Carrier 38AU Appendix C, Low Ambient Option - Factory Installed, Operation, Troubleshooting

Models: 38AU

1 56
Download 56 pages 45.1 Kb
Page 47
Image 47
APPENDIX C

APPENDIX C

Low Ambient Option — Factory Installed

Units with the factory installed low ambient option are equipped with a MotormasterR solid-state head pressure control which regulates fan speed. A temperature sensor, mounted on circuit 1 of the outdoor coil (see Figs. 44 and

45)controls the speed of approved outdoor fan motors in order to maintain a constant head pressure in the outdoor coil. The control maintains the appropriate head pressure at low ambient temperatures down to -20_F (-28_C).

Wind baffles are required to prevent wind cross currents from causing abnormally low condensing temperatures.

SUse 20-gauge sheet metal to fabricate wind baffles (see Fig. 46 and Table 14) and mounting brackets (see Fig. 47).

NOTE: Mounting brackets are for use on 15 ton model units only.

S Install the wind baffles as show in Fig. 48, for 15 ton units and Fig. 49, for 20 ton units .

Operation —

Fan on/off control in cooling-only units (38AUZ, 38AUD) is provided by an outdoor fan relay (OFR).

In cooling mode, fan motor speed of outdoor motors OFM1 and OFM3 is regulated by the speed control temperature sensor on outdoor coil 1 for a minimum coil condensing temperature of approximately 100_F (38_C) at higher outdoor ambient temperature and 80_F (27_C) at lower ambient. Additionally, outdoor fan motor OFM2 and OFM4 are turned on/off by the low ambient temperature switch, LAS, operating the low ambient relay (LAR). The LAS control temperatures are open 42_F +/- 5_F, close 57_F +/- 5_F (open 5.5_C +/- 2.8_C, close 13.9_C +/- 2.8_C).

To override the speed control for full fan speed operation during service or maintenance, either:

a.remove sensor and place in hot water >120_F (>49_C), or

b.rewire to bypass control by connecting speed control input and output power wires.

Troubleshooting —

OBSERVATION

POSSIBLE REMEDY

Fans won’t start

All fans:

 

Check power & wiring

 

Check outdoor fan relay (OFR)

 

OFM1, OFM3 only:

 

Check speed control sensor location

 

Check speed sensor resistance

 

OFM2, OFM4 only:

 

Check low ambient switch (LAS)

 

Check low ambient relay (LAR)

 

 

Cooling --- Center outdoor

Normal operation

fans (OFM2, OFM4) off

 

below approximately 60_F

 

(16_C) outdoor ambient.

 

 

 

Cooling --- Center outdoor

Check low ambient switch (LAS)

fans (OFM2, OFM4) not on

Check low ambient relay (LAR)

above approximately 60_F

 

(16_C) outdoor ambient

 

 

 

Cooling --- Slow fan speed

Normal operation

for outer fans (OFM1,

 

OFM3) at start or during

 

low outdoor ambient

 

 

 

Cooling --- Slow fan speed

Check speed control sensor location

for outer fans (OFM1,

Check speed control sensor

OFM3) above 85_F (29_F)

resistance

outdoor ambient (should

Check fan motor capacitor

be full speed)

 

 

 

Cooling --- motor current

Normal operation

into speed control is

Up to 30% higher A at partial speed

greater than motor name-

at low ambient

plate FLA

 

 

 

Speed Control Sensor Resistance —

TEMPERATURE

RESISTANCE

_F +/---2_F

_C +/---1_C

Ohms, nominal

 

 

 

--- 22

--- 30

88350

 

 

 

--- 4

--- 20

48485

 

 

 

14

--- 10

27650

 

 

 

32

0

16325

 

 

 

50

10

9950

 

 

 

68

20

6245

 

 

 

77

25

5000

 

 

 

86

30

4028

 

 

 

104

40

2663

 

 

 

122

50

1801

 

 

 

140

60

1244

 

 

 

158

70

876

38AU

47

Page 47
Image 47