A.O. Smith 2000, 3400, 2600, 1700 Boiler Installation Considerations, General, Hydronic System

Page 15

BOILER INSTALLATION CONSIDERATIONS

GENERAL

If the system is to be filled with water for testing or other purposes during cold weather and before actual operation, care must be taken to prevent freezing of water in the system. Failure to do so may cause the water in the system to freeze with resulting damage to the system.

Damage due to freezing is not covered by the warranty.

Figure 78 on Page 80 shows a typical primary, secondary piping method. This is the preferred piping method for most stainless steel boilers. Other piping methods, however, may provide good system operation. A prime concern when designing heating systems is the maintenance of proper flow through the unit during boiler operation. The secondary pump should be sized per the recommended flow rate of the boiler, see Dimension and Capacity Data section in this manual.

Before locating the boiler:

1.Check for nearby connection to:

System water piping

Venting connections

Gas supply piping

Electrical power

2.Locate the boiler so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.

3.Check area around the boiler. Remove any combustible materials, gasoline and other flammable liquids.

4.Make sure the gas control system components are protected from dripping or spraying water or rain during operation or service.

5.If a new boiler will replace an existing boiler, check for and correct system problems, such as:

System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits.

Lack of freeze protection in boiler water causing system and boiler to freeze and leak.

HYDRONIC SYSTEM

The following is a brief description of the equipment required for the installations noted in this manual. All installations must comply with local code.

WATER SUPPLY LINE

These boilers can be used only in a forced circulation hot water heating system. Since most forced circulation systems will be of the closed type, install the water supply line as shown on piping

diagram.

Fast filling of large pipe, old radiator installations and pressure purging of series loop systems (where high pressures are not available) requires bypassing of the pressure reducing valve.

Generally,­ pressure purging is not possible with a well pump system. High point air venting is essential.

If the system is of the open type, a pressure reducing valve will not be required as the water supply to the system will be controlled by a manu­ally operated valve. An overhead surge tank is required. A minimum pressure of 15 psi (100 kPa) must be maintained on the boiler at all times to ensure avoidance of potential damage to the boiler which may not be covered by the warranty.

EXPANSION TANK

If the system is of the closed type, install an expansion tank. The sizing of the expansion tank for a closed system is very important and is directly related to the total water volume of the system.

An air separator as shown in the piping diagrams is recommended especially for modern commercial hydronic systems. See Figure 78 on Page 80.

VENT VALVES

It is recommended that automatic, loose key or screw-driver type vent valves be installed at each convector or radiator.

SYSTEM HEADERS

Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler. To achieve good water distribution with maximum pressure drop for several­ circuits, manifolds should be larger than system mains.

The circuits should be spaced on the heater at a minimum of 3” (76 mm) center to center. Install a balancing cock in each return line.

Manifold headers are recommended for split systems with or without zone valves and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water flow.

CHECK VALVES

Check valves must be installed to isolate each boiler in installations where multiple boilers/pumps are installed in the same zone.

COOLING PIPING

When the boiler is used in conjunction with a refrigeration system it must be installed so that the chilled medium is piped in parallel with the boiler. Appropriate flow control valves, manual or motorized, must be provided to prevent the chilled medium from entering the boiler.

If the boiler is connected to chilled water piping or its heating coils are exposed to refrigerated air, the boiler piping system must be equipped with flow valves or other automatic means to prevent gravity circulation through the boiler during the cooling cycle.

Primary/secondary pumping of both the chiller(s) and the boiler(s) is an excellent winter-summer change-over method, because cooling flow rates are so much more than heating flow rates. In this way each system (heating or cooling) is circulated independently.

15

Image 15
Contents XP Boiler Table of Contents Safe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Qualifications IntroductionModel Identification Abbreviations UsedOperating Characteristics Dimensions and Capacity DataDouble Heat Exchanger Boiler Rough in Dimensions Double Electrical Requirements RatingsXB Models FLOW, Head and Temperature Rise FLOW, Head and Temperature RiseSingle Heat Exchanger Boiler Components Features and ComponentsDouble Heat Exchanger Boiler Components Low water cutoff board and sensor probe Lwco Component DescriptionControl Components LOW Water Cutoff Device Lwco Flame Sensor Water Temperature SensorsWater Temperature Limit Controls Main Power Supply SwitchBoiler Installation Considerations GeneralHydronic System Thermal Expansion Internal ContaminantsHOT Water Boiler System General Water Line Connections Closed Water SystemsGAS Connections Explosion HazardGAS Supply Line Sizing Corrosive Materials and Contamination SourcesLOW Voltage Control Wiring Field WiringVAC Power Supply Wiring Power Supply CheckSuggested Pipe Size for Multiple GAS Appliances Natural GAS Replacing Existing Common Vented Boiler General RequirementsRequired Ability LocationLeveling Installation ClearancesPanels and Covers Chemical Vapor CorrosionConfined Space Outdoor AIR Through TWO Openings Fresh AIR Openings for Confined SpacesOutdoor AIR Through ONE Opening Ducts Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts AIR from Other Indoor SpacesVenting Vent and AIR Pipe Installation Requirements for Installation in CanadaAIR Inlet Pipe Materials Venting Supports Vertical Installation RequirementsHorizontal Installation Requirements Direct Vent Installation RequirementsModels Vent KIT Numbers XB/XW TEE Models Vent KIT Numbers XB/XW Rain CAPModels Vent AIR Intake XB/XW KIT Numbers Rain CAP Elbow Models Vent AIR Intake XB/XW KIT Numbers TEE ElbowDirect VENT, Vertical Vent Horizontal Intake Power Vent Termination Clearances Sidewall Power VentDirect Vent Termination Clearances Sidewall Direct VentBELOW. Keep Clear of ALL Obstructions Direct Vent Horizontal Termination VENT/AIR Termination LocationsTermination Clearances Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations VerticalModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch XP Models AO Smith Condensate Neutralizer KIT Numbers Condensate DisposalCondensate Neutralizer Condensate TrapGAS Supply Connections GAS Supply Pipe ConnectionsGAS Pressure Requirements Check for GAS Leaks Pipe Sizes for Propane GASPurging GAS Line Check GAS Supply Inlet PressureManifold Pressure Connections Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Boiler Start UP and OperationsWater Hardness Medium 0-12 Grains PER Gallon XW Model Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness INSPECT/FILL Condensate SystemLighting and Operating Instructions Setting of the Test Mode AdjustmentHigh Fire Rate Control System Burner Control SystemOverview Specifications Communications and DisplaysBurner Control Operation General Operational Sequence Lead LAG Domestic HOT WaterLead LAG LL Master General Operation Features Local Operator Interface Display SystemDefinitions Installation Instructions S7999B OI Display Quick Setup S7999B OI DisplayMounting the S7999B OI Display and Power Supply Navigation POWER-UP ValidationCommon OI Display page Symbols Starting UP the S7999B OI DisplayS7999B Display page Flow Status or Home Configure ButtonKeyboard Configuration PasswordLogin Change Parameter SettingsParameter Verify Example of Change ConfigurationFAULT/ALARM Handling Data CommentHistory Button Example of Hydronic History Operation Button Control Expanded Alert DetailSystem Configuration S7999B OI Display only Diagnostics ButtonConfiguration System Synchronization S7999B OI Display onlyHydronic Control Code Description Recommended Troubleshooting Lockout Codes TroubleshootingReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Allowed Code DescriptionFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors Inspect Boiler Area Maintenance ProceduresMaintenance Schedules General MaintenanceBurner Maintenance Blower CompartmentAIR Filter BOX Venting Maintenance Heat Exchanger MaintenanceCondensate Removal System Handling Ceramic Fiber Materials Replacement PartsInlet DIA Piping DiagramsStorage Tank AOS Conditions and Exceptions Limited Warranty

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.