Hearth and Home Technologies SAPPH-D-CSB, 839-1390, 839-1440, 839-1460, SAPPH-D-CWL owner manual 203mm

Page 14

8 in.

1/4 in. (6mm)

(203mm)

 

 

 

 

 

7 in.

 

 

 

(178mm)

7 in.

 

6 in.

(178mm)

 

 

 

(152mm)

 

 

 

 

Fold Strap Here

Sheet Metal Screw

Wall Thimble

Figure 5.7

Wall Thimble Cover/Ceiling

Firestop as Required by Local

JurisdictionStrap

Figure 5.9

(NOTE: Some termination caps may cause the vent pipe to be off center on flashing). Ensure that proper clearances to combustible materials are maintained. If you are not using an approved termination cap with a built-in standoff on a building with vinyl siding, a vinyl siding standoff should be installed between the termination cap and the exterior wall (Figure 5.8). Follow manufacturer’s instructions for attaching the vinyl siding standoff to the horizontal termination cap. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. The vent terminal cap shall not be recessed into a wall or siding. Remove siding from the area where the standoff will be located.

Note: The attachment from the vent pipe to the vent termination cap must be sealed with silicone. Termination caps shall not be recessed into a wall or siding.

WARNING

Fire Hazard.

Exhaust Fume Risk.

Impaired Performance of Appliance.

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

WALL THIMBLE COVER

WALL THIMBLE

VINYL SIDING

Apply sealant to all four sides

SCREWS

Bolt horizontal top to vinyl standoff

SCREWS

Vinyl siding standoff with siding beneath removed

WARNING

Do NOT connect a pipe section to a termination cap without using the telescoping flue section found on the termination cap.

WARNING

Burn Risk.

Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

Figure 5.8

Step 5.

Place the wall thimble cover over the pipe assembly and slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the vent termination cap assembly. It is important that the vent pipe extend into the vent termination cap a sufficient distance so as to result in a minimum pipe overlap of 1-1/4 in. (32mm). Secure the connection between the vent pipe and the vent termination cap by attaching the two sheet metal strips extending from the vent termination cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section (Figure 5.9).

Page 14

Quadra-Fire · Sapphire · 250-7233H

September 1, 2008

Image 14
Contents Do Discardnot What to do if you smell gasDo not Discard this Manual Welcome to the Quadra-Fire Family Table of Contents 1Listing and Code Approvals Manufacturer Requirements Requirements for the Commonwealth of MassachusettsBELOW. Keep Clear of ALL Obstructions Getting Started Design & Installation ConsiderationsTools will apply to every installation Tools and Supplies NeededSelecting Appliance Location ClearancesTermination Locations 4Vent Termination Minimum ClearancesAlcove Applications Use of Elbows Vent InformationVenting Components Measuring StandardsHow to Use the Vent Graph Venting Guidelines Exception for Rear Vent KIT, Horizontal InstallationType a Up & Out Type B Rear Installations for Use with Rear Vent KitHorizontal Termination For installations requiring a vertical rise on the exterior 203mm Vertical Termination Direct Vent PipeStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Type a Up & Out Installations for Top Vent Configurations Existing Masonry ChimneyCut and bend flashing as needed to fit Sealant adhesive Flex Liner Flex Coupler Sheet Metal Screws Converting to LP Gas Gas InformationFuel Conversions Propane Natural GAS Gas Pressures PressureGas Connection Check for GAS LeaksStanding Pilot Ignition System Wiring Recommendation for WireConnecting to the Appliance Wire Size Max. LengthON/OFF Top and Rear Vent Conversion Appliance SetupRemove Shipping Materials At the TOP of the appliance, with exceptions notedReplace Burner Orifice for Horizontal Vent Configurations 059 53 DMS 096 41DMS Grille Cover Plate InstallationAccessories For Both Quartet and Solitaire Fronts Front InstallationFronts are shipped attached to the face Quartet Door AlignmentQty Description Hearth Legs InstallationPositioning the Logs Blower from front Glass Door Assembly Installation Blower InstallationMineral Wool Page Blower For TOP or Rear Vent Installations Damper AdjustmentShutter Adjustment Make adjustmentControls Operating InstructionsBefore Lighting Appliance For Your Safety Read Before Lighting Lighting ApplianceAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Troubleshooting Symptom Possible Cause Corrective ActionBe Placed in this Opening Maintaining and Servicing Appliance After servicingMaintenance Tasks Inspect Necessary. USE Caution When CLEANING/HANDLING Ceramic BurnerAppliance Dimension Diagram Reference MaterialsQuadra-Fire · Sapphire · 250-7233H September 1 Vent Components DiagramMm inner pipe 6-5/8 in mm outer pipe Vent Components List HHT SL-PTermination Caps & Kits Sapphire Item # DescriptionService Parts cont’d Hinge Assembly Accessories Cast Parts Individual PiecesService and Maintenance Log Date of Service Performed By Description of ServiceWarranty Policy Hearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHearth & Home Technologies Limited Warranty Cont’d Dealer Telephone SapphireContact Information