38AU
CHECK VOLTAGE IMBALANCE
AB |
|
| V | AC |
| V | BC |
| V | |||||
(AB + AC + BC)/3 = AVERAGE VOLTAGE = |
|
|
|
|
| V |
|
|
| |||||
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = |
|
|
|
| V |
|
|
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! CALL LOCAL POWER COMPANY FOR ASSISTANCE.
CHECK INDOOR UNIT FAN SPEED AND RECORD.
CHECK OUTDOOR UNIT FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
SUCTION PRESSURE | CIR 1: |
|
| CIR 2: |
|
|
|
| ||||||||||
SUCTION LINE TEMP | CIR 1: |
|
| CIR 2: |
|
|
|
| ||||||||||
LIQUID PRESSURE | CIR 1: |
|
| CIR 2: |
|
|
|
| ||||||||||
LIQUID LINE TEMP | CIR 1: |
|
| CIR 2: |
|
|
|
| ||||||||||
ENTERING OUTDOOR UNIT AIR TEMP |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
LEAVING OUTDOOR UNIT AIR TEMP |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
INDOOR UNIT |
|
|
|
|
| |||||||||||||
INDOOR UNIT |
|
|
|
| ||||||||||||||
INDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
INDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
COMPRESSOR 1 AMPS (L1/L2/L3) |
|
| / |
|
|
|
|
|
| / |
|
| ||||||
COMPRESSOR 2 AMPS (L1/L2/L3) |
|
| / |
|
|
|
|
|
| / |
|
|
NOTES:
Copyright 2010 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 | Printed in U.S.A. | Edition Date: 11/10 | Catalog No: |
|
| ||
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. | Replaces: |
56