A.O. Smith 2000 Pipe Sizes for Propane GAS, Purging GAS Line, Check GAS Supply Inlet Pressure

Page 39

PIPE SIZES FOR PROPANE GAS

Make sure to contact the gas supplier for pipe sizes, tanks, and 100% lockup gas pressure regulator.

PURGING GAS LINE

Gas line purging is required with new piping or systems in which air has entered. Gas purging should be performed per NFPA 54 for US and CAN B149.1 for Canada.

CHECK GAS SUPPLY INLET PRESSURE

CSA or UL listed flexible gas connections are acceptable, but make sure that the line has adequate capacity to allow your boiler to fire at full rate. Consult with local codes for proper installation or service procedures.

Do not adjust or attempt to measure gas valve outlet pressure. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

Make sure the gas piping are sized for the proper flow and length of pipe, to avoid excessive pressure drop. The gas meter and the gas regulator must be properly sized for the total gas load.

Perform the below steps when checking inlet gas supply:

1.Turn the main power switch to the “OFF” position.

2.Shut off gas supply.

3.Remove the 1/8" pipe plug on the main gas shutoff valve and install a suitable 1/8" fitting (field supplied) for the manometer tubing. Place the tubing of the manometer over the tap once the 1/8" fitting is installed.

4.Slowly turn on the gas supply.

5.Ensure inlet pressure is within specified range.

6.If the gas pressure is out of range, contact the gas utility, gas supplier, qualified installer or service agency to determine the necessary steps to provide proper gas pressure to the control.

CHECK FOR GAS LEAKS

Before operating the boiler, make sure to check the floor near and around the boiler for gas odorant or any unusual odor. Remove the top access panel and check for odor in the interior of the boiler enclosure. Do not start the boiler if there is any indication of a gas leak. Use an approved leak detection solution and repair any leaks at once.

In the case of propane boilers, the supplier mixes an odorant with the propane to make its presence detectable. But in some instances, the odorant can fade, and the gas may no longer have an odor. Before operating the boiler, make sure the propane supplier verify the correct odorant level in the gas.

Do not adjust or attempt to measure gas valve outlet pressure. The gas valve is factory set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

39

Image 39
Contents XP Boiler Table of Contents Safe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Qualifications IntroductionModel Identification Abbreviations UsedOperating Characteristics Dimensions and Capacity DataDouble Heat Exchanger Boiler Rough in Dimensions Double Electrical Requirements RatingsXB Models FLOW, Head and Temperature Rise FLOW, Head and Temperature RiseSingle Heat Exchanger Boiler Components Features and ComponentsDouble Heat Exchanger Boiler Components Low water cutoff board and sensor probe Lwco Component DescriptionControl Components LOW Water Cutoff Device Lwco Flame Sensor Water Temperature SensorsWater Temperature Limit Controls Main Power Supply SwitchBoiler Installation Considerations GeneralHydronic System Thermal Expansion Internal ContaminantsHOT Water Boiler System General Water Line Connections Closed Water SystemsGAS Connections Explosion HazardGAS Supply Line Sizing Corrosive Materials and Contamination SourcesLOW Voltage Control Wiring Field WiringVAC Power Supply Wiring Power Supply CheckSuggested Pipe Size for Multiple GAS Appliances Natural GAS Replacing Existing Common Vented Boiler General RequirementsRequired Ability LocationLeveling Installation ClearancesPanels and Covers Chemical Vapor CorrosionConfined Space Outdoor AIR Through TWO Openings Fresh AIR Openings for Confined SpacesOutdoor AIR Through ONE Opening Ducts Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts AIR from Other Indoor SpacesVenting Vent and AIR Pipe Installation Requirements for Installation in CanadaAIR Inlet Pipe Materials Venting Supports Vertical Installation RequirementsHorizontal Installation Requirements Direct Vent Installation RequirementsModels Vent KIT Numbers XB/XW TEE Models Vent KIT Numbers XB/XW Rain CAPModels Vent AIR Intake XB/XW KIT Numbers Rain CAP Elbow Models Vent AIR Intake XB/XW KIT Numbers TEE ElbowDirect VENT, Vertical Vent Horizontal Intake Power Vent Termination Clearances Sidewall Power VentDirect Vent Termination Clearances Sidewall Direct VentBELOW. Keep Clear of ALL Obstructions Direct Vent Horizontal Termination VENT/AIR Termination LocationsTermination Clearances Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations VerticalModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch XP Models AO Smith Condensate Neutralizer KIT Numbers Condensate DisposalCondensate Neutralizer Condensate TrapGAS Supply Connections GAS Supply Pipe ConnectionsGAS Pressure Requirements Check for GAS Leaks Pipe Sizes for Propane GASPurging GAS Line Check GAS Supply Inlet PressureManifold Pressure Connections Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Boiler Start UP and OperationsWater Hardness Medium 0-12 Grains PER Gallon XW Model Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness INSPECT/FILL Condensate SystemLighting and Operating Instructions Setting of the Test Mode AdjustmentHigh Fire Rate Control System Burner Control SystemOverview Specifications Communications and DisplaysBurner Control Operation General Operational Sequence Lead LAG Domestic HOT WaterLead LAG LL Master General Operation Features Local Operator Interface Display SystemDefinitions Installation Instructions S7999B OI Display Quick Setup S7999B OI DisplayMounting the S7999B OI Display and Power Supply Navigation POWER-UP ValidationCommon OI Display page Symbols Starting UP the S7999B OI DisplayS7999B Display page Flow Status or Home Configure ButtonKeyboard Configuration PasswordLogin Change Parameter SettingsParameter Verify Example of Change ConfigurationFAULT/ALARM Handling Data CommentHistory Button Example of Hydronic History Operation Button Control Expanded Alert DetailSystem Configuration S7999B OI Display only Diagnostics ButtonConfiguration System Synchronization S7999B OI Display onlyHydronic Control Code Description Recommended Troubleshooting Lockout Codes TroubleshootingReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Allowed Code DescriptionFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors Inspect Boiler Area Maintenance ProceduresMaintenance Schedules General MaintenanceBurner Maintenance Blower CompartmentAIR Filter BOX Venting Maintenance Heat Exchanger MaintenanceCondensate Removal System Handling Ceramic Fiber Materials Replacement PartsInlet DIA Piping DiagramsStorage Tank AOS Conditions and Exceptions Limited Warranty

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.