Maintenance Procedures
Check Burner Flame | Flame Signal |
Inspect the burner flame through the obser- vation port on the burner mounting plate.
If flame pattern is not fully blue and covers the entire burner surface, shut the unit down and allow it to cool thoroughly.
Close the manual gas valve on the gas sup- ply line and disconnect the gas piping to remove the burner assembly from the unit.
Remove the burner head mounting screws and remove the burner head. Inspect the head for deterioration. Use compressed air or a vacuum to clean the burner head.
Remove the venturi and gas valve assem- bly from the blower.
Use the vacuum cleaner or compressed air to clean the interior of the blower assembly. Inspect the blower blades to ensure they are clean and not damage.
The flame signal should be at least 0.6∝ Α. Refer to the PERFORMANCE PLUS
Check the ignitor for fouling or damaged insulation if a low flame signal is read.
Check ground wiring and continuity as a cause for low flame signal. Replace igni- tor if ground and continuity conditions are satisfactory.
Check Combustion Levels
Refer to page 53 of this manual for mea- suring combustion levels and burner adjustments.
Review With Owner
Ensure the owner understands the impor- tance to perform the maintenance schedule specified in this manual.
Remind the owner of the importance to call a licensed contractor should the unit or sys- tem exhibit any unusual behavior.