TROUBLESHOOTING (cont)
| PROBLEM |
| SOLUTION |
|
|
| |
COMPRESSOR CYCLES ON |
|
| |
|
| ||
1. | Liquid line solenoid valve(s) fails to open. | 1. Check liquid line solenoid valve(s) for proper operation. Replace if necessary. | |
2. | Filter drier plugged. | 2. | Replace filter drier. |
3. | Expansion valve power head defective. | 3. | Replace power head. |
4. | Low refrigerant charge. | 4. | Add charge. Check |
Airflow Restricted |
|
| |
1. | Coil iced up. | 1. | Check refrigerant charge. |
2. | Coil dirty. | 2. | Clean coil fins. |
3. | Air filters dirty. | 3. | Clean or replace filters. |
4. | Dampers closed. | 4. | Check damper operation and position. |
|
| ||
1. | Electrical connections loose. | 1. | Tighten all connections. |
2. | Fan relay defective. | 2. | Replace relay. |
3. | Motor overload open. | 3. | Power supply. |
4. | Motor defective. | 4. | Replace motor. |
5. | Fan belt broken or slipping. | 5. | Replace or tighten belt. |
|
|
| |
COMPRESSOR RUNNING BUT COOLING INSUFFICIENT |
|
| |
Suction Pressure Low |
|
| |
1. | Refrigerant charge low. | 1. | Add refrigerant. |
2. | Head pressure low. | 2. | Check refrigerant charge. Check |
3. | Air filters dirty. | 3. | Clean or replace filters. |
4. | Expansion valve power head defective. | 4. | Replace power head. |
5. | Indoor coil partially iced. | 5. | Check |
6. | Indoor airflow restricted. | 6. | Remove obstruction. |
Suction Pressure High |
|
| |
1. | Heat load excessive. | 1. | Check for open doors or windows in vicinity of fan coil. |
|
|
| |
UNIT OPERATES TOO LONG OR CONTINUOUSLY |
|
| |
1. | Low refrigerant charge. | 1. | Add refrigerant. |
2. | Control contacts fused. | 2. | Replace control. |
3. | Air in system. | 3. | Purge and evacuate system. |
4. | Partially plugged expansion valve or filter drier. | 4. | Clean or replace. |
|
|
| |
SYSTEM IS NOISY |
|
| |
1. | Piping vibration. | 1. | Support piping as required. |
2. | Compressor noisy. | 2. | Replace compressor if bearings are worn. |
|
|
| |
COMPRESSOR LOSES OIL |
|
| |
1. | Leak in system. | 1. | Repair leak. |
2. | Crankcase heaters not energized during shutdown. | 2. | Check wiring and relays. Check heater and replace if defective. |
3. | Improper interconnecting piping design. | 3. | Check piping for oil return. Replace if necessary. |
|
|
| |
FROSTED SUCTION LINE |
|
| |
Expansion valve admitting excess refrigerant. | Adjust expansion valve. | ||
|
|
| |
HOT LIQUID LINE |
|
| |
1. | Shortage of refrigerant due to leak. | 1. | Repair leak and recharge. |
2. | Expansion valve opens too wide. | 2. | Adjust expansion valve. |
|
|
| |
FROSTED LIQUID LINE |
|
| |
1. | Restricted filter drier. | 1. | Remove restriction or replace. |
2. | Liquid line solenoid valve partially closed. | 2. | Replace valve. |
|
|
|
|