APC ACRD100, ACRD101 manual Identify the cooling unit, Configure Modbus

Page 26

Type. Set the rack deployment strategy for the cooling units of this cooling group:

Spot: The cooling unit is used as a stand-alone unit.

In-Row: Air flow is not ducted. Hot-aisle air is cooled and the cooled-air supply is shared by all loads in the row.

RACS (Rack Air Containment System): Air flow in the enclosure is controlled by a ducting system fitted to the enclosure.

HACS (Hot Aisle Containment System): Air flow in the room is controlled by enclosing the hot air aisle. The loads share an enclosed common hot aisle.

Capacity Ctrl. Set the capacity control of the cooling unit:

Disc (Discrete): The cooling unit operates as a room air conditioner. The evaporator fan speed will remain constant at the user setting and the compressor will cycle on and off to maintain the cool setpoint.

Note: The Disc mode is only available in a Spot cooling configuration.

Prop (Proportional): The cooling unit matches the cooling output to the load demand. This is accomplished using hot gas adjustment and fan speed control. Load demand is determined by the cool setpoint and the temperature sensor at the rear of the cooling unit (in Spot configurations) or the temperature sensor at the front of the load rack (in In-Rowand RACS configurations).

Fan Cntrl. This selection allows air flow to be controlled automatically by the cooling unit or manually by user-selected fan speed preference. This property only applies to Spot (Proportional), InRow, RACS and HACS deployments.

Auto: Air flow is automatically controlled by the unit.

Manual: the air flow is fixed to the value of the Fan Speed Preference property. See page 19 for more information.

Identify the cooling unit

Path: Main > Set Identification

The Set Identification menu contains settings that identify the name and location of the cooling unit.

Name. Assign a Name of up to 40 alpha-numeric characters to this cooling unit. Location. Enter the Location, up to 40 alpha-numeric characters, of the cooling unit.

Note: Only the first 19 characters (of the 40 that are possible to enter) will display on the display interface. You must use Telnet , the Control console or the Web to access all 40 characters. See page 38 for more information.

Configure Modbus

Path: Main > Configure Modbus

Use the Configure Modbus menu to set up communication between the cooling unit and the building management system.

Modbus. Enable or Disable the Modbus communication protocol.

Target Id. Each Modbus device must have a unique target identification number. Enter a unique number, from 1 to 247, for this cooling unit.

Baud Rate. Choose either 9600 bps or 19200 bps.

Fixed settings: 8 data bits, no parity, 1 stop bit. These settings cannot be modified.

18

InRow RD 10 kW Air Cooled Operation and Maintenance

Image 26
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Overview Symbols used in this manualCross-reference symbol used in this manual Safety Ensure that Inspection ChecklistsInitial inspection checklist Electrical inspection checklist Mechanical inspection checklist Ensure thatFinal inspection checklist User interface inspection checklistStart-up inspection checklist While the cooling unit is operating, ensure thatCharging With Refrigerant Calculating R410A chargeInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Oil charging procedure Compressor Oil ChargeInRow RD 10 kW Air Cooled Operation and Maintenance Operation Display InterfaceStatus Screen Name Status Information Displayed Using the Display InterfaceScrolling status screens Main menu screensNavigating the main menu Navigating the sub-menusStart the cooling unit Using the Path statementPassword entry Stop the cooling unit General ConfigurationCooling unit configuration Contacts Cooling Group ConfigurationConfigure the cooling group View the state of input and output contactsConfigure Modbus Identify the cooling unitControl the Environment SetpointsPID settings Control Method Proportional Integral Derivative Loop Behavior PID Tuning CorrectionTune the PID loop Thresholds Service intervalsRun hours Password and time-out Date and timeAdjust display settings Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusCooling group status About the cooling unitClear the event log Event LogView the event log Clear active alarms Respond to AlarmsView active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more Overview Quick ConfigurationTCP/IP configuration methods Ini file utility APC Device IP Configuration WizardBootp & Dhcp configuration NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp ModbusRecover From a Lost Password Environment Monthly Preventive MaintenanceCleanliness Mechanical ElectricalSemi-Annual Preventive Maintenance Functional testsTroubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective ActionPage Page APC Worldwide Customer Support 990-3212A-001 11/2009