Enter the appropriate table to select the recommended line sizes.

Model:

Line Sizes Table

Quantity of Line Sets

 

 

 

38AUZ

5

1

 

 

 

38AUD

6

2

 

 

 

Liquid Lift —

A liquid lift condition exists when the outdoor unit is located below the indoor (evaporator) unit and liquid flows vertically up in a portion of the liquid line. The vertical column of liquid reduces the available state point subcooling at the evaporator coil’s thermal expansion valve. This effect reduces the length of liquid lift (feet of elevation) that a liquid line size can accommodate. Longer linear tube lengths will also reduce the amount of liquid lift possible.

Check Tables 5 (38AUZ) and 6 (38AUD) for maximum liquid lift capabilities for line sizes. Reselect the liquid

line tube size if necessary. If maximum available tube size cannot provide the required lift distance on this installation, relocate the outdoor unit to reduce the equivalent line length or the lift requirement.

Suction Riser —

A suction riser condition exists when the outdoor unit is located above the indoor (evaporator) unit and suction vapor must flow vertically up to return to the compressor. Oil return is a concern when the suction tube size is too large to produce the minimum refrigerant velocity to ensure oil return at minimum load conditions.

Check Table 7 for maximum suction tube size for 38AU units at minimum load conditions. Consider suction speed riser (reduced tube size for vertical segment only) or double suction riser arrangement if the recommended suction tube size does not provide necessary minimum flowrates for this riser.

38AU

Table 5 – 38AUZ 16-25 Piping Recommendations (Single-Circuit Unit)

R-410A

 

 

 

 

 

 

Equivalent Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ft

 

 

0-38

 

38-75

 

75-113

 

113-150

150-188

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m

 

 

0-12

 

12-23

 

23-34

 

34-46

46-57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Linear Length

 

 

 

 

 

 

 

 

 

 

 

Ft

 

 

0-25

 

25-50

 

50-75

 

75-100

100-125

 

Model

m

 

 

0-8

 

8-15

 

15-23

 

23-30

30-38

 

38AUZ*16

Liquid Line

 

5/8

 

5/8

 

5/8

 

5/8

5/8

 

 

Max Lift

 

25

 

50

 

75

 

100

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

 

1-1/8

 

1-3/8

 

1-3/8

 

1-3/8

1-3/8

1-5/8

 

Charge (lbs)

 

 

 

 

 

 

 

 

 

 

 

Novation

 

24.3

 

27.5

 

30.6

 

33.7

37.8

 

 

RTPF

 

42.7

 

45.9

 

49.0

 

52.1

56.2

 

 

 

 

 

 

 

 

 

 

 

 

 

38AUZ*25

Liquid Line

 

5/8

 

5/8

 

5/8

 

5/8

5/8

 

 

Max Lift

 

25

 

50

 

71

 

77

63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

 

1-1/8

1-3/8

1-3/8

 

1-3/8

1-5/8

1-5/8

1-5/8

 

 

Charge (lbs)

 

37.8

 

40.8

 

44.6

 

47.8

51.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legend:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equivalent

Equivalent tubing length, including effects of refrigeration specialties devices

 

 

 

Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Linear Length

Typical linear tubing length, (50% added to linear to define Equivalent Length for this table)

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line

Tubing size, inches OD.

 

 

 

 

 

 

 

 

 

 

Max Lift

Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —

 

S

Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV

 

 

 

S

Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

Tube size, inches OD

 

 

 

 

 

 

 

 

 

 

Charge

Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size

 

(where applicable)

 

 

 

 

 

 

 

 

 

 

 

NOTE:

For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m),

 

contact your local Carrier representative.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Page 13
Image 13
Carrier appendix Liquid Lift, Suction Riser, 38AUZ 16-25 Piping Recommendations Single-Circuit Unit