State Industries STC-074 specifications Gas Valve

Page 11

SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

The supply gas pressure is normally measured at the gas valve inlet gas pressure tap,

if available, when the gas is flowing. The manifold gas pressure

is measured at the manifold pressure tap of the gas valve when the gas is flowing.

Gas valves used are 24 volt AC combination-step opening gas valves. They incorporate the main valve and gas pressure regulator into one body. The Low Gas Pressure Switch, the Supply Gas Inlet, and the Supply Gas Pressure Tap are shown in the Inlet View to the right.

The top view of the gas valve, shown on the right, shows the Main Gas Regulator, Manifold Pressure Tap, Top Knob, and the Limited Bleed Vent Port. The main gas regulator is found under the silver cap screw. It is factory preset to 3.5 inches W.C. and

adjusts gas pressure output from 3.0 to 5 inches water column. Caution: Always test the manifold pressure at the outlet when the gas is flowing.

Gas Valve

Inlet View

Top View

©2003

10

Technical Training Department

Ashland City, Tennessee

Image 11
Contents Service Handbook Table of Contents SBN Service Handbook Introduction Custom Commercial Storage Tank Model Number Break Down QualificationsTop and Front Views of Minimum Clearances To Combustibles Installation ConsiderationsRequired Exterior Clearances Exterior ClearanceComb AIR Make-Up Air Direct Communication Not Direct Vent Make-Up Air Horizontal Ducts Make-Up Air Vertical DuctsAir for Combustion Flammable Items Contaminated AirGas Valve Outlet View Venting Atmospheric Multiple Heaters VentingNine Rules for Good Vents SBN Tank Type Commercial GAS Water Heater Service Handbook SBN Tank Type Commercial GAS Water Heater Service Handbook Multiple Gas Fired Tank-Type Heaters Type B GAS VentTechnical Dataventing Top View SequenceFront View of Water Heater SBN Tank Type Commercial GAS Water Heater Service Handbook HSI Integrated Ignition Control Board HSI Lower Front View of SBN Water HeaterECO Wiring DiagramElectrical Sequence of SBN Water Heater Operation PRE-SERVICE Checklist Water Heater Control Ignition Control Board ConditionsTest 2 Polarity Check Flash Codes of Diagnostic IndicatorTest 3 Continuity Check High Limit ECO Test 2 Polarity CheckIs not present Test 4 Upper Temperature Probe Continuity CheckTest 3 Continuity Check of High Limit ECO Is indicatedCheck to Inducer Test on Ignition Board 4 Pin Receptacle E4 Test 5 Calling for Heat no Inducer OperationWater Heater Control VAC Check of Blower Prover/Low Gas Pressure Circuit Test 6 Inducer ON-NO IgnitionVoltage is not present between E4, Pin Test of Igniter and gas valve circuit Test 8 Igniter Heats no Main BurnerContinuity Check Of Gas Valve Coil Test 9 Igniter Heats no Main BurnerFlame Prover Circuit Check Test 10 Main Burner Ignition for Less than 5 SecondsIf… Then Test 11 Water Heater Shutting OFF below SettingDisplay Lights on Integrated Heater Control ECO SBN Tank Type Commercial GAS Water Heater Service Handbook Technical Training Department 120 154 180 199 200A 250A 275A 310A 366A 400A General Questions and Answers SBN Tank Type Commercial GAS Water Heater Service Handbook Draft Proving Pressure Switch Table