A.O. Smith 2000 Direct Venting Vertical Termination, Prepare ROOF/WALL Penetrations, Clearances

Page 35

DIRECT VENTING: VERTICAL TERMINATION

Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.

VENT/AIR TERMINATION LOCATIONS:

Follow these guidelines for locating the vent/air terminations:

1.Make sure the total length of piping for vent or air do not exceed the limits mentioned in Table 14 and Table 15 on

Page 36.

2.The vent must terminate at least 3 feet above the highest place in which the vent penetrates the roof and at least 2 feet above any part of a building within 10 feet horizontal.

3.The air piping must terminate in a down-turned 180° elbow, using a mesh screen, no further than 2 feet (0.6 m) from the center of the vent pipe. This placement avoids recirculation of flue products into the combustion air stream.

4.The vent piping must terminate in an up-turned rain cap as shown in Figure 35. When the vent termination uses a rain cap as illustrated in Figure 35, maintain at least 36" (914

mm)above the air inlet. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet (0.6 m) apart and with the vent termination at least 1 foot above the air intake.

5.Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment and also not blocked or restricted by snow accumulation.

6.If installing both intake air and vent piping in a Direct Vent configuration vertically through the roof; ensure that all exterior vertical clearance requirements shown in Figure 35 are being maintained. These clearances and those cited by local and national codes must be maintained.

Note: On flat roof installations the intake air and the vent terminations must be a minimum of 24 inches (60 cm) above any parapet, vertical wall or structure within 10 feet (3 m) horizontally. See Figure 37.

Figure 36.  STAINLESS STEEL AIR/VENT TERMINATION -

VERTICAL

Figure 37.  VERTICAL TERMINATION - FLAT ROOF

CLEARANCES

PREPARE ROOF/WALL PENETRATIONS

1.Air pipe penetration:

Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

• 7½ inch (178 mm) hole for 6 inch (152 mm) vent pipe

• 8½ inch (203 mm) hole for 7 inch (178 mm) vent pipe

Insert a galvanized metal thimble in the vent pipe hole (when required by local codes).

3.Space the air and vent holes to provide the minimum spacing shown in Figure 35 and Figure 36.

4.Follow all local codes for isolation of vent pipe when passing through floors, ceilings, and roofs.

5.Provide flashing and sealing boots sized for the vent pipe and air pipe.

Figure 35.  PVC/CPVC AIR/VENT TERMINATION -

VERTICAL

35

Image 35
Contents XP Boiler Table of Contents Important Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Qualifications IntroductionModel Identification Abbreviations UsedOperating Characteristics Dimensions and Capacity DataDouble Heat Exchanger Boiler Rough in Dimensions Double Electrical Requirements RatingsXB Models FLOW, Head and Temperature Rise FLOW, Head and Temperature RiseSingle Heat Exchanger Boiler Components Features and ComponentsDouble Heat Exchanger Boiler Components Low water cutoff board and sensor probe Lwco Component DescriptionControl Components LOW Water Cutoff Device Lwco Flame Sensor Water Temperature SensorsWater Temperature Limit Controls Main Power Supply SwitchHydronic System Boiler Installation ConsiderationsGeneral Thermal Expansion Internal ContaminantsHOT Water Boiler System General Water Line Connections Closed Water SystemsGAS Connections Explosion HazardGAS Supply Line Sizing Corrosive Materials and Contamination SourcesLOW Voltage Control Wiring Field WiringVAC Power Supply Wiring Power Supply CheckSuggested Pipe Size for Multiple GAS Appliances Natural GAS Replacing Existing Common Vented Boiler General RequirementsRequired Ability LocationLeveling Installation ClearancesPanels and Covers Chemical Vapor CorrosionOutdoor AIR Through ONE Opening Confined Space Outdoor AIR Through TWO OpeningsFresh AIR Openings for Confined Spaces Ducts Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts AIR from Other Indoor SpacesVenting AIR Inlet Pipe Materials Vent and AIR Pipe InstallationRequirements for Installation in Canada Venting Supports Vertical Installation RequirementsHorizontal Installation Requirements Direct Vent Installation RequirementsModels Vent KIT Numbers XB/XW TEE Models Vent KIT Numbers XB/XW Rain CAPModels Vent AIR Intake XB/XW KIT Numbers Rain CAP Elbow Models Vent AIR Intake XB/XW KIT Numbers TEE ElbowDirect VENT, Vertical Vent Horizontal Intake Power Vent Termination Clearances Sidewall Power VentDirect Vent Termination Clearances Sidewall Direct VentBELOW. Keep Clear of ALL Obstructions Termination Direct Vent Horizontal TerminationVENT/AIR Termination Locations Clearances Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations VerticalModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch XP Models AO Smith Condensate Neutralizer KIT Numbers Condensate DisposalCondensate Neutralizer Condensate TrapGAS Pressure Requirements GAS Supply ConnectionsGAS Supply Pipe Connections Check for GAS Leaks Pipe Sizes for Propane GASPurging GAS Line Check GAS Supply Inlet PressureManifold Pressure Connections Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Boiler Start UP and OperationsWater Hardness Medium 0-12 Grains PER Gallon XW Model Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness INSPECT/FILL Condensate SystemLighting and Operating Instructions Setting of the Test Mode AdjustmentHigh Fire Rate Overview Control SystemBurner Control System Burner Control Operation SpecificationsCommunications and Displays General Operational Sequence Lead LAG LL Master General Operation Lead LAGDomestic HOT Water Definitions FeaturesLocal Operator Interface Display System Mounting the S7999B OI Display and Power Supply Installation Instructions S7999B OI DisplayQuick Setup S7999B OI Display Navigation POWER-UP ValidationCommon OI Display page Symbols Starting UP the S7999B OI DisplayS7999B Display page Flow Status or Home Configure ButtonKeyboard Configuration PasswordLogin Change Parameter SettingsParameter Verify Example of Change ConfigurationHistory Button FAULT/ALARM HandlingData Comment Example of Hydronic History Operation Button Control Expanded Alert DetailSystem Configuration S7999B OI Display only Diagnostics ButtonHydronic Control ConfigurationSystem Synchronization S7999B OI Display only Code Description Recommended Troubleshooting Lockout Codes TroubleshootingReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Allowed Code DescriptionFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors Inspect Boiler Area Maintenance ProceduresMaintenance Schedules General MaintenanceAIR Filter BOX Burner MaintenanceBlower Compartment Condensate Removal System Venting MaintenanceHeat Exchanger Maintenance Handling Ceramic Fiber Materials Replacement PartsInlet DIA Piping DiagramsStorage Tank AOS Conditions and Exceptions Limited Warranty

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.