PANELS AND COVERS

All panels and covers (e.g. control and junction box covers; front, side and rear panels of boiler) must be in place after service and/ or before opera­tion of boiler. This will ensure that all gas ignition components will be protected from water.

The XP is a low-pressure boiler (Category IV) to be used as either hot water supply (domestic/commercial water heating) or hot water heating (hydronic) application. Category IV appli­ances are often termed “High Effi­ciency” appliances.

CHEMICAL VAPOR CORROSION

Boiler corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Spray can propellants, cleaning solvents,­ refrigerator and air conditioning refrigerants,­ swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence.

Products of this sort should not be stored near boiler. Also, air which is brought in contact with boiler should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. Failure to observe this requirement will void warranty.

INSTALLATION CLEARANCES

This boiler is approved for installation in an alcove with minimum clearances to combustibles.

Table 12.  INSTALLATION CLEARANCES

 

RECOMMENDED

CLEARANCES FROM

 

SERVICE

COMBUSTIBLE

 

CLEARANCES

MATERIALS

Front

30" (762 mm)

8" (203 mm)

Rear

36" (610 mm)

24" (610 mm)

Left

24 " (610 mm)

1" (25.4 mm)

Right

24 " (610 mm)

2" (51 mm)

Top

24" (610 mm)

6" (152 mm)

2” (51 mm) clearance is allowable from combustible construction for hot water pipes.

Sufficient area should be provided at the front and rear of the unit for proper­ servicing. In a utility room installa­tion, the door opening should be wide enough to allow the boiler to enter or to permit the replacement of another appli­ance such as a boiler.

FLOORING AND FOUNDATION:

All models are approved for installation on combustible flooring, but must never be installed on carpeting. Do not install the boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death, or substantial property damage.

If flooding is possible, elevate the boiler sufficiently to prevent water from reaching the boiler.

LEVELING

Because this unit is a Category IV appliance it produces some amounts of condensation. The unit has a condensation disposal system that requires this unit to be level to properly drain. Each unit should be checked to be certain that it is level prior to starting the unit.

If the unit is not level, obtain and insert shims under the feet at the frame base to correct this condition.

AIR REQUIREMENTS

Breathing Hazard - Carbon Monoxide Gas

Install appliance in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.

To avoid injury, combustion and ventilation air must be taken from outdoors.

Do not place chemical vapor emitting products near water heater.

Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.

For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided.

An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner flame, causing sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation.

Do not install the boiler in a confined space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confined Space section that follows.

Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause property damage, serious bodily injury or death.

UNCONFINED SPACE

An unconfined space is one whose volume is not less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and fireplaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air.

UNUSUALLY TIGHT CONSTRUCTION

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows.

22

Image 22
Contents XP Boiler Table of Contents Approvals Safe INSTALLATION, USE and ServiceImportant Definitions General Safety Abbreviations Used IntroductionModel Identification QualificationsDimensions and Capacity Data Operating CharacteristicsDouble Heat Exchanger Boiler Rough in Dimensions Double Ratings Electrical RequirementsFLOW, Head and Temperature Rise XB Models FLOW, Head and Temperature RiseFeatures and Components Single Heat Exchanger Boiler ComponentsDouble Heat Exchanger Boiler Components Component Description Low water cutoff board and sensor probe LwcoControl Components Main Power Supply Switch Flame Sensor Water Temperature SensorsWater Temperature Limit Controls LOW Water Cutoff Device LwcoGeneral Boiler Installation ConsiderationsHydronic System Closed Water Systems Internal ContaminantsHOT Water Boiler System General Water Line Connections Thermal ExpansionExplosion Hazard GAS ConnectionsCorrosive Materials and Contamination Sources GAS Supply Line SizingPower Supply Check Field WiringVAC Power Supply Wiring LOW Voltage Control WiringSuggested Pipe Size for Multiple GAS Appliances Natural GAS Location General RequirementsRequired Ability Replacing Existing Common Vented BoilerChemical Vapor Corrosion Installation ClearancesPanels and Covers LevelingFresh AIR Openings for Confined Spaces Confined Space Outdoor AIR Through TWO OpeningsOutdoor AIR Through ONE Opening AIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts DuctsVenting Requirements for Installation in Canada Vent and AIR Pipe InstallationAIR Inlet Pipe Materials Direct Vent Installation Requirements Vertical Installation RequirementsHorizontal Installation Requirements Venting SupportsModels Vent KIT Numbers XB/XW Rain CAP Models Vent KIT Numbers XB/XW TEEModels Vent AIR Intake XB/XW KIT Numbers TEE Elbow Models Vent AIR Intake XB/XW KIT Numbers Rain CAP ElbowDirect VENT, Vertical Vent Horizontal Intake Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentBELOW. Keep Clear of ALL Obstructions VENT/AIR Termination Locations Direct Vent Horizontal TerminationTermination Vertical Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations ClearancesModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch Condensate Trap Condensate DisposalCondensate Neutralizer XP Models AO Smith Condensate Neutralizer KIT NumbersGAS Supply Pipe Connections GAS Supply ConnectionsGAS Pressure Requirements Check GAS Supply Inlet Pressure Pipe Sizes for Propane GASPurging GAS Line Check for GAS LeaksBoiler Start UP and Operations Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Manifold Pressure ConnectionsINSPECT/FILL Condensate System Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness Water Hardness Medium 0-12 Grains PER Gallon XW ModelLighting and Operating Instructions Adjustment Setting of the Test ModeHigh Fire Rate Burner Control System Control SystemOverview Communications and Displays SpecificationsBurner Control Operation General Operational Sequence Domestic HOT Water Lead LAGLead LAG LL Master General Operation Local Operator Interface Display System FeaturesDefinitions Quick Setup S7999B OI Display Installation Instructions S7999B OI DisplayMounting the S7999B OI Display and Power Supply Starting UP the S7999B OI Display POWER-UP ValidationCommon OI Display page Symbols NavigationS7999B Display page Flow Configure Button Status or HomeChange Parameter Settings Configuration PasswordLogin KeyboardExample of Change Configuration Parameter VerifyData Comment FAULT/ALARM HandlingHistory Button Example of Hydronic History Control Expanded Alert Detail Operation ButtonDiagnostics Button System Configuration S7999B OI Display onlySystem Synchronization S7999B OI Display only ConfigurationHydronic Control Troubleshooting Code Description Recommended Troubleshooting Lockout CodesReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Code Description AllowedFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors General Maintenance Maintenance ProceduresMaintenance Schedules Inspect Boiler AreaBlower Compartment Burner MaintenanceAIR Filter BOX Heat Exchanger Maintenance Venting MaintenanceCondensate Removal System Replacement Parts Handling Ceramic Fiber MaterialsPiping Diagrams Inlet DIAStorage Tank AOS Limited Warranty Conditions and Exceptions

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.