5 Hydronic piping (continued)
Figure 5-2 Single Boiler - Recommended - Primary / Secondary Piping with a Hot Water Generator
HOT WATER
GENERATOR
WATER
GENERATOR
CIRCULATOR
FROM SYSTEM
SYSTEM RETURN
SENSOR
12"
MAX
RELIEF | BALL VALVE |
(TYPICAL) | |
VALVE |
|
AIR SEPERATOR
DRAIN PORT (TYPICAL)
SYSTEM SUPPLY
SENSOR
SYSTEM
CIRCULATOR
|
|
| TO SYSTEM |
BOILER |
|
|
|
DRAIN | PRESSURE |
| MAKE UP |
| REDUCING VALVE | BACK FLOW | |
|
| WATER | |
|
| PREVENTER | |
EXPANSION | PRESSURE |
| |
|
| ||
TANK | GAUGE |
|
|
|
|
| |
(RECOMMENDED) |
|
|
|
FLOW CHECK |
|
|
|
VALVE (TYPICAL) |
|
|
|
BOILER PUMP
NOTICE
NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in operation to prevent short cycling and high limit issues.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.