Fault Finding Solutions Sections
12.0 Fault Finding
AIs there 230V at:
1. |
|
|
| NO |
|
|
|
|
|
|
|
|
Main terminals L and N | Check electrical supply |
|
|
|
| |||||||
NO |
|
|
|
| ||||||||
2. |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |||
Main terminal fuse |
|
| NO |
| Replace fuse |
|
|
|
|
| Display | |
|
|
|
|
|
|
|
|
|
| |||
3. |
|
|
|
|
|
|
|
|
| illuminated | ||
|
|
|
|
|
|
|
|
| ||||
PCB - X1 connector |
| Check wiring |
|
|
|
| ||||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| ||
| terminals 1,2 |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
BCheck all system wiring and pump
CService Reset
Condensate Pump does not run On Reset is there 230V at:
NO
Replace PCB
1. | PCB - X3 connector terminals 5 & | NO | ||
| 6 for at least 2 seconds |
|
| |
|
|
|
|
|
|
|
|
|
|
2. | Condensate Pump terminals for at | NO | ||
| least 2 seconds |
|
| |
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
| YES | |
| Condensate Pump runs | |||
|
|
| ||
|
|
|
|
|
Replace PCB
Replace wiring
Replace Cond. Pump
Condensate drain system blocked
NO
Replace Float Switch
YES
Clean condensate drain system
D
E
| Fan connections correct at fan. PCB - | YES | |||
| X2 connector, is 230V AC across | ||||
|
|
|
| ||
| terminals 5 & 7 |
|
|
| |
|
|
|
|
|
|
|
| NO |
|
|
|
|
|
|
|
| |
|
|
|
| ||
E20 - Temperature sensor faulty. |
|
|
| ||
Cold resistance approximately |
| NO | |||
10kΩ @ 25° C |
| ||||
|
|
| |||
(resistance reduces with increase in temp.) |
|
|
| ||
E28 - Incorrect PCBfitted |
|
|
| ||
|
|
|
|
|
|
Fan jammed or faulty winding
Replace PCB
Replace sensor or PCB(E28)
YES
Replace fan
F 1.
Check and correct the connection of the tube between the venturi and gas valve
G
2. |
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Gas at burner |
| Ensure gas is on and purged |
|
|
|
|
| Replace PCB |
|
|
| ||||||||||
|
|
|
|
| NO |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
| |
|
|
|
|
| PCB - X3 connector is 230V AC across |
|
|
|
|
|
|
| |||||||||
|
|
|
|
| Replace gas valve |
|
| ||||||||||||||
|
|
|
|
|
|
|
| terminals 1 & 2 |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
| voltage at PCB - X2 connector is |
| NO |
|
|
|
| ||||||
Check and correct if necessary |
|
|
|
|
|
|
|
| |||||||||||||
|
|
| Replace PCB |
| |||||||||||||||||
1. | Ignition electrode and lead |
|
| YES |
| 110V AC across terminals 2 & 5 |
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
| (Note: from multimeter connect |
|
|
|
|
|
|
| |||||||||||
2. | Electrode connection |
|
|
|
|
| YES |
|
|
|
| ||||||||||
|
|
|
| ‘common’ to 2 & ‘volts’ to 5) |
| Replace igniter |
| ||||||||||||||
3. Spark gap and position |
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
| Check wiring |
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
36© Baxi Heating UK Ltd 2009