A.O. Smith 1700, 3400, 2600 Communications and Displays, Specifications, Burner Control Operation

Page 46

COMMUNICATIONS AND DISPLAYS

Two modes of communications are available to the R7910.

1.The R7910 has two RS485 communication ports for ModBus that allows for interfacing to one or all R7910s of a system and presents them individually to the user. The S7999B System Operator interface is a color touchscreen displays used for configuration and monitoring of the R7910A. Control Operation and display status in both test and graphical modes can be shown along with the ability to setup. The R7910 can also be remotely reset through the S7999B display.

2.Either ModBus RS485 communication port can be used to allow configuration and status data to be read and written to the R7910. Support a Master S7999B or a Building Automation master to control the R7910 to respond to a single ModBus address to service the requests of the ModBus master in a Lead/Lag arrangement.

The local S7910 Keyboard display, the S7999B System Operator interface, and the S7999C Local Operator Interface are optional components.

The S7999B (or the DSP3944 which is a portable S7999B) or is required configuration of the parameters of the R7910 but is not needed for the operation of the system once configured.

SPECIFICATIONS

1.Electrical Ratings: Operating voltage

24VAC (20 to 30 VAC, 60 Hz ±5%)

30 amps (Single Heat Exchanger)

60 amps (Double Heat Exchanger)

Connected Load for Valve and annunciator functions:

24VAC, 60Hz

120VAC (+10%/-15%), 60Hz (±5%)

Model Specific

2.Corrosion:

R7910A must not be used in a corrosive environment.

3.Operating Temperature: -4°F to 150°F (-20°C to 66°C)

4.Storage/Shipping Temperature: -40°F to 150°F (-40°C to 66°C).

5.Humidity:

Up to 95% Relative Humidity, noncondensing at 104°F for 14 days. Condensing moisture may cause safety shutdown.

6.Vibration: 0.0 to 0.5g Continuous (V2 level)

7.Enclosure: Nema 1/IP40.

8.Approvals:

Underwriters Laboratories, Inc. (UL): Component Recognized: File No. MP268 (MCCZ)

R7910 is certified as UL372 Primary Safety Controls.

The R7910 is certified as UL353 Limit Rated device when using part number 50001464 dual element limit rated NTC sensors.

CSD-1 Acceptable.

Meets CSD-1 section CF-300 requirements as a Primary Safety Control.

Meets CSD-1 section CW-400 requirements as a Temperature Operation control.

Meets CSD-1 section CW-400 requirements as a Temperature High Limit Control when configured for use with 10 kohm NTC sensors.

Federal Communications Commission, Part 15, Class B. Emissions.

BURNER CONTROL OPERATION

SAFETY SHUTDOWN OF BURNER CONTROL FUNCTIONS

Safety Shutdown (Lockout) occurs if any of the following occur during the indicated period:

1.INITIATE PERIOD:

a. A/C line power errors occurred.

b. Four minute INITIATE period has been exceeded.

2. STANDBY PERIOD:

a. Flame signal is present after 240 seconds.

b. Preignition Interlock is open an accumulative time of 30 seconds.

c. Interlock Start check feature is enabled and the Interlock String (including Airflow Switch) is closed for 120 seconds with the controller closed. (jumpered or welded Interlock).

d. Main Valve Terminal is energized. e. Internal system fault occurred.

3. PREPURGE PERIOD:

a. Preignition Interlock opens anytime during PREPURGE period.

b. Flame signal is detected for 10 seconds accumulated time during PREPURGE.

c. Purge Rate Fan RPM or High Fire Switch fails to close within four minutes and fifteen seconds after the firing rate motor is commanded to drive to the high fire position at the start of

PREPURGE.

d. Light off Rate Fan RPM or Low Fire Switch fails to close within four minutes and fifteen seconds after the firing rate motor is commanded to drive to the low fire position at the end of

PREPURGE.

e. Lockout Interlock (if programmed) does not close within 10 seconds.

f. Lockout Interlock opens during PREPURGE. g. Pilot Valve terminal is energized.

h. Main Valve terminal is energized. i. Internal system fault occurred.

4. PRE-IGNITION TIME

a. Lockout Interlock opens.

b. IAS Purge and Ignition enabled and the Interlock opens. c. Preignition Interlock opens.

d. Pilot Valve terminal is energized. e. Main Valve terminal is energized.

5. PILOT FLAME ESTABLISHING PERIOD (PFEP):

a. Lockout Interlock opens (if enabled). b. Pilot Valve terminal is not energized.

c. No flame is present at the end of the PFEP, or after programmed number of retry attempts.

d. Main valve terminal is energized. e. Internal system fault occurred.

46

Image 46
Contents XP Boiler Table of Contents Approvals Safe INSTALLATION, USE and ServiceImportant Definitions General Safety Abbreviations Used IntroductionModel Identification QualificationsDimensions and Capacity Data Operating CharacteristicsDouble Heat Exchanger Boiler Rough in Dimensions Double Ratings Electrical RequirementsFLOW, Head and Temperature Rise XB Models FLOW, Head and Temperature RiseFeatures and Components Single Heat Exchanger Boiler ComponentsDouble Heat Exchanger Boiler Components Component Description Low water cutoff board and sensor probe LwcoControl Components Main Power Supply Switch Flame Sensor Water Temperature SensorsWater Temperature Limit Controls LOW Water Cutoff Device LwcoGeneral Boiler Installation ConsiderationsHydronic System Closed Water Systems Internal ContaminantsHOT Water Boiler System General Water Line Connections Thermal ExpansionExplosion Hazard GAS ConnectionsCorrosive Materials and Contamination Sources GAS Supply Line SizingPower Supply Check Field WiringVAC Power Supply Wiring LOW Voltage Control WiringSuggested Pipe Size for Multiple GAS Appliances Natural GAS Location General RequirementsRequired Ability Replacing Existing Common Vented BoilerChemical Vapor Corrosion Installation ClearancesPanels and Covers LevelingFresh AIR Openings for Confined Spaces Confined Space Outdoor AIR Through TWO OpeningsOutdoor AIR Through ONE Opening AIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts DuctsVenting Requirements for Installation in Canada Vent and AIR Pipe InstallationAIR Inlet Pipe Materials Direct Vent Installation Requirements Vertical Installation RequirementsHorizontal Installation Requirements Venting SupportsModels Vent KIT Numbers XB/XW Rain CAP Models Vent KIT Numbers XB/XW TEEModels Vent AIR Intake XB/XW KIT Numbers TEE Elbow Models Vent AIR Intake XB/XW KIT Numbers Rain CAP ElbowDirect VENT, Vertical Vent Horizontal Intake Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentBELOW. Keep Clear of ALL Obstructions VENT/AIR Termination Locations Direct Vent Horizontal TerminationTermination Vertical Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations ClearancesModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch Condensate Trap Condensate DisposalCondensate Neutralizer XP Models AO Smith Condensate Neutralizer KIT NumbersGAS Supply Pipe Connections GAS Supply ConnectionsGAS Pressure Requirements Check GAS Supply Inlet Pressure Pipe Sizes for Propane GASPurging GAS Line Check for GAS LeaksBoiler Start UP and Operations Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Manifold Pressure ConnectionsINSPECT/FILL Condensate System Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness Water Hardness Medium 0-12 Grains PER Gallon XW ModelLighting and Operating Instructions Adjustment Setting of the Test ModeHigh Fire Rate Burner Control System Control SystemOverview Communications and Displays SpecificationsBurner Control Operation General Operational Sequence Domestic HOT Water Lead LAGLead LAG LL Master General Operation Local Operator Interface Display System FeaturesDefinitions Quick Setup S7999B OI Display Installation Instructions S7999B OI DisplayMounting the S7999B OI Display and Power Supply Starting UP the S7999B OI Display POWER-UP ValidationCommon OI Display page Symbols NavigationS7999B Display page Flow Configure Button Status or HomeChange Parameter Settings Configuration PasswordLogin KeyboardExample of Change Configuration Parameter VerifyData Comment FAULT/ALARM HandlingHistory Button Example of Hydronic History Control Expanded Alert Detail Operation ButtonDiagnostics Button System Configuration S7999B OI Display onlySystem Synchronization S7999B OI Display only ConfigurationHydronic Control Troubleshooting Code Description Recommended Troubleshooting Lockout CodesReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Code Description AllowedFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors General Maintenance Maintenance ProceduresMaintenance Schedules Inspect Boiler AreaBlower Compartment Burner MaintenanceAIR Filter BOX Heat Exchanger Maintenance Venting MaintenanceCondensate Removal System Replacement Parts Handling Ceramic Fiber MaterialsPiping Diagrams Inlet DIAStorage Tank AOS Limited Warranty Conditions and Exceptions

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.