STARTING UP THE S7999B OI DISPLAY

POWER-UP VALIDATION

The Home page will appear and the “Power” LED will be blinking when the device is properly powered. Select the Setup button to adjust the contrast and sound as desired.

If the screen is dim, check the pin 1 and 2 wiring connections.

Note: An Advanced Startup screen displays for five seconds after power-up before the Home page displays. This screen allows the user to upgrade the software in the System Display and should normally be bypassed.

Three LEDs exist for I/O traffic: one for the Ethernet network port and two for Modbus™ ports. Modbus Com Port 2 is not active on this device.

1.Make sure the Power and COM1 LEDs are blinking.

2.If the LEDs are not blinking:

Make sure the proper connections have been made between the Modbus COM1 Port and the first controller device in the Modbus network.

Ensure proper wiring of the OI Display 9-pin Header Connections.

3.If connected to a BAS application, COM2 LED will blink indicating BAS traffic.

HOME PAGE (S7999B OI DISPLAY)

Make sure a screen similar to Figure 51 appears after the OI Display has completely powered up.

Figure 51.  S7999B HOME PAGE (BOILER 1 IN NORMAL OPERATION)

Figure 52.  S7999B LEAD LAG HOME PAGE

On System applications, each Burner Control System is represented on the Home page by an icon and name. Pressing the icon allows the user to zoom in on that boiler and see its specific details. These details are provided on a new page, which can include additional buttons that display additional detail and operation information, which itself leads to other pages. The pages are traversed in a tree structure method, as shown in Figure 53 on Page 52.

The Control System icons will appear in one of four colors indicating the boiler status.

Blue: Normal operation

Red: Lockout condition

Gray: Standby mode (burner switch off)

Gray and crossed out: communication error (disconnected or powered off)

Yellow: Preparing for Start-up.

Up to 8 Systems can be displayed on the Home page. The name of each boiler is displayed next to the Control System icon button. When Lead Lag is enabled, the system header temperature and firing rate are displayed for each System. When the burner is in standby or not firing the firing rate is not displayed.

Note: The boiler name may be cut off on the Home page when all icons are present.

The Home page also includes a System Analysis button that allows the user to view status information on a system-wide (that is, multiple boiler) basis. The user can choose which status information to compare from the Burner Controls in the system.

Pressing the Setup button on the Home page displays miscellaneous setup and diagnostic functions. It also contains the setup configuration for BAS applications, under the Advanced Setup button. Pressing the Control System icon opens that control’s status page.

PAGE NAVIGATION

The Burner Control System OI Displays present information and options in a paged manner. Pages are displayed in a tree structure in which the user navigates up and down to arrive at the desired Function (see Figure 53). The page descriptions are provided below so that you can understand the purpose of each and view the selections, parameters, and information that is available or required on each.

COMMON OI DISPLAY PAGE SYMBOLS

Most pages have a Home button in the top-left corner of the screen and a Back button in the top-right corner of the screen. The Home button returns the user to the Home page and terminates any operation in progress. The Back button returns the user to the previous page.

Two other icons may be noticed near the boiler name.

A bell will be displayed if the system is in Lockout that reset will be required.

A padlock will be shown on screens that require a password to change the parameter. An unlocked padlock indicates the password has been entered to change the parameter.

51

Image 51
Contents XP Boiler Table of Contents Safe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Qualifications IntroductionModel Identification Abbreviations UsedOperating Characteristics Dimensions and Capacity DataDouble Heat Exchanger Boiler Rough in Dimensions Double Electrical Requirements RatingsXB Models FLOW, Head and Temperature Rise FLOW, Head and Temperature RiseSingle Heat Exchanger Boiler Components Features and ComponentsDouble Heat Exchanger Boiler Components Low water cutoff board and sensor probe Lwco Component DescriptionControl Components LOW Water Cutoff Device Lwco Flame Sensor Water Temperature SensorsWater Temperature Limit Controls Main Power Supply SwitchBoiler Installation Considerations GeneralHydronic System Thermal Expansion Internal ContaminantsHOT Water Boiler System General Water Line Connections Closed Water SystemsGAS Connections Explosion HazardGAS Supply Line Sizing Corrosive Materials and Contamination SourcesLOW Voltage Control Wiring Field WiringVAC Power Supply Wiring Power Supply CheckSuggested Pipe Size for Multiple GAS Appliances Natural GAS Replacing Existing Common Vented Boiler General RequirementsRequired Ability LocationLeveling Installation ClearancesPanels and Covers Chemical Vapor CorrosionConfined Space Outdoor AIR Through TWO Openings Fresh AIR Openings for Confined SpacesOutdoor AIR Through ONE Opening Ducts Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts AIR from Other Indoor SpacesVenting Vent and AIR Pipe Installation Requirements for Installation in CanadaAIR Inlet Pipe Materials Venting Supports Vertical Installation RequirementsHorizontal Installation Requirements Direct Vent Installation RequirementsModels Vent KIT Numbers XB/XW TEE Models Vent KIT Numbers XB/XW Rain CAPModels Vent AIR Intake XB/XW KIT Numbers Rain CAP Elbow Models Vent AIR Intake XB/XW KIT Numbers TEE ElbowDirect VENT, Vertical Vent Horizontal Intake Power Vent Termination Clearances Sidewall Power VentDirect Vent Termination Clearances Sidewall Direct VentBELOW. Keep Clear of ALL Obstructions Direct Vent Horizontal Termination VENT/AIR Termination LocationsTermination Clearances Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations VerticalModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch XP Models AO Smith Condensate Neutralizer KIT Numbers Condensate DisposalCondensate Neutralizer Condensate TrapGAS Supply Connections GAS Supply Pipe ConnectionsGAS Pressure Requirements Check for GAS Leaks Pipe Sizes for Propane GASPurging GAS Line Check GAS Supply Inlet PressureManifold Pressure Connections Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Boiler Start UP and OperationsWater Hardness Medium 0-12 Grains PER Gallon XW Model Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness INSPECT/FILL Condensate SystemLighting and Operating Instructions Setting of the Test Mode AdjustmentHigh Fire Rate Control System Burner Control SystemOverview Specifications Communications and DisplaysBurner Control Operation General Operational Sequence Lead LAG Domestic HOT WaterLead LAG LL Master General Operation Features Local Operator Interface Display SystemDefinitions Installation Instructions S7999B OI Display Quick Setup S7999B OI DisplayMounting the S7999B OI Display and Power Supply Navigation POWER-UP ValidationCommon OI Display page Symbols Starting UP the S7999B OI DisplayS7999B Display page Flow Status or Home Configure ButtonKeyboard Configuration PasswordLogin Change Parameter SettingsParameter Verify Example of Change ConfigurationFAULT/ALARM Handling Data CommentHistory Button Example of Hydronic History Operation Button Control Expanded Alert DetailSystem Configuration S7999B OI Display only Diagnostics ButtonConfiguration System Synchronization S7999B OI Display onlyHydronic Control Code Description Recommended Troubleshooting Lockout Codes TroubleshootingReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Allowed Code DescriptionFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors Inspect Boiler Area Maintenance ProceduresMaintenance Schedules General MaintenanceBurner Maintenance Blower CompartmentAIR Filter BOX Venting Maintenance Heat Exchanger MaintenanceCondensate Removal System Handling Ceramic Fiber Materials Replacement PartsInlet DIA Piping DiagramsStorage Tank AOS Conditions and Exceptions Limited Warranty

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.