Air Conditioner & Heat Pump with PURON→
—Quick Reference Guide
S Puron→
S Puron→ refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S Puron→ systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating.
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S Puron→, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Use only factory specified
S Do not install a
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
SA factory approved,
S Do not use an
S If indoor unit is equipped with a TXV, it must be changed to a Puron→ TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, break vacuum with dry nitrogen before opening system.
S Always replace filter drier after opening system for service.
S Do not vent Puron→ into the atmosphere. S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text. S All Puron→ heat pumps must have indoor TXV.
S Do not leave Puron→ suction line driers in place for more than 72 hours.
APPENDIX B
Wiring Diagram List
Unit | Electrical Characteristics | Diagram Number |
|
|
|
38AUD*16 | 38AU500540 | |
|
|
|
| 38AU500541 | |
|
|
|
| 38AU500542 | |
|
|
|
38AUD*25 | 38AU500565 | |
|
|
|
| 38AU500566 | |
|
|
|
| 38AU500567 | |
|
|
|
38AUZ*16 | 38AU500537 | |
|
|
|
| 38AU500538 | |
|
|
|
| 38AU500539 | |
|
|
|
38AUZ*25 | 38AU500568 | |
|
|
|
| 38AU500569 | |
| 38AU500570 | |
|
|
|
46