Service Manual
1Service
Table 1-1 (continued from previous page) Sequence of Operation
|
| OPERATION |
|
| DISPLAY | |||
|
| |||||||
8. If the space heating call for heat is active, and the tank |
| |||||||
thermostat or sensor starts a DHW call for heat, the boiler will |
| |||||||
switch to the DHW mode. If programmed for normal DHW |
| |||||||
operation (not as a zone), the DHW pump will turn on first, then |
| |||||||
the | boiler | pump | will | turn | off 2 | seconds later. |
| |
This will divert the boiler’s outlet water from the heating system |
| |||||||
and | send | it | to | the | tank | coil | instead. |
|
The control will then modulate to maintain the outlet |
| |||||||
temperature to the DHW boiler set point. |
|
|
| |||||
|
| |||||||
9. If the boiler is not part of a Cascade, and both the space heating |
| |||||||
and DHW calls for heat remain active long enough, the boiler will |
| |||||||
switch back and forth between the two heating modes until one |
| |||||||
of them is satisfied. |
|
|
|
|
|
| ||
|
| |||||||
10. Once both calls for heat are satisfied, the control will turn off the |
| |||||||
burner. The blower will continue to run during a 10 second |
| |||||||
postpurge. |
|
|
|
|
|
|
| |
|
| |||||||
11. Any pumps that are running will continue to run for their |
| |||||||
respective pump delay times before turning off, unless |
| |||||||
programmed | to |
| remain | on | continuously. |
| ||
A 60 second |
| |||||||
new call for heat until it times out. |
|
|
|
| ||||
|
|
|
| |||||
12. In Standby, ready to start a new cycle. |
|
|
| |||||
|
|
|
|
|
|
|
|
|
12