Same tube sizes are capable of handling higher flowrates (expressed as tons of cooling capacity) with Puron refrigerant compared to
Installation –
1.Remove the existing evaporator coil or fan coil and install the replacement coil when appropriate.
2.Drain oil from low points and traps in suction line tubing (and hot gas bypass tubing if appropriate) and evaporator if they were not replaced. Removing oil from evaporator coil may require purging of the tubing with dry nitrogen.
3.Unless indoor unit is equipped with a Puron→ ap- proved metering device, change the metering device to a thermal expansion valve (TXV) designed for PuronR
4.Remove the existing outdoor unit. Install the new out- door unit according to these installation instructions.
5.Install a new
6.If a suction line filter drier is also to be installed, in- stall suction line drier downstream of suction line ser- vice valve at condensing unit.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never install
7.If required, install a 100% activated alumina suction line filter drier at the outdoor unit.
8.Evacuate and charge the system according to the in- structions in this installation manual.
9.Operate the system for 10 hr. Monitor the pressure drop across the suction line filter drier. If pressure drop exceeds 3 psig (21kPa), replace