Quantity of R410A in 1/2 in OD liquid line: (area) x (length in ft) x (density): 0.0010554 (ft2) x L (ft) x 61.0 (lbm/ft3)

Density of liquid R410A at 40.6°C (105°F) and 260 psig: 0.98 g/cm3 (61.0 lbm/ft3 ) Cross sectional area for 1/2 in OD pipe is 0.0010554 ft2.

Liquid line charge for 1/2 in OD ACR copper tube: 0.095 kg/m (0.0644 lb/ft).

Cross sectional area for 5/8 in OD pipe is 0.001619 ft2.

Quantity of R410A in 5/8 in OD liquid line: (area) x (length in ft) x (density): 0.001619 (ft2) x L (ft) x 61.0 (lbm/ft3).

Liquid line charge for 5/8 in OD ACR copper tube: 0.146 kg/m (0.099 lb/ft).

Example:

Calculate the total R410A charge for an FCB5 condenser with 25 ft of 1/2 in OD liquid piping. Minimum outdoor design temperature is -28.9°C (-20°F).

Note: Imperial units are used in this example.

Total R410A charge: 3.5 + 4.9 + 13.6 + (25*0.0644) = 23.6 lb.

8

InRow RD 10 kW Air Cooled Operation and Maintenance

Image 16
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Cross-reference symbol used in this manual Symbols used in this manualOverview Safety Initial inspection checklist Inspection ChecklistsEnsure that Electrical inspection checklist Mechanical inspection checklist Ensure thatUser interface inspection checklist Start-up inspection checklistFinal inspection checklist While the cooling unit is operating, ensure thatCharging With Refrigerant Calculating R410A chargeInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Oil charging procedure Compressor Oil ChargeInRow RD 10 kW Air Cooled Operation and Maintenance Operation Display InterfaceUsing the Display Interface Scrolling status screensStatus Screen Name Status Information Displayed Main menu screensNavigating the main menu Navigating the sub-menusPassword entry Using the Path statementStart the cooling unit Cooling unit configuration General ConfigurationStop the cooling unit Cooling Group Configuration Configure the cooling groupContacts View the state of input and output contactsConfigure Modbus Identify the cooling unitControl the Environment SetpointsPID settings Tune the PID loop Loop Behavior PID Tuning CorrectionControl Method Proportional Integral Derivative Run hours Service intervalsThresholds Password and time-out Date and timeAdjust display settings Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusCooling group status About the cooling unitView the event log Event LogClear the event log Respond to Alarms View active alarmsClear active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more TCP/IP configuration methods Quick ConfigurationOverview Bootp & Dhcp configuration APC Device IP Configuration WizardIni file utility NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp ModbusRecover From a Lost Password Cleanliness Monthly Preventive MaintenanceEnvironment Mechanical ElectricalSemi-Annual Preventive Maintenance Functional testsTroubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective ActionPage Page APC Worldwide Customer Support 990-3212A-001 11/2009