AIR INLET PIPE MATERIALS

Make sure the air inlet pipe(s) are sealed. The acceptable air inlet pipe materials are:

PVC/CPVC

AL 29-4C

An adapter is provided for transition between the air inlet connection on the boiler and the plastic air inlet pipe.

Seal all joints and seams of the air inlet pipe using either Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or a high quality UL Listed silicone sealant. Do not install seams of vent pipe on the bottom of horizontal runs.

Secure all joints with a minimum of 3 sheet metal screws or pop rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all screws or rivets installed in the vent pipe.

Make sure that the air inlet pipes are properly supported.

The PVC/ CPVC air inlet pipe must be cleaned and sealed with the pipe manufacturer’s recommended solvents and standard commercial pipe cement for the material used. The PVC, CPVC, air inlet pipe should use a silicone sealant to ensure a proper seal at the boiler connection and the air intake adapter connection. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.

VENT AND AIR PIPE INSTALLATION

1.Measure from the boiler level to vent. Refer to the Table 14 on Page 36 for the allowable lengths.

2.Prepare pipes to the required lengths and deburr the inside and outside of the pipe ends. Chamfer outside the pipe end to ensure even cement distribution when joining.

3.Clean all pipe ends and fittings using a clean dry rag. (Moisture will retard curing and dirt or grease will prevent adhesion.)

4.Dry fit vent or air piping to ensure proper fit before assembling any joint. The pipe should go a third to two-thirds into the fitting to ensure proper sealing after cement is applied.

5.Priming and Cementing:

Handle pipes and fittings carefully to prevent contamination of surfaces.

Apply an even coat of primer to the fitting socket.

Apply an even coat of primer to the pipe end to approximately 1/2" beyond the socket depth.

Apply a second primer coat to the fitting socket.

While primer is still wet, apply an even coat of approved cement to the pipe equal to the depth of the fitting socket.

While primer is still wet, apply an even coat of approved cement to the fitting socket.

Apply a second coat of cement to the pipe.

While the cement is still wet, insert the pipe into the fitting, if possible twist the pipe a 1/4 turn as you insert it.

Note: If voids are present, sufficient cement was not applied and joint could be defective.

Clear excess cement from the joint removing ring or beads as it will needlessly soften the pipe.

When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume.

Failure to properly seal all joints and seams may result in flue gas recirculation, spillage of flue products and carbon monoxide emissions causing severe personal injury or death.

Figure 22.  PVC/CPVC VENTING WITH ADAPTER

REQUIREMENTS FOR INSTALLATION IN CANADA

1.Installations must be made with a vent pipe system certified to ULC-S636. IPEX is an approved vent manufacturer in Canada supplying vent material listed to ULC-S636.

2.The initial 3 feet of plastic vent pipe from the appliance flue outlet must be readily accessible for visual inspection.

3.The components of the certified vent system must not be interchanged with other vent systems or unlisted pipe/ fittings.

Figure 23.  PVC/CPVC VENTING - HORIZONTAL

26

Image 26
Contents XP Boiler Table of Contents Important Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Abbreviations Used IntroductionModel Identification QualificationsDimensions and Capacity Data Operating CharacteristicsDouble Heat Exchanger Boiler Rough in Dimensions Double Ratings Electrical RequirementsFLOW, Head and Temperature Rise XB Models FLOW, Head and Temperature RiseFeatures and Components Single Heat Exchanger Boiler ComponentsDouble Heat Exchanger Boiler Components Component Description Low water cutoff board and sensor probe LwcoControl Components Main Power Supply Switch Flame Sensor Water Temperature SensorsWater Temperature Limit Controls LOW Water Cutoff Device LwcoHydronic System Boiler Installation ConsiderationsGeneral Closed Water Systems Internal ContaminantsHOT Water Boiler System General Water Line Connections Thermal ExpansionExplosion Hazard GAS ConnectionsCorrosive Materials and Contamination Sources GAS Supply Line SizingPower Supply Check Field WiringVAC Power Supply Wiring LOW Voltage Control WiringSuggested Pipe Size for Multiple GAS Appliances Natural GAS Location General RequirementsRequired Ability Replacing Existing Common Vented BoilerChemical Vapor Corrosion Installation ClearancesPanels and Covers LevelingOutdoor AIR Through ONE Opening Confined Space Outdoor AIR Through TWO OpeningsFresh AIR Openings for Confined Spaces AIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts DuctsVenting AIR Inlet Pipe Materials Vent and AIR Pipe InstallationRequirements for Installation in Canada Direct Vent Installation Requirements Vertical Installation RequirementsHorizontal Installation Requirements Venting SupportsModels Vent KIT Numbers XB/XW Rain CAP Models Vent KIT Numbers XB/XW TEEModels Vent AIR Intake XB/XW KIT Numbers TEE Elbow Models Vent AIR Intake XB/XW KIT Numbers Rain CAP ElbowDirect VENT, Vertical Vent Horizontal Intake Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentBELOW. Keep Clear of ALL Obstructions Termination Direct Vent Horizontal TerminationVENT/AIR Termination Locations Vertical Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations ClearancesModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch Condensate Trap Condensate DisposalCondensate Neutralizer XP Models AO Smith Condensate Neutralizer KIT NumbersGAS Pressure Requirements GAS Supply ConnectionsGAS Supply Pipe Connections Check GAS Supply Inlet Pressure Pipe Sizes for Propane GASPurging GAS Line Check for GAS LeaksBoiler Start UP and Operations Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Manifold Pressure ConnectionsINSPECT/FILL Condensate System Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness Water Hardness Medium 0-12 Grains PER Gallon XW ModelLighting and Operating Instructions Adjustment Setting of the Test ModeHigh Fire Rate Overview Control SystemBurner Control System Burner Control Operation SpecificationsCommunications and Displays General Operational Sequence Lead LAG LL Master General Operation Lead LAGDomestic HOT Water Definitions FeaturesLocal Operator Interface Display System Mounting the S7999B OI Display and Power Supply Installation Instructions S7999B OI DisplayQuick Setup S7999B OI Display Starting UP the S7999B OI Display POWER-UP ValidationCommon OI Display page Symbols NavigationS7999B Display page Flow Configure Button Status or HomeChange Parameter Settings Configuration PasswordLogin KeyboardExample of Change Configuration Parameter VerifyHistory Button FAULT/ALARM HandlingData Comment Example of Hydronic History Control Expanded Alert Detail Operation ButtonDiagnostics Button System Configuration S7999B OI Display onlyHydronic Control ConfigurationSystem Synchronization S7999B OI Display only Troubleshooting Code Description Recommended Troubleshooting Lockout CodesReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Code Description AllowedFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors General Maintenance Maintenance ProceduresMaintenance Schedules Inspect Boiler AreaAIR Filter BOX Burner MaintenanceBlower Compartment Condensate Removal System Venting MaintenanceHeat Exchanger Maintenance Replacement Parts Handling Ceramic Fiber MaterialsPiping Diagrams Inlet DIAStorage Tank AOS Limited Warranty Conditions and Exceptions

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.