher SH set point. This parameter can only be changed by the installer by accessing parameter B3. The temperature range of this parameter is 32°F (0°C) to 190°F (88°C). The default value is 185°F (85°C).

SH1 - SH3 Offset Set Point

The SH offset sets how many degrees above set point the temperature has to go before the boiler will shut off. This parameter can only be changed by the installer by accessing parameters B4, B7 and B10. The temperature range of these parameters is 0°F to 20°F. The default value is 10°F.

SH1 - SH3 Differential Set Point

The SH differential sets how many degrees below the offset the temperature has to drop before the boiler turns back on. This parameter can only be changed by the installer by accessing parameters B5, B8 and B11. The range is 0°F to 60°F. The default is 20°F.

3-Way Valve Time

Not used.

20

Service Manual

C: Data Logging

Reset last 10 errors

The reset last 10 errors function clears the last 10 errors log.

D: Functions

Service Mode Delay

By pressing the pin button on the front of the display for five

(5)seconds, the control will be placed in Service Mode. This will override all other heat demands. The Service Mode allows the installer to set the unit to either maximum firing rate or minimum firing rate for the purpose of combustion analysis. The delay sets the length of time the boiler will stay in the Service Mode if no keys have been pressed before going back to its original state. This parameter can only be changed by the installer by accessing parameter D1. The time range of this parameter is 0 to 30 minutes. The default value is 20 minutes.

Freeze Protection Pump On

The SMART SYSTEM control will turn on the boiler and system pump outputs whenever the inlet temperature drops below this setting. This is done to prevent the water in the heat exchanger from freezing. Certain low-temperature applications (such as snow melt) can operate at temperatures around freezing, so this setting needs to be lowered in these cases. The installer can adjust the temperature at which the pump outputs are turned on by accessing parameter D2. The minimum setting is -4°F (-20°C), and the maximum setting is 45°F (7.2°C). The default setting is 45°F (7.2°C).

Freeze Protection Burner On

If running the pumps does not prevent the inlet temperature from falling closer to freezing, the SMART SYSTEM control will fire the burner at low fire. The installer can adjust the temperature at which the burner fires by adjusting parameter D3. The minimum setting is -4°F (-20°C), and the maximum setting is 45°F (7.2°C). The default setting is 37°F (2.8°C).

Freeze Protection Burner Differential

Once the burner has started firing due to a low inlet temperature, the inlet temperature must increase by this amount before the burner turns back off. The installer can adjust this differential by accessing parameter D4. The minimum setting is 0°F, and the maximum is 20°F. The default setting is 5°F (2.8°C).

Image 20
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler What is in this manual? ServiceMaintenance TroubleshootingService Near boiler pipingKnight XL display Navigation DialControl inputs LOW Voltage Connection BoardSmart Control Module Control outputsAccess modes General OperationHow the boiler operates How the control module operatesOperation Display From previous page Sequence of Operation Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Parameter table GeneralSettings Reset Notification Temperature units C / F Viewable and changeable control parametersDate and Time Software VersionFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling SH Ramp Delay Control modesControlling Sensor BMS Thermostat Input Active / InactiveCascade Offset Minimum On/Off TimeCirculation pumps Service Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check boiler relief valveCheck ignition ground wiring Check all boiler wiringCheck control settings Inspect ignition and flame sense electrodesCheck flame signal Cleaning boiler heat exchangerReview with owner Model Kit Part Component Number DescriptionTroubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No BurnerOperation Unit Does NotChecking temperature sensors Temperature ResistanceWire Color R/BK and Y Wire Color G and Y Resistance TemperatureNoisy No PumpBoiler Pump System Pump DHW PumpSwitch/LWCO FlowAnti-cycling Flame Fail IgnAuto Reset Flame SequenceHigh Limit Fan LowGV/Relay FailFan High Fan Speed HighFlue Temp High Delta T HighOutlet Temp HighParameters Progr Service BlkRem Ctrl Flt Watch Dog Error No Error StoredLow 24 vac Write EEPromCombustion Analysis Procedure Gas Valve AdjustmentOr Obstruction Gas Supply PressureModels 601 Gas valve adjustment procedureModel Page