I. PRELIMINARY INFORMATION |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| OUTDOOR: MODEL NO. |
|
|
|
|
| SERIAL NO. |
|
|
| ||||||
| INDOOR: AIRHANDLER MANUFACTURER |
|
|
|
|
|
|
|
|
|
|
| ||||
| MODEL NO. |
|
|
|
|
| SERIAL NO. |
|
|
| ||||||
| ADDITIONAL ACCESSORIES |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
II. |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| OUTDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| IS THERE ANY SHIPPING DAMAGE? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
| |||
| IF SO, WHERE: |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||||||
| WILL THIS DAMAGE PREVENT UNIT |
| (Y/N) |
|
|
|
|
| ||||||||
| CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? |
| (Y/N) |
|
|
| ||||||||||
| HAS THE GROUND WIRE BEEN CONNECTED? | (Y/N) |
|
|
|
|
|
|
|
|
| |||||
| HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? | (Y/N) |
|
| ||||||||||||
| ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? | (Y/N) |
|
|
CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED?
(Y/N) |
|
|
|
|
|
|
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? | (Y/N) |
|
| |||
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? | (Y/N) |
|
|
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? | (Y/N) | |||||||
ARE PROPER AIR FILTERS IN PLACE? | (Y/N) |
|
|
|
|
|
|
|
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? | (Y/N) | |||||||
DO THE FAN BELTS HAVE PROPER TENSION? | (Y/N) |
|
|
|
|
|
| |
HAS CORRECT FAN ROTATION BEEN CONFIRMED? | (Y/N) |
|
|
|
PIPING
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR AND INDOOR COILS,
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? | (Y/N) |
|
|
|
|
|
|
| |
LOCATE, REPAIR, AND REPORT ANY LEAKS. |
|
|
|
|
|
| |||
HAVE LIQUID LINE SERVICE VALVES BEEN OPENED? | (Y/N) |
|
| ||||||
HAVE SUCTION LINE SERVICE VALVES BEEN OPENED? | (Y/N) |
|
|
38AU