Venting and Combustion Air Installation
-Must maintain 4 feet of clearance below and horizontally from doors and windows. See dimension A Fig. 17.
If the venting application is a vertical direct or
-The vent must terminate at least 3 feet above the roof and at least 2 feet higher than any portion of the building within 10 feet.
Multiple Vent Terminations
For multiple unit installation venting horizon- tally, it is recommended to vent as direct vent using the Horizontal Wall Thimble Kit or Horizontal Concentric Kit. The terminations of these installations must maintain the same horizontal centerline and be spaced a minimum 18 inches from center to center.
For multiple unit installation venting vertically, it is recommended to vent as direct vent using Triangle Tube Vertical Concentric Vent Kit. The concentric vent / combustion air termina- tions must maintain a minimum 18 inch spac- ing from vent centerline to vent centerline.
Locating the Combustion Air Inlet
When ducting outside combustion air directly to the appliance the installer must use the fol- lowing guidelines:
1.The total equivalent length of the air inlet duct should not exceed 100 feet as given in Table 2, page 33.
2.The installer must consider the following when determining the location of the com- bustion air inlet:
-The air inlet must terminate at least 12 inches above grade or projected snow line.
-The combustion air inlet must be locat- ed a minimum 12 inches from the vent termination. This does not apply to Horizontal Concentric Direct Venting
applications using the Horizontal Wall Thimble kit . See Fig. 23 page 35
-The combustion air inlet should not be located above the vent termination.
-The combustion air inlet must be locat- ed in the same pressure zone as the vent termination.
Venting Option - Non Direct Vent / Vertical
In this vent application the PERFORMANCE PLUS is vented vertically through the roof or an unused chimney using only approved 3 inch stainless steel vent material and using room air for combustion.
The installer should consider the following when choosing this vent option:
a.The vent system must contain a con- densate trap located no higher than 2 feet above the unit. As shown in Fig. 19 page 34.
b.The vent system must pitch back to the unit 1/4 inch per foot or as specified by the vent manufacturer.
c.Clearance to combustibles must be maintained per the vent manufacturer’s requirements. Refer to the vent manu- facturer’s installation instructions for additional details.
d.At a minimum, a
NOTICE
When using an unused chimney as a means of a raceway for the 3 inch vent, the surrounding space cannot be used to draw combustion air.
29