Cornelius 10 Operate CONT’D, Refrigeration System, Temperature Sensing, Device and HIGH-PRESSURE

Page 48

Trouble

Probable Cause

Remedy

COMPRESSOR DOES NOT

I. Hi-pressure cutout tripped

I. Reset pressure switch (see

OPERATE (CONT’D)

(remote Cooling Unit only).

REFRIGERATION SYSTEM

 

 

TEMPERATURE SENSING

 

 

DEVICE AND HIGH-PRESSURE

 

 

CUTOUT SWITCH in

 

 

OPERATORS INSTRUCTIONS

 

 

SECTION.

J.No voltage to control board.

J.Check for loose or broken wiring. Check 240/24 VAC power transformer for 24 VAC output. (see NOTE below)

K.

Inoperative compressor.

K.

Replace compressor.

L.

Temperature sensor is shorted

L.

Check for loose, broken, or

 

or open circuit.

 

disconnected wire or plug at

 

 

 

pre-cool coil. Repair or replace

 

 

 

wire. Confirm which temperature

 

 

 

sensor has failed by using the

 

 

 

Aurora Series

 

 

 

System Analyzer (P/N

 

 

 

309197-000).

M.

Loose or broken wire to

M.

Repair or replace wire.

 

satellite board from ice sensor

 

 

 

probe on main control board

 

 

 

(see low-voltage system wiring

 

 

 

diagram).

 

 

NOTE: The 240/24 VAC power transformer has an overload reset button located on its 24 VAC output side (see Figure 3). An overload on the transformer will cause its reset button to pop out disrupting the 24 VAC output to the main control board. Overload reset button must be pressed in to restore 24 VAC output.

COMPRESSOR OPERATES

A. Cooling capacity is exceeded

CONTINUOUSLY BUT DOES

by overdrawing.

NOT FORM SUFFICIENT ICE

 

BANK.

 

A.Reduce amount of drinks drawn per given time.

B.Standard Cooling Unit with condenser coil and fan assembly-- Cooling Unit located in excessively hot area or air circulation through condenser coil is restricted.

C.Remote Rooftop Condenser Coil and Fan Assembly-- Air circulation through condenser coil is restricted.

B.Relocate unit or check and if necessary, clean air filter as instructed.

C.Check and if necessary, clean condenser coil as instructed.

D.Insufficient refrigerant charge. D. Check refrigeration system with gage set and Aurora

Series System Analyzer

(P/N 309197000). Find and repair refrigeration leak, then replenish refrigerant charge.

43

300381000

Image 48 Contents
AURORAR10,000 Cooling Unit This Document Contains Important InformationTable of Contents Table of Contents cont’d Table of Contents cont’d LOOSE-SHIPPED Parts General Description Cooling Unit DescriptionDesign Data Cooling Unit Model NumbersSystem Theory of Operation Remote Condenser Coil and FAN ASS’Y Data P/NFlow Diagram Typical Installation Unpacking and Inspection Identification of LOOSE-SHIPPED PartsSelecting Location Cooling UnitInstalling Cooling Unit Remote Condenser Coil and FAN ASS’Y if ApplicablePlacing Cooling Unit in Location Connecting Electrical Power Circuit to Cooling Unit 24VAC Power TransformerCooling Unit factory warranty Connecting Plain Water Inlet Supply Line to Cooling Unit Connecting CO2 Inlet Supply Line to Cooling UnitPlacing Cooling Unit in Operating Position Cooling Unit Space RequiredPreparing Cooling Unit for Operation OperationStarting Cooling Unit Refrigeration System Starting Carbonated Water Circulating PumpActivating Syrup Systems Dispensing Station Adjustments Installing Line Identification LabelAdjusting Water Flow Rate Leak Check and Insulating Cooling Unit Outlet LinesThis page Left Blank Intentionally Cooling Unit Refrigeration Power Switch Cooling Unit Carbonator Motor SwitchCooling Unit Circulating Motor Switch Operating ControlsAdjustments Cleaning and Sanitizing Cooling Unit MaintenanceCleaning CO2 GAS Check Valves Preparing Cooling Unit for SHIPPING, STORING, or Relocating Periodic InspectionPeriodic Cleaning Cleaning Condenser CoilChecking ICE Water Bath Changing ICE Water Bath FAN Assembly Item 4 300381000 Carbonator Liquid Level Control Switches Carbonated Water Circulating Pump Motor Lubrication Primary CO2 RegulatorSecondary CO2 Regulators Index Part NameAdjusting Carbonators Tanks Liquid Levels Daily Cleaning of UnitWater Flow Rate Sanitizing POST-MIX Syrup Systems Wash Syrup SystemsFlush Syrup Systems Sanitize Syrup Systems Water Flush Syrup SystemsPurge Water OUT of Syrup Systems Restore Operation Cleaning CO2 System GAS Check Valves Connecting External Carbonator to Cooling UnitSyrup Flavor Change Carbonators CO2 Inlet Lines CO2 GAS Check Valve300381000 300381000 Wiring Diagram LOW-VOLTAGE System Model Number Wiring Diagram HIGH-VOLTAGE System This page Left Blank Intentionally WATER-TO-SYRUP ‘RATIO’ Dispensed Drink TOO LOW or TOO High Dispensed Product Carbonation TOO LOWComes OUT Dispensing Valve Clear But Foams in CUP Only Carbonated Water aOnly Carbonated Water Dispensed CONT’DOnly Syrup Dispensed Carbonator MotorsOperate Refrigeration Power Erratic CyclingCarbonator Water Pump MotorTemperature Sensing Operate CONT’DRefrigeration System Device and HIGH-PRESSUREBank CONT’D Refrigeration Flow Diagram Commpressor OperatesContinuousls but does Not Form Sufficient ICEWarranty Page One Cornelius Place Anoka, Minnesota 612 800