Lochinvar 400 - 801 Checking temperature sensors, Temperature Resistance, Resistance Temperature

Page 35

Service Manual

3Troubleshooting (continued)

Checking temperature sensors

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor

It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Knight XL Installation and Operation Manual for correct terminal location.

Table 3-2A - Inlet Water/System Sensor Resistance vs. Temperature

Temperature

Resistance

Temperature

Resistance

 

 

 

 

50

18,780

158

1,990

 

 

 

 

68

12,263

176

1,458

86

8,194

194

1,084

 

 

 

 

104

5,592

212

817

122

3,893

 

 

140

2,760

 

 

 

 

 

 

Table 3-2B - Outdoor Air Sensor Resistance vs. Temperature

Temperature

Resistance

Temperature

Resistance

 

 

 

 

-50

490,813

20

46,218

 

 

 

 

-40

336,606

30

34,558

-30

234,196

40

26,099

 

 

 

 

-20

165,180

50

19,900

10

118,018

60

15,311

 

 

 

 

0

85,362

70

11,883

10

62,465

80

9,299

 

 

 

 

Table 3-2C - Outlet Water Sensor Resistance vs. Temperature

 

 

S1a

 

 

S1b

 

 

 

 

 

(Wire Color - R/BK and Y)

 

 

(Wire Color - G and Y)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

19,553

158

2,004

50

40,030

158

3,478

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

12,690

176

1,464

68

25,030

176

2,492

 

 

 

86

8,406

194

1,084

86

16,090

194

1,816

 

 

 

 

 

 

 

 

 

 

 

 

 

 

104

5,715

212

816

104

10,610

212

1,344

 

 

 

122

3,958

 

 

122

7,166

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

140

2,786

 

 

140

4,943

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3-2D - Flue Sensor Resistance vs. Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S3a

 

 

S3b

 

 

 

 

 

(Wire Color - W/B and Y)

 

 

(Wire Color - PR and Y)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

50

40,030

158

3,478

50

258,500

158

16,870

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

25,030

176

2,492

68

125,500

176

12,000

 

 

 

86

16,090

194

1,816

86

80,220

194

8,674

 

 

 

 

 

 

 

 

 

 

 

 

 

 

104

10,610

212

1,344

104

52,590

212

6,369

 

 

 

122

7,166

 

 

122

35,270

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

140

4,943

 

 

140

24,160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

Image 35
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessDisplay panel parameter access General Parameter tableSettings Reset Notification Software Version Temperature units C / FViewable and changeable control parameters Date and TimeFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling BMS Thermostat Input Active / Inactive SH Ramp DelayControl modes Controlling SensorMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Wire Color R/BK and Y Wire Color G and YDHW Pump NoisyNo Pump Boiler Pump System PumpFlow Switch/LWCOFlame Fail Ign Anti-cyclingFan Low Auto ResetFlame Sequence High LimitFan Speed High GV/RelayFail Fan HighHigh Flue Temp HighDelta T High Outlet TempParameters Progr Service BlkRem Ctrl Flt Write EEProm Watch Dog ErrorNo Error Stored Low 24 vacGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModels 601 Gas valve adjustment procedureModel Page