Carrier 38AU appendix Legend and Notes for Table, Unbalanced 3-PhaseSupply Voltage

Models: 38AU

1 56
Download 56 pages 45.1 Kb
Page 22
Image 22
Legend and Notes for Table 10

38AU

Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data

 

NOMINAL

VOLTAGE

 

COMPRESSOR

 

 

 

 

NO C.O. or UNPWRD C.O.

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

UNIT

RANGE

No. 1

No. 2

 

OFM

POWER SUPPLY

DISCONNECT SIZE

SUPPLY

 

 

 

 

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38AU

 

 

 

 

 

 

 

 

 

FLA

 

FUSE or

 

 

 

V---Ph---Hz

Min

Max

RLA

LRA

RLA

LRA

Qty

 

MCA

HACR

FLA

LRA

 

 

(ea)

 

 

 

 

 

 

 

 

 

 

 

BRKR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

25.0

164

25.0

164

3

 

1.5

60.8/60.8

80/80

63/63

337/337

D*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

12.2

100

12.2

100

3

 

0.8

29.9

40

31

206

Z*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

9.0

78

9.0

78

3

 

0.7

22.4

30

23

162

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

30.1

225

30.1

225

4

 

1.5

73.7/73.7

100/100

76/76

462/462

D*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

16.7

114

16.7

114

4

 

0.8

40.8

50

42

236

Z*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

12.2

80

12.2

80

4

 

0.7

30.3

40

31

168

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL

VOLTAGE

 

COMPRESSOR

 

 

 

 

w/ PWRD C.O.

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

UNIT

RANGE

No. 1

No. 2

 

OFM

POWER SUPPLY

DISCONNECT SIZE

SUPPLY

 

 

 

 

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38AU

 

 

 

 

 

 

 

 

 

FLA

 

FUSE or

 

 

 

V---Ph---Hz

Min

Max

RLA

LRA

RLA

LRA

Qty

 

MCA

HACR

FLA

LRA

 

 

(ea)

 

 

 

 

 

 

 

 

 

 

 

BRKR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

25.0

164

25.0

164

3

 

1.5

65.6/65.6

90/90

68/68

342/342

D*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

12.2

100

12.2

100

3

 

0.8

32.1

40

33

208

Z*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

9.0

78

9.0

78

3

 

0.7

24.1

30

25

164

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

30.1

225

30.1

225

4

 

1.5

78.5/78.5

100/100

82/82

467/467

D*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

16.7

114

16.7

114

4

 

0.8

43

50

45

238

Z*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

12.2

80

12.2

80

4

 

0.7

32

40

33

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legend and Notes for Table 10

LEGEND:

 

 

BRKR

---

Circuit breaker

CO

---

Convenient outlet

FLA

---

Full Load Amps

LRA

---

Locked Rotor Amps

MCA

---

Minimum Circuit Amps

 

 

Protection

NEC

---

National Electrical Code

PWRD CO

---

Powered convenient outlet

RLA

---

Rated Load Amps

UNPWR CO

---

Unpowered convenient outlet

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.The MCA values are calculated in accordance with The NEC. Article 440.

3.Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL). Standard 1995.

4.The 575--- v units are UL, Canada--- listed only.

5.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to de- termine the percentage of voltage imbalance.

Example: Supply voltage is 230-3-60

% Voltage Imbalance = 100 x

max voltage deviation from average voltage

 

average voltage

 

AB = 224 v

BC = 231 v

AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

 

 

3

3

 

 

=227

Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v

(BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

 

227

 

 

 

= 1.76%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

22