A.O. Smith 2000, 3400, 2600, 1700 instruction manual General Operational Sequence

Page 47

6. MAIN FLAME ESTABLISHING PERIOD (MFEP):

a. Lockout Interlock opens (if enabled). b. Pilot valve terminal is not energized. c. Main valve terminal is not energized. d. No flame present at the end of MFEP. e. Internal system fault occurred.

7. RUN PERIOD:

a. No flame is present, or flame is lost (if enabled-lockout). b. Lockout Interlock opens) if enabled).

c. IAS Purge and Ignition enabled and the Interlock opens.

d. Pilot terminal energized (if programmed as Interrupted Pilot). e. Main valve terminal is not energized.

f. Internal system fault occurred.

8. POSTPURGE PERIOD:

a. Preignition Interlock does not close in five seconds. b. Pilot Valve terminal is energized.

c. Main Valve terminal is energized. d. Internal system fault occurred.

e. Flame sensed 240 seconds accumulated time after the RUN period.

SAFETY SHUTDOWN:

1.If the lockout interlocks open or a sensor designated as a safety limit are read as defective, Control System will lockout and the blower motor will be de-energized.

If these open during the firing period, all fuel valves will be de- energized, the system will complete postpurge, and will lockout indicated by an alarm.

2.If the pilot flame is not detected by the end of the last (3 number recycle attempt), pilot trial for ignition period, the pilot valve, and ignition transformer will be de-energized, the system will complete post purge and will lockout indicated by an alarm.

3.If the main flame is not detected at the end of the last recycle attempt of the main flame establishing period, all fuel valves will be de-energized, the device will complete postpurge, and will lockout indicated by an alarm.

4.If the flame sensing signal is lost during the run period (if lockout is selected), all fuel valves will be de-energized within 4 seconds after the loss of the flame signal, the device will complete postpurge, and will lockout indicate by an alarm.

5.Manual reset is required following any safety shutdown. Manual reset may be accomplished by pressing the push button on the device, pressing the remote reset wired into connector J10, or through an attached display.

Interrupting power to Control System will cause electrical resets, but does not reset a lockout condition.

GENERAL OPERATIONAL SEQUENCE

INITIATE

The R7910 enters the Initiate sequence on Initial Power up or:

Voltage fluctuations vary less than 20VAC or greater than 30VAC.

Frequency fluctuations vary +/-5% (57 to 63 Hz).

If Demand, LCI, or Stat interrupt (open) during the Prepurge Period.

After the reset button is pressed or fault is cleared at the displays.

The Initiate sequence also delays the burner motor from being energized and de-energized from an intermittent AC line input or control input.

If an AC problem exists for more than 240 seconds a lockout will occur.

HYDRONIC/CENTRAL HEATING

Start-up sequence central heating request (system in standby):

1.Heat request detected (On Setpoint - On Hysteresis).

2.The CH pump is switched on.

3.After a system Safe Start Check, the Blower (fan) is switched on after a dynamic ILK switch test (if enabled).

4.After the ILK switch is closed and the purge rate proving fan RPM is achieved (or High Fire Switch is closed) - prepurge time is started.

5.When the purge time is complete, the purge fan RPM is changed to the Lightoff Rate or if used, the damper motor is driven to the Low Fire Position.

6.As soon as the fan-rpm is equal to the light-off rpm (or the Low Fire Switch closes), the Trial for Ignition or Pre-Ignition Time is started.

7.Pre-Ignition Time will energize the ignitor and check for flame.

8.Trial for Ignition. Specifics for timings and device actions are defined by the OEM or installer.

9.The ignition and the gas valve are switched on.

10.The ignition is turned off at the end of the direct burner ignition period, or for a system that does use a pilot, at the end (or optionally at the middle) of the Pilot Flame Establishing Period (PFEP). For an interrupted pilot system this is followed by a Main Flame Establishing Period (MFEP) where the pilot ignites the main burner. For an intermittent pilot there is no MFEP.

11.The fan is kept at the lightoff rate during the stabilization timer, if any.

12.Before the release to modulation, the fan is switched to minimum RPM for the CH Forced Rate and Slow Start Enable, if the water is colder than the threshold.

13.At the end of the CH-heat request the burner is switched off and the fan stays on until post purge is complete.

14.A new CH-request is blocked for the forced off time set by the Anti Short Cycle (if enabled).

15.The pump stays on during the pump overrun time (if enabled).

16.At the end of the pump overrun time the pump will be switched off.

47

Image 47
Contents XP Boiler Table of Contents Important Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Qualifications IntroductionModel Identification Abbreviations UsedOperating Characteristics Dimensions and Capacity DataDouble Heat Exchanger Boiler Rough in Dimensions Double Electrical Requirements RatingsXB Models FLOW, Head and Temperature Rise FLOW, Head and Temperature RiseSingle Heat Exchanger Boiler Components Features and ComponentsDouble Heat Exchanger Boiler Components Low water cutoff board and sensor probe Lwco Component DescriptionControl Components LOW Water Cutoff Device Lwco Flame Sensor Water Temperature SensorsWater Temperature Limit Controls Main Power Supply SwitchHydronic System Boiler Installation ConsiderationsGeneral Thermal Expansion Internal ContaminantsHOT Water Boiler System General Water Line Connections Closed Water SystemsGAS Connections Explosion HazardGAS Supply Line Sizing Corrosive Materials and Contamination SourcesLOW Voltage Control Wiring Field WiringVAC Power Supply Wiring Power Supply CheckSuggested Pipe Size for Multiple GAS Appliances Natural GAS Replacing Existing Common Vented Boiler General RequirementsRequired Ability LocationLeveling Installation ClearancesPanels and Covers Chemical Vapor CorrosionOutdoor AIR Through ONE Opening Confined Space Outdoor AIR Through TWO OpeningsFresh AIR Openings for Confined Spaces Ducts Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts AIR from Other Indoor SpacesVenting AIR Inlet Pipe Materials Vent and AIR Pipe InstallationRequirements for Installation in Canada Venting Supports Vertical Installation RequirementsHorizontal Installation Requirements Direct Vent Installation RequirementsModels Vent KIT Numbers XB/XW TEE Models Vent KIT Numbers XB/XW Rain CAPModels Vent AIR Intake XB/XW KIT Numbers Rain CAP Elbow Models Vent AIR Intake XB/XW KIT Numbers TEE ElbowDirect VENT, Vertical Vent Horizontal Intake Power Vent Termination Clearances Sidewall Power VentDirect Vent Termination Clearances Sidewall Direct VentBELOW. Keep Clear of ALL Obstructions Termination Direct Vent Horizontal TerminationVENT/AIR Termination Locations Clearances Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations VerticalModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch XP Models AO Smith Condensate Neutralizer KIT Numbers Condensate DisposalCondensate Neutralizer Condensate TrapGAS Pressure Requirements GAS Supply ConnectionsGAS Supply Pipe Connections Check for GAS Leaks Pipe Sizes for Propane GASPurging GAS Line Check GAS Supply Inlet PressureManifold Pressure Connections Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Boiler Start UP and OperationsWater Hardness Medium 0-12 Grains PER Gallon XW Model Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness INSPECT/FILL Condensate SystemLighting and Operating Instructions Setting of the Test Mode AdjustmentHigh Fire Rate Overview Control SystemBurner Control System Burner Control Operation SpecificationsCommunications and Displays General Operational Sequence Lead LAG LL Master General Operation Lead LAGDomestic HOT Water Definitions FeaturesLocal Operator Interface Display System Mounting the S7999B OI Display and Power Supply Installation Instructions S7999B OI DisplayQuick Setup S7999B OI Display Navigation POWER-UP ValidationCommon OI Display page Symbols Starting UP the S7999B OI DisplayS7999B Display page Flow Status or Home Configure ButtonKeyboard Configuration PasswordLogin Change Parameter SettingsParameter Verify Example of Change ConfigurationHistory Button FAULT/ALARM HandlingData Comment Example of Hydronic History Operation Button Control Expanded Alert DetailSystem Configuration S7999B OI Display only Diagnostics ButtonHydronic Control ConfigurationSystem Synchronization S7999B OI Display only Code Description Recommended Troubleshooting Lockout Codes TroubleshootingReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Allowed Code DescriptionFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors Inspect Boiler Area Maintenance ProceduresMaintenance Schedules General MaintenanceAIR Filter BOX Burner MaintenanceBlower Compartment Condensate Removal System Venting MaintenanceHeat Exchanger Maintenance Handling Ceramic Fiber Materials Replacement PartsInlet DIA Piping DiagramsStorage Tank AOS Conditions and Exceptions Limited Warranty

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.