Alarm Message

Severity

Action Required

 

 

 

High Suction Pres

Warning

• Check the air filter and fans for obstructions

(High Suction Pressure)

 

• If the problem persists, contact APC at a number on the back cover

 

 

of this manual.

 

 

 

Fan Num Fault

Warning

• A hardware failure exists. For assistance, contact APC at a number

(Fan # Fault)

 

on the back cover of this manual.

 

 

 

Water Detected

Warning

• Identify the source of the leak. Water could be from the condensate

 

 

pump, condensate carryover from the evaporator, or condensation.

 

 

• For assistance, contact APC at a number on the back cover of this

 

 

manual.

 

 

 

Conds Pump Fault

Warning

• A hardware failure exists. For assistance, contact APC at a number

(Condensate Pump Fault)

 

on the back cover of this manual.

 

 

 

Pan Full

Critical

• Empty the pan and make sure the drain line is not clogged.

(Condensate Pan Full Fault)

 

• If the problem persists, contact APC at a number on the back cover

 

 

of this manual.

 

 

 

Fan PwrSp Fault

Critical

• Make sure the power source is connected properly and the power is

(Upper Fan Power Supply

 

on.

Fault)

 

• If the problem persists, contact APC at a number on the back cover

 

 

of this manual.

 

 

 

Fan PwrSp Fault

Warning

• Make sure the power source is connected properly and the power is

(Lower Fan Power Supply

 

on.

Fault)

 

• If the problem persists, contact APC at a number on the back cover

 

 

of this manual.

 

 

 

Air Fltr RnHr Violation

Warning

• Reset the Air Filter Run Hours after the air filter is cleaned or

(Air Filter Run Hours

 

replaced.

Violation)

 

 

 

 

 

Grp Comm Fault

Critical

• Make sure the number of cooling units in the group is configured

(Group Communication Fault)

 

properly and the A-Link connections between cooling units are

 

 

correct.

 

 

• Make sure the system is receiving power and is connected properly.

 

 

• A hardware failure exists. For assistance, contact APC at a number

 

 

on the back cover of this manual.

 

 

 

Sply Air High Temp

Warning

• Make sure the Supply Air threshold is set correctly in the Set Unit

(Supply Air High Temperature

 

Threshlds screen.

Violation)

 

• If the problem persists, contact APC at a number on the back cover

 

 

of this manual.

 

 

 

Rtn Air High Temp

Warning

• Make sure the Return Air threshold is set correctly in the Set Unit

(Return Air High Temperature

 

Threshlds screen.

Violation)

 

• If the problem persists, contact APC at a number on the back cover

 

 

of this manual.

 

 

 

Filter DP Sensor Failure

Warning

• Make sure the sensor is connected properly.

 

 

• If the problem persists, replace the sensor or contact APC at a

 

 

number on the back cover of this manual.

 

 

 

Suction Temperature Sensor

Warning

• Make sure the sensor is connected properly.

Failure

 

• If the problem persists, replace the sensor or contact APC at a

 

 

number on the back cover of this manual.

 

 

 

30

InRow RD 10 kW Air Cooled Operation and Maintenance

Image 38
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Overview Symbols used in this manualCross-reference symbol used in this manual Safety Ensure that Inspection ChecklistsInitial inspection checklist Electrical inspection checklist Mechanical inspection checklist Ensure thatFinal inspection checklist User interface inspection checklistStart-up inspection checklist While the cooling unit is operating, ensure thatCharging With Refrigerant Calculating R410A chargeInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Oil charging procedure Compressor Oil ChargeInRow RD 10 kW Air Cooled Operation and Maintenance Operation Display InterfaceStatus Screen Name Status Information Displayed Using the Display InterfaceScrolling status screens Main menu screensNavigating the main menu Navigating the sub-menusStart the cooling unit Using the Path statementPassword entry Stop the cooling unit General ConfigurationCooling unit configuration Contacts Cooling Group ConfigurationConfigure the cooling group View the state of input and output contactsConfigure Modbus Identify the cooling unitControl the Environment SetpointsPID settings Control Method Proportional Integral Derivative Loop Behavior PID Tuning CorrectionTune the PID loop Thresholds Service intervalsRun hours Password and time-out Date and timeAdjust display settings Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusCooling group status About the cooling unitClear the event log Event LogView the event log Clear active alarms Respond to AlarmsView active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more Overview Quick ConfigurationTCP/IP configuration methods Ini file utility APC Device IP Configuration WizardBootp & Dhcp configuration NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp ModbusRecover From a Lost Password Environment Monthly Preventive MaintenanceCleanliness Mechanical ElectricalSemi-Annual Preventive Maintenance Functional testsTroubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective ActionPage Page APC Worldwide Customer Support 990-3212A-001 11/2009