State Industries STC-074 Test 9 Igniter Heats no Main Burner, Continuity Check Of Gas Valve Coil

Page 35

SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

TEST 9 - IGNITER HEATS – NO MAIN BURNER

Conditions:

ƒTest 8 completed then:

ƒTurn off power

ƒDisconnect wires from gas valves

TEST 9

Continuity Check Of Gas Valve Coil

If…

...then

 

 

 

Œcheck meter scale setting to read between 550

 

meter reads 0 or 1

and 650 Ohms

 

 

 

Œreplace Gas Valve

 

 

meter indicates pilot and main coil have

Œvalve should be okay

 

 

Œstill no gas to main burner, then coil may be

 

continuity

 

stuck - Replace Valve

 

 

 

 

 

 

 

 

 

©2003

34

Technical Training Department

Ashland City, Tennessee

Image 35
Contents Service Handbook Table of Contents SBN Service Handbook Introduction Custom Commercial Storage Tank Model Number Break Down QualificationsTop and Front Views of Minimum Clearances To Combustibles Installation ConsiderationsRequired Exterior Clearances Exterior ClearanceComb AIR Make-Up Air Direct Communication Not Direct Vent Make-Up Air Horizontal Ducts Make-Up Air Vertical DuctsAir for Combustion Flammable Items Contaminated AirGas Valve Outlet View Venting Atmospheric Multiple Heaters VentingNine Rules for Good Vents SBN Tank Type Commercial GAS Water Heater Service Handbook SBN Tank Type Commercial GAS Water Heater Service Handbook Multiple Gas Fired Tank-Type Heaters Type B GAS VentTechnical Dataventing Top View SequenceFront View of Water Heater SBN Tank Type Commercial GAS Water Heater Service Handbook HSI Integrated Ignition Control Board HSI Lower Front View of SBN Water HeaterECO Wiring DiagramElectrical Sequence of SBN Water Heater Operation PRE-SERVICE Checklist Water Heater Control Ignition Control Board ConditionsTest 2 Polarity Check Flash Codes of Diagnostic IndicatorTest 3 Continuity Check High Limit ECO Test 2 Polarity CheckIs not present Test 4 Upper Temperature Probe Continuity CheckTest 3 Continuity Check of High Limit ECO Is indicatedCheck to Inducer Test on Ignition Board 4 Pin Receptacle E4 Test 5 Calling for Heat no Inducer OperationWater Heater Control VAC Check of Blower Prover/Low Gas Pressure Circuit Test 6 Inducer ON-NO IgnitionVoltage is not present between E4, Pin Test of Igniter and gas valve circuit Test 8 Igniter Heats no Main BurnerContinuity Check Of Gas Valve Coil Test 9 Igniter Heats no Main BurnerFlame Prover Circuit Check Test 10 Main Burner Ignition for Less than 5 SecondsIf… Then Test 11 Water Heater Shutting OFF below SettingDisplay Lights on Integrated Heater Control ECO SBN Tank Type Commercial GAS Water Heater Service Handbook Technical Training Department 120 154 180 199 200A 250A 275A 310A 366A 400A General Questions and Answers SBN Tank Type Commercial GAS Water Heater Service Handbook Draft Proving Pressure Switch Table