APC Cooling Unit Manual: ACRD100 and ACRD101 Official Guide

Page 24

Stop the cooling unit

Path: Main > On/Standby

Press the ENTER key to change the setting to Standby. The cooling unit enters the standby mode.

Electrical Hazard: The Standby option does not remove power from the cooling unit. You must disconnect power at the mains to remove power from the cooling unit.

General Configuration

The cooling group configuration options are set during the commissioning of the cooling units in the cooling group.

Caution: This procedure must be performed by APC authorized personnel only. Changing the settings incorrectly can cause malfunctions to your cooling unit.

Cooling unit configuration

Path: Main > Configure Unit > General

Use the General menu to set the start-up delay, idle on leak, and refrigerant fill settings.

Start-up Dly (Start-up Delay). The delay begins when the cooling unit is started and initialized. The cooling unit cannot begin operation until this delay expires. Use the start-up delay to restart equipment sequentially after a scheduled downtime or a power outage.

Idle On Leak. When set to Yes, the cooling unit will enter idle mode if a Water Detection Fault activates. Set to No to disable the cooling unit from entering idle mode if a leak is detected.

Note: The leak sensor (APC part number AP9325) is optional.

Note: There are three alarms that will cause the cooling unit to enter idle mode:

Water Detection Fault (when Idle On Leak is set to Yes)

Condensate Pump Fault

Cooling Failure

See “Alarm messages and suggested actions” on page 29 for more information on alarms.

Refrig Fill. Set to Start to add refrigerant to the system. This setting turns on the compressor and sets the fans to maximum speed until the compressor suction pressure drops below 50 psig for two minutes, twenty minutes elapse, or the property setting is changed to Abort.

Caution: The Refrig Fill setting is intended only for charging the unit with refrigerant.

16

InRow RD 10 kW Air Cooled Operation and Maintenance

Image 24
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Symbols used in this manual Cross-reference symbol used in this manualOverview Safety Inspection Checklists Initial inspection checklistEnsure that Electrical inspection checklist Mechanical inspection checklist Ensure thatUser interface inspection checklist Start-up inspection checklistFinal inspection checklist While the cooling unit is operating, ensure thatCharging With Refrigerant Calculating R410A chargeInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Oil charging procedure Compressor Oil ChargeInRow RD 10 kW Air Cooled Operation and Maintenance Operation Display InterfaceUsing the Display Interface Scrolling status screensStatus Screen Name Status Information Displayed Main menu screensNavigating the main menu Navigating the sub-menusUsing the Path statement Password entryStart the cooling unit General Configuration Cooling unit configurationStop the cooling unit Cooling Group Configuration Configure the cooling groupContacts View the state of input and output contactsConfigure Modbus Identify the cooling unitControl the Environment SetpointsPID settings Loop Behavior PID Tuning Correction Tune the PID loopControl Method Proportional Integral Derivative Service intervals Run hoursThresholds Password and time-out Date and timeAdjust display settings Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusCooling group status About the cooling unitEvent Log View the event logClear the event log Respond to Alarms View active alarmsClear active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more Quick Configuration TCP/IP configuration methodsOverview APC Device IP Configuration Wizard Bootp & Dhcp configurationIni file utility NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp ModbusRecover From a Lost Password Monthly Preventive Maintenance CleanlinessEnvironment Mechanical ElectricalSemi-Annual Preventive Maintenance Functional testsTroubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective ActionPage Page APC Worldwide Customer Support 990-3212A-001 11/2009