| Builders |
|
|
|
|
| Opening |
|
| (575mm max Valour Dimension |
|
5570mm min | Fireplace | 560mm min | 595mm max | Regalia ONLY ) | |
Opening | |||||
|
390mm min
490mm max
584mm min
SURROUND OR FINISHED
WALL FACE
570mm minimum | 560mm minimum 590mm maximum | Solid, non combustible hearth | ||
HEARTH |
|
|
| to support the boiler, |
|
|
| as specified in BS 5871. |
LEVEL
305mm minimum
Fig. 9
5.0Site Requirements
5.1Builders Opening (Fig. 9)
1.The boiler unit is designed to fit within a standard builders opening, the minimum dimensions of which are as shown.
Height 570mm
Width 584mm
Depth 305mm
2.The opening should be soundly constructed of brick,
3.The base of the opening should be sound and non- combustible and must be flat and level.
4.The base of the builders opening should be at the same height as the finished level of the hearth.
IMPORTANT: If a false chimney breast is intended to house the boiler, a simulated builders opening, within the breast, must be provided.
5.The builders opening must not communicate with voids, pipe ducts or spaces other than the room in which the appliance is situated.
5.2Location
1.The appliance must be installed in the living space of a dwelling. It is recommended that it is a ground floor location.
2.Restrictions to the siting of the appliance are covered by BS 5546. The appliance may not be installed in bathrooms or shower rooms. bedrooms or bed sitting rooms.
5.3Fireplace Opening & Surround
1.If a fireplace surround is to be used, it must be centrally placed and have opening sizes as shown in Fig. 9.
5.4Firefont Frame Extension Kit
1.To accommodate the firefront there must be at least 95mm from the surround or finished face to the front of the boiler.
2.If necessary this can be increased by the use of Frame Extension Kits. Each extension increases the effective depth of the opening by 50mm.
3.See the instructions supplied with the firefront for full details.