APPENDIX C
Low Ambient Option — Factory Installed
Units with the factory installed low ambient option are equipped with a MotormasterR
45)controls the speed of approved outdoor fan motors in order to maintain a constant head pressure in the outdoor coil. The control maintains the appropriate head pressure at low ambient temperatures down to
Wind baffles are required to prevent wind cross currents from causing abnormally low condensing temperatures.
SUse
NOTE: Mounting brackets are for use on 15 ton model units only.
S Install the wind baffles as show in Fig. 48, for 15 ton units and Fig. 49, for 20 ton units .
Operation —
Fan on/off control in
In cooling mode, fan motor speed of outdoor motors OFM1 and OFM3 is regulated by the speed control temperature sensor on outdoor coil 1 for a minimum coil condensing temperature of approximately 100_F (38_C) at higher outdoor ambient temperature and 80_F (27_C) at lower ambient. Additionally, outdoor fan motor OFM2 and OFM4 are turned on/off by the low ambient temperature switch, LAS, operating the low ambient relay (LAR). The LAS control temperatures are open 42_F +/- 5_F, close 57_F +/- 5_F (open 5.5_C +/- 2.8_C, close 13.9_C +/- 2.8_C).
To override the speed control for full fan speed operation during service or maintenance, either:
a.remove sensor and place in hot water >120_F (>49_C), or
b.rewire to bypass control by connecting speed control input and output power wires.
Troubleshooting —
OBSERVATION | POSSIBLE REMEDY |
Fans won’t start | All fans: |
| Check power & wiring |
| Check outdoor fan relay (OFR) |
| OFM1, OFM3 only: |
| Check speed control sensor location |
| Check speed sensor resistance |
| OFM2, OFM4 only: |
| Check low ambient switch (LAS) |
| Check low ambient relay (LAR) |
|
|
Cooling | Normal operation |
fans (OFM2, OFM4) off |
|
below approximately 60_F |
|
(16_C) outdoor ambient. |
|
|
|
Cooling | Check low ambient switch (LAS) |
fans (OFM2, OFM4) not on | Check low ambient relay (LAR) |
above approximately 60_F |
|
(16_C) outdoor ambient |
|
|
|
Cooling | Normal operation |
for outer fans (OFM1, |
|
OFM3) at start or during |
|
low outdoor ambient |
|
|
|
Cooling | Check speed control sensor location |
for outer fans (OFM1, | Check speed control sensor |
OFM3) above 85_F (29_F) | resistance |
outdoor ambient (should | Check fan motor capacitor |
be full speed) |
|
|
|
Cooling | Normal operation |
into speed control is | Up to 30% higher A at partial speed |
greater than motor name- | at low ambient |
plate FLA |
|
|
|
Speed Control Sensor Resistance —
TEMPERATURE | RESISTANCE | |
_F | _C | Ohms, nominal |
|
|
|
88350 | ||
|
|
|
48485 | ||
|
|
|
14 | 27650 | |
|
|
|
32 | 0 | 16325 |
|
|
|
50 | 10 | 9950 |
|
|
|
68 | 20 | 6245 |
|
|
|
77 | 25 | 5000 |
|
|
|
86 | 30 | 4028 |
|
|
|
104 | 40 | 2663 |
|
|
|
122 | 50 | 1801 |
|
|
|
140 | 60 | 1244 |
|
|
|
158 | 70 | 876 |
38AU