A.O. Smith 1700, 3400, 2600 Corrosive Materials and Contamination Sources, GAS Supply Line Sizing

Page 18

It is important to guard against gas valve fouling from contaminants in the gas ways. Such fouling may cause improper operation, fire or explosion. If copper supply lines are used they must be approved for gas service.

When local codes require a main manual shut-off valve outside the boiler jacket, a suitable main manual shut-off valve must be installed in a location complying with those codes.

Before attaching gas line be sure that all gas pipe is clean on inside. To trap any dirt or foreign material in the gas supply line, a drip leg (or sediment trap) must be incorporated in piping. The drip leg must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas supplier. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CAN/CSA B149.1

Size of gas supply piping may be larger than heater connection on installations where a significant run of piping is required.

To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to boiler gas inlet. When installing and tightening gas piping use a second wrench to hold the gas valve to keep the valve from turning. To prevent damage to the gas valve do not use pipe wrench on the valve body.

Fittings and unions in gas line must be of metal to metal type. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases. The boiler and its gas connection must be leak tested before placing the boiler in operation.

GAS SUPPLY LINE SIZING

The gas piping installation must be capable of supplying the maximum probable gas demand without excessive pressure loss. Depending on local practices, the ALLOWABLE PRESSURE LOSS between the gas meter, or service regulator and each appliance is generally 0.3 or 0.5 inches of water column (0.075 or 0.124 kPa).

For single boiler installation, refer to Table 8 and Table 9 to size iron pipe or equivalent gas supply line size to be used with single unit.

For multiple boiler installation or installations of a single boiler with other gas appliances, please refer to Table 10 and Table 11 on Page 20 to size iron pipe or equivalent gas supply line. These tables are taken from the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CAN/CSA B149.1.

Table 10 is based on a pressure drop of 0.5 inches water column (0.124 kPa), and a gas with a specific gravity of

0.60and a heating value of 1,000 BTU/ft3, approximately that of Natural Gas.

Table 11 is based on a pressure drop of 0.5 inches water column (0.124 kPa), and a gas with a specific gravity of

1.53and a heating value of 2,500 BTU/ft3, approximately that of Propane Gas.

Where it is necessary to use more than the average number of fittings (i.e., elbows, tees and valves in gas supply line) use a pipe larger than specified to compensate for increased pressure drop.

Table 8 and Table 9 shows the maximum equivalent gas pipe length for a single unit installation. It does not take into account other appliances that may be connected to the gas line. For installation of multiple units, or instances where several appliances are connected to the same line, use Table 10 and Table 11 for proper sizing.

Table 8. 

SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE SIZING. MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).

BTU

2”

 

2-1/2”

3”

 

 

4”

Input

Nat

 

Pro

Nat

Pro

Nat

 

Pro

Nat

 

Pro

920,000

70

 

150

175

-----

-----

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

1,300,000

40

 

100

100

200

-----

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

1,700,000

20

 

60

70

150

200

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

2,000,000

20

 

50

50

100

150

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

2,600,000

10

 

30

30

70

90

 

200

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

3,400,000

-----

 

-----

20

40

50

 

125

200

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

Natural gas 1000 Btu/ft^3, 0.60 specific gravity @ 0.3 in. w.c. pressure drop. Propane gas 2500 Btu/ft^3, 1.50 specific gravity @ 0.3 in. w.c. pressure drop.

Table 9. 

SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE SIZING. MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).

BTU

2”

 

2-1/2”

3”

 

 

4”

Input

Nat

 

Pro

Nat

Pro

Nat

 

Pro

Nat

 

Pro

920,000

125

 

200

200

-----

-----

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

1,300,000

80

 

175

175

-----

-----

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

1,700,000

40

 

100

100

-----

-----

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

2,000,000

30

 

80

80

200

200

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

2,600,000

20

 

50

50

125

150

 

-----

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

3,400,000

10

 

30

30

70

90

 

200

-----

 

-----

 

 

 

 

 

 

 

 

 

 

 

 

Natural gas 1000 Btu/ft^3, 0.63 specific gravity @ 0.5 in. w.c. pressure drop. Propane gas 2500 Btu/ft^3, 1.50 specific gravity @ 0.5 in. w.c. pressure drop.

CORROSIVE MATERIALS AND CONTAMINATION SOURCES

Products to avoid:

Spray cans containing chloro/fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms

Adhesives used to fasten building products and other similar products

Areas likely to have contaminants:

Dry cleaning/laundry areas and establishments

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

18

Image 18
Contents XP Boiler Table of Contents Safe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Abbreviations Used IntroductionModel Identification QualificationsDimensions and Capacity Data Operating CharacteristicsDouble Heat Exchanger Boiler Rough in Dimensions Double Ratings Electrical RequirementsFLOW, Head and Temperature Rise XB Models FLOW, Head and Temperature RiseFeatures and Components Single Heat Exchanger Boiler ComponentsDouble Heat Exchanger Boiler Components Component Description Low water cutoff board and sensor probe LwcoControl Components Main Power Supply Switch Flame Sensor Water Temperature SensorsWater Temperature Limit Controls LOW Water Cutoff Device LwcoBoiler Installation Considerations GeneralHydronic System Closed Water Systems Internal ContaminantsHOT Water Boiler System General Water Line Connections Thermal ExpansionExplosion Hazard GAS ConnectionsCorrosive Materials and Contamination Sources GAS Supply Line SizingPower Supply Check Field WiringVAC Power Supply Wiring LOW Voltage Control WiringSuggested Pipe Size for Multiple GAS Appliances Natural GAS Location General RequirementsRequired Ability Replacing Existing Common Vented BoilerChemical Vapor Corrosion Installation ClearancesPanels and Covers LevelingConfined Space Outdoor AIR Through TWO Openings Fresh AIR Openings for Confined SpacesOutdoor AIR Through ONE Opening AIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts DuctsVenting Vent and AIR Pipe Installation Requirements for Installation in CanadaAIR Inlet Pipe Materials Direct Vent Installation Requirements Vertical Installation RequirementsHorizontal Installation Requirements Venting SupportsModels Vent KIT Numbers XB/XW Rain CAP Models Vent KIT Numbers XB/XW TEEModels Vent AIR Intake XB/XW KIT Numbers TEE Elbow Models Vent AIR Intake XB/XW KIT Numbers Rain CAP ElbowDirect VENT, Vertical Vent Horizontal Intake Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentBELOW. Keep Clear of ALL Obstructions Direct Vent Horizontal Termination VENT/AIR Termination LocationsTermination Vertical Direct Venting Vertical TerminationPrepare ROOF/WALL Penetrations ClearancesModel Vent Diameter Vent MIN. Length Vent MAX. Length Inch Condensate Trap Condensate DisposalCondensate Neutralizer XP Models AO Smith Condensate Neutralizer KIT NumbersGAS Supply Connections GAS Supply Pipe ConnectionsGAS Pressure Requirements Check GAS Supply Inlet Pressure Pipe Sizes for Propane GASPurging GAS Line Check for GAS LeaksBoiler Start UP and Operations Filling and Purging of Heating Boiler InstallationFilling HOT Water Supply Boiler Installation Manifold Pressure ConnectionsINSPECT/FILL Condensate System Freeze Protection Hydronic Heating InstallationCHECK/CONTROL Water Hardness Water Hardness Medium 0-12 Grains PER Gallon XW ModelLighting and Operating Instructions Adjustment Setting of the Test ModeHigh Fire Rate Control System Burner Control SystemOverview Specifications Communications and DisplaysBurner Control Operation General Operational Sequence Lead LAG Domestic HOT WaterLead LAG LL Master General Operation Features Local Operator Interface Display SystemDefinitions Installation Instructions S7999B OI Display Quick Setup S7999B OI DisplayMounting the S7999B OI Display and Power Supply Starting UP the S7999B OI Display POWER-UP ValidationCommon OI Display page Symbols NavigationS7999B Display page Flow Configure Button Status or HomeChange Parameter Settings Configuration PasswordLogin KeyboardExample of Change Configuration Parameter VerifyFAULT/ALARM Handling Data CommentHistory Button Example of Hydronic History Control Expanded Alert Detail Operation ButtonDiagnostics Button System Configuration S7999B OI Display onlyConfiguration System Synchronization S7999B OI Display onlyHydronic Control Troubleshooting Code Description Recommended Troubleshooting Lockout CodesReserved ILK OFF Flame Operation Faults 105 Flame detected out of sequence Adjust the LF switch while in this position Inspect the Combustion Pressure Switch to make Code Description Recommended Troubleshooting Lockout Codes Code Description Recommended Troubleshooting Lockout Codes Code Description AllowedFan Parameter Errors Code Description Steam 20mA water temperature setting was invalid Abnormal Recycle Hardware flame bias delta high Eeprom DHW Plate Heat Exchanger Errors General Maintenance Maintenance ProceduresMaintenance Schedules Inspect Boiler AreaBurner Maintenance Blower CompartmentAIR Filter BOX Venting Maintenance Heat Exchanger MaintenanceCondensate Removal System Replacement Parts Handling Ceramic Fiber MaterialsPiping Diagrams Inlet DIAStorage Tank AOS Limited Warranty Conditions and Exceptions

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.