Domestic Piping | 
  | 
  | |
SECTION IV - Domestic Piping | 
  | 
  | |
CAUTION  | 
  | ||
  | 
  | ||
General Piping Requirements  | 
  | 
  | |
The Temperature / Pressure relief valve  | |||
• All plumbing must meet or exceed all  | is not intended for constant duty, such as  | ||
local, state and national plumbing codes.  | relief of pressure due to normal thermal  | ||
• Use pipe dope or tape suitable for  | expansion.  | ||
  | 
  | ||
potable water.  | Water Hammer | ||
• Use isolation valves to isolate system  | |||
  | 
  | ||
components.  | Water hammer is the effect of sudden pres-  | ||
• Install unions for easy removal of the  | sure changes occurring in the domestic pip-  | ||
ing. These pressure changes are typically  | |||
PERFORMANCE PLUS from the sys-  | |||
the result of “fast acting” positive   | |||
tem piping.  | |||
valves closing. These types of valves can  | |||
  | |||
Domestic Supply Pressure | be typically found on dishwashers and  | ||
clothes washers.  | |||
For applications in which the domestic sup-  | The effects of water hammering can cause  | ||
ply pressure exceeds 70 psig it is recom-  | damage to system components and tank  | ||
mended to install a pressure reducing valve  | welds on the unit.  | ||
on the cold water supply.  | Installation of hammer arresters is recom-  | ||
Maintaining the cold water supply at or  | |||
mended at these types of appliances, which  | |||
below 70 psig will prevent normal thermal  | incorporate   | ||
expansion from repeatedly forcing the T&P  | valves. Consult the manufacturer of water  | ||
relief valve open.  | hammer arresters for recommendation on  | ||
  | sizing and installation requirements.  | ||
Thermal Expansion
If the cold water supply contains a backflow preventer, check valve and / or a pressure reducing valve, the installer must install a domestic thermal expansion tank on the cold water supply. (See Fig. 6 page 17)
Installing a thermal expansion tank will prevent normal thermal expansion from repeatedly forcing the T&P relief valve open.
When installing a thermal expansion tank ensure the charge pressure of the tank is equal to the cold water supply pressure at the point of installation. Consult the ther- mal expansion tank manufacturer’s instruc- tions for further information on installation and sizing.
Temperature / Pressure Relief Valve
The PERFORMANCE PLUS has a factory installed Temperature / Pressure Relief valve. Ensure the rating of the T&P relief valve is correctly sized as follows per AGA:
  | 
  | 
  | 
  | 
  | Model | AGA Rating | 
  | 
  | PG   | 100,000 Btu/hr  | 
  | 
  | PG   | 200,000 Btu/hr  | 
  | 
  | PG   | 200,000 Btu/hr  | 
  | 
  | PG   | 200,000 Btu/hr  | 
  | 
  | PG   | 200,000 Btu/hr  | 
  | 
  | 
  | 
  | 
  | 
14